- 17 -
System Troubleshooting Procedure
1) Depending upon the switching method used for the Feedline Voltage Controller model FVC-1,
make sure the jumper inside the unit is set to respond to your method of switching, BCD voltage
or 1-of-4 ground switching. By default, the FVC-1 is set for BCD voltage control with the jumper
JMP1 connecting to the two pins below EXT. If you are using your own 4 position grounding
switch for FVC-1 control, JMP1 inside the FVC-1 must be reset to jumper setting INT.
Additional information on the connections to the FVC-1 unit is available in this manual.
Only when a DX Engineering CC-8 or CC-8A Switch Control Console unit or other BCD
voltage control is used, the JMP1 jumper must be set to EXT. Also check that the connections
from the BCD voltage source and the FVC-1 control. From the CC-8 or CC-8A to the FVC-1,
connections correspond to A to NEG, B to POS, and G to G. When rotating the switch from
position 1, 2, 3, and 4, or 5, 6, 7 and 8, if all LEDs light normally, measure BCD output
voltages. Normally, +12 to 18 Vdc is output on the rear panel green 5-pin connector pins
reference to ground pin G. Voltage measured may be as high as +18 Vdc unloaded. If the CC-8
or CC-8A has only a couple LEDs lit with the control cable disconnected, then it may have
sustained lightning pulse damage and will need to be repaired or replaced. A new CC-8A is
available separately from DX Engineering.
After checking the FVC-1 control switching, continue troubleshooting the RBS with the entire
system connected normally.
2) With the main Reversible Beverage System feedline connected to the FVC-1, test the voltages
between the OUT terminal and the ground G terminal of the FVC-1, while switching through
the four positions. The sequence that should be measured is 0 V, - 12 Vdc, +12 Vdc, and 12
Vac. The voltage will read on a multi-meter at about 6 to 7 V because they are half-wave
rectified, pulsating dc. These are the same voltages that are being sent out onto the feedline.
Only -12 Vdc is used to switch a single RBS.
If the voltages measured are not normal with the feedline line connected, then disconnect the
feedline and retest. If voltages are still incorrect, there is a problem with FVC-1 power supply
(must be 12 Vac, NOT 12 Vdc), jumpering (see #1 above), or switching control (wrong or bad
connection). Correct FVC-1 operation as discussed above.
If voltages were wrong with the feedline connected but are now okay with the feedline
disconnected from the FVC-1, this indicates:
a) A short circuit in the feedline,
b) A bad RLS-2 in a four-direction double RBS,
c) Or a short or an open in a feedline or a section of the RBS, which includes the RBS-1FP
Feedpoint Unit, a break or a short in the ladder line Beverage antenna wire, or a short or
open in the RBS-1RT Reflection Transformer.
The first direction of reception is with no voltage sent on the feedline. The default direction of
reception (jumper selected inside the RBS-1FP Feedpoint Unit and feedline connection
dependent) is Away from the unit.