DX Engineering DXE-R4S-SYS-V3 Instruction Manual

Receive Four Square System
DXE-R4S-SYS-V3
U.S. Patent No. 7,423,588
DXE-R4S-SYS-V3 Components Shown
© DX Engineering 2022
1200 Southeast Ave. - Tallmadge, OH 44278 USA
Phone: (800) 777-0703 ∙ Tech Support and International: (330) 572-3200
E-mail: DXEngineering@DXEngineering.com
2
Table of Contents
Introduction
3 Default Jumper Configuration Settings
18
System Overview
4 Diagram 1 - Default Configuration
19
Features
4 Optimizing the Array
20
Additional Parts Required
5 Operation
20
Example of Array Performance
5 Normal Receive Four Square Operation
21
Site Selection
7 Receive Four Square Troubleshooting
21
Proximity to Transmit Antennas
7
Topographical Considerations
8
Site Selection in Relation to Noise Sources
8
Ground System
9
Appendix A - Alternate Configurations
26
Lightning Protection
9 Supplying Power Using the Feedline
26
Sizing the Array
10 Directional Control Using the Feedline
27
Four Square Layout
11 Diagram 2 - Alternate Configuration
28
System Operational Overview
12 Diagram 3 - Alternate Configuration
29
Installation
12 DXE-RFS-3 and Active Element Power
30
Active Antenna Elements
13 Directional Control
30
Active Antenna Feedlines
14 Internal Jumper Selection
30
Delay Lines
14 Default Jumper Configuration
31
Control and Power Connections
16 Technical Support and Warranty
32
Default Configuration
18
Figures
Figure 1 - Site Selection Clear Distance
7
Figure 2 - Layout of the DXE-R4S-SYS-V3 Four Square System
11
Figure 3 - Array Diagonal Dimension
15
Figure 4 - Jumper Locations showing Default Settings
19
Tables
Table 1 - Array Safety Distance Minimums at 1500 watts
8
Table 2 - Array Side Lengths
10
Table 3 - Examples of DLY3 Required Length
15
Table 4 - BCD Directional Control Matrix, “1” Equals +12 Vdc (Default)
27
Table 5 - Differential Voltage Control Matrix
28
3
Introduction
DXE-R4S-SYS-V3 - Complete Receive Four Square Array Package
Complete Receive Four Square Array Package
W8JI design RFS-3 array controller Four DXE-RSEAV-1 Antennas with state-of-the-art DXE-AVA-3 Active Matching Units Optimized 160-40 meters with 70ft. element side spacing; functions 100 kHz to 30 MHz Excellent directivity in a small space and better signal-to noise ratio than transmit arrays and
other receive arrays
Switchable in four 90 degree spaced directions Reduced susceptibility to high angle signals compared to EWE, Flag, Pennant, or K9AY
arrays
Low current DC powered control console allows system operation without AC power mains
DXE-R4S-SYS-V3 (U.S. Patent No. 7,423,588) is the complete Receive Four Square Array Package which includes:
(1) DXE-RSEAV-4 Receive Short Element Active Vertical Antennas (4) w/ Internal
Element Grounding Relays
(1) DXE-EC-4 Four Position BCD
Control Console
(1) DXE-RFS-3 Receiving Four
Array Controller
(1) DXE-RG6UFQ-1000 CATV RG6 Style
Coaxial cable, 75 , RG6 Quad Shield, Flooded for Direct Burial, 1000' Spool
(1) DXE-CPT-659 CATV, RG6
and RG-59 Coaxial Cable Stripper, Includes 1 Replacement Blade
(1) DXE-EX6XL-25 75 Quad Shield Coaxial
Cable Compression F Connectors for DXE-RG6UFQ RG6 Cable, 25 pack
(1) DXE-SNS-CT1 Crimp Tool for Type F
75 Coaxial cable Compression Connectors
4
System Overview
The DXE-R4S-SYS-V3 is an advanced four square receiving system that uses four symmetrically spaced elements to provide switching for a 4-direction receiving antenna system. This unique system uses time delay phasing rather than the single band phase shifting used in traditional four squares. When used with active receive elements, this time delay phasing scheme provides the correct phase relationship across a wide frequency range producing useful front-to-rear ratio (F/R) response over octaves of bandwidth.
This system uses directionally-optimized time delays to produce wider and deeper rear nulls. Wide null areas and a narrow main lobe greatly reduce noise and undesirable signals.
The system is more reliable than a conventional transmitting four square system in receiving applications. Most transmitting four squares use large, exposed open-frame relays which can become contaminated or corroded. This system uses sealed relays; contact size is optimized for receiving applications.
Features
Advantages of the DXE-R4S-SYS-V3 Receive Four Square Antenna System over other receiving arrays include:
Seamless stainless steel RFS-3 enclosure, for enhanced weather resistance Reduced susceptibility to high angle signals compared to EWE, Flag, Pennant, and K9AY
antennas
Excellent directivity in a small space for better signal-to-noise ratio Switching of four 90 degree spaced directions Directivity over a very wide frequency range using DX Engineering’s Active Receive
Antennas
Requires less space than a Beverage antenna. Active elements need only a minimal ground
system
Easier to deploy and maintain than a four direction Beverage antenna system Using active elements, system allows close proximity to transmit antennas using
transmit/receive sequencer
Enhanced relay contact reliability Low current DC powered control console allows system operation without AC power mains
This manual will describe the DXE-R4S-SYS-V3 Receive Four Square System in detail.
The DXE-R4S-SYS-V3 is a sophisticated system that requires critical control and
operational voltage and three specialized delay line connections with lengths that
are dependent upon band coverage optimized four square size.
Failure to make quality feedline and delay line connections can cause the entire
array to not function correctly or to perform poorly.
5
Additional Parts Required, Not Supplied with the DXE-R4S-SYS-V3
Four Conductor Power and Control Cable for RFS-3
Four conductor cable (3 plus ground), 22 gauge minimum is required. Economically priced
COM-CW-4 is a four conductor control wire which may be used. Ground Rods (5/8" x 4 to 6 feet) for the Active Receive Vertical elements and the RFS-3 unit. Mounting pipe for the DXE-RFS-3. The DXE-RFS-3 unit has been pre-drilled to accommodate
up to a 2 inch OD pipe using the included DXE-SSVC-2P Stainless Steel V-Bolt Saddle Clamp for 1" to 2" OD pipe. If smaller pipe mounting is desired, the optional DXE-CAVS-1P V-Bolt Saddle clamp can be used for pipe from 3/4" to 1-3/4" inches OD. Note: JTL-12555 Jet-Lube SS-30 Anti­Seize must be used on all clamps, bolts and stainless steel threaded hardware to prevent galling and to ensure proper tightening. The controller can also be mounted on a sturdy wooden post, but provision for grounding the DXE-RFS-3 unit must be made.
Example of Array Performance
Dedicated receive antennas have better signal-to-noise ratios. Directing the antenna away from noise sources or toward the desired signal path is the primary benefit. Antenna gain is a secondary advantage. As frequency increases, the fixed array size becomes electrically larger in terms of wavelength. The increased electrical spacing produces higher sensitivity (average gain) even though front-to-rear ratio only changes slightly. On the low bands, once the receiving system limits on external noise, antenna directivity (F/R) is the only thing that affects the signal-to-noise ratio.
An average Beverage antenna exhibits about -6 dB gain. You would need two reversible Beverage systems to obtain 4-direction selectivity and you still would be limited to one or two bands. The DXE-R4S-SYS-V3 system occupies less space, is much easier to install, is less conspicuous and operates over a wider frequency range with similar or better performance.
A test array was constructed using DX Engineering Active Elements and a side length of only 35 feet. It showed excellent performance across a wide frequency range. This side length is optimal for 40 m, according to Table 2. The array functioned well from 3 MHz to 15 MHz. As shown, the patterns stay clean with good directivity and front-to-rear performance. The elevation angle is 15 degrees for all patterns. On this size array, amplification was required below 3 MHz.
Note: The DXE-RFS Receiving system must be separated from transmitting or other
antennas and structures (particularly metal) by at least 1/2-wavelength. Less separation may cause significant pattern distortion and the introduction of re­radiated noise and signals into the system. This becomes apparent as reduced front-to-rear directivity in one or more directions or a higher noise level.
In a different test array with 50 foot side lengths, optimum performance occurred between 3 and 4 MHz. Performance on 7 MHz was also excellent. Amplification was used below 2 MHz. The highest usable frequency was 10 MHz. This array also produced usable F/R ratios down to the lower end of the AM broadcast band (600 kHz).
6
Increasing the array size increases its sensitivity on the lower frequencies, sliding the performance curve toward the low frequencies and potentially eliminating the need for amplification.
7
Site Selection
Site selection is important. The DXE-R4S-SYS-V3 system can be positioned as close as 1/10 wavelength to transmitting antennas. The DXE-RSEAV-4 Active Elements are bypassed to ground when power is turned off. A programmable sequencer, such as the optional DXE-TVSU-1B will be required with the DXE-R4S-SYS-V3, for an array located within 50 ft. of transmitting antennas.
Significant pattern distortion or coupling may result from close spacing. To prevent pattern degradation, reception of re-radiated electrical noise or other interference, separation of 1/2 wavelength (at the lowest operating frequency) is ideal. See Figure 1. The goal is to do the best you can by balancing all the factors.
The minimum distance to any transmitting antenna from the Four Square perimeter is 1/10 wavelength. Greater than 1/2 wavelength is the minimum distance that will limit coupling to other antennas and the introduction of broadband re-radiated noise and signals.
Figure 1 - Site Selection Clear Distance
Proximity to Transmitting Antennas
The DXE-RSEAV-4 Active Elements and your transmitting antenna need only minimal physical separation to maintain safe power levels when the optional DXE-TVSU-1B sequencer is used. With 1500 watts output and a unity gain (0 dB) antenna, the closest active element can be 1/10 wavelength from the transmitting antenna at the lowest transmitting frequency. Doubling the protection distance quadruples safe power levels. See Table 1.
8
For example, transmitting legal-limit power output (1500 watts) into an ideal four square transmitting antenna produces about 6,000 watts ERP (6 dB gain). Because of the increased radiated power level, nearly 1/2 wavelength minimum spacing between the transmitting and receiving antenna arrays is required, even when using the optional DXE-TVSU-1B Time Variable Sequencer Unit to remove power from the active receive antennas used in the receive four square array.
Table 1 indicates minimum safe distances for the sequenced active array from transmitting antennas with 0 dB, 3 dB and 6 dB gain (ERP) using a 1500 watt transmitter. Your actual system may vary according to location and proximity to various objects.
Band
Unity (0 dB) Gain
3 dB Gain (2x)
6 dB Gain (4x)
160m (1.8 MHz)
55 feet
110 feet
220 feet
80m (3.5 MHz)
28 feet
56 feet
112 feet
40m (7.0 MHz)
15 feet
30 feet
60 feet
Table 1 - Array Safety Distance Minimums at 1500 watts
For any DX Engineering Receive Four Square, using the optional DXE-TVSU-1B Time Variable Sequencer Unit to sequence Active antenna power will ensure that transmitted energy will not cause damage to the receive system.
Topographical Considerations
Flat land is best. Erecting the receiving array on sloped land or steep hills may degrade performance. To avoid pattern degradation, antenna elements must have reasonably similar elevations. It's recommended the ground height difference between any element in the array be less than 10% of the array diameter. For example, a 60 foot diameter array should be within six feet of level. Every effort should be taken to make the elements symmetrical. Elements should all be identical in construction and grounding, and should be mounted above any standing water line but as close to the ground as possible. In general, the system will not be affected by trees or foliage as long as the foliage does not contact the element. Ideally, in important receiving directions, there should be a clear electrical path for at least 1 wavelength. The site should allow a ground system to be evenly distributed around the antennas, if one is required.
Site Selection in Relation to Noise Sources
Because the array is directional across its corners, use this example as a guide: If you have a noise source and if your primary listening area is northeast, locate the array northeast of the dominant noise source. This ensures the array is looking away from the source of noise when beaming in the primary listening direction. The second-best location for the array is when the noise source is as far as possible from either side of the array. If you look at patterns, the ideal location for the array is one that places undesired noise in a deep null area.
If your location doesn’t have the usual noise sources (power lines, electric fences, etc.), locate the array so that your transmitting antennas and buildings are off the back or side of the receiving array.
9
Noise that limits the ability to hear a weak signal on the lower bands is generally a mixture of local ground wave and ionosphere propagated noise sources. Some installations suffer from a dominant noise source located close to the antennas. Noise level differences between urban and rural locations can be more than 30 dB during the daytime on 160 meters. Nighttime can bring a dramatic increase in the overall noise level as noise propagates via the ionosphere from multiple distant sources. Since the noise is external to the antenna, directivity can reduce noise intensity. Consider these things about noise sources:
If noise is not evenly distributed, performance will depend on the gain difference between
the desired signal direction (azimuth and elevation) and average gain in the direction of noise.
If noise predominantly arrives from the direction and angle of desired signals (assuming
polarization of signals and noise are the same) there will be no improvement in the signal-to­noise ratio.
If the noise originates in the near-field of the antenna, everything becomes unpredictable. This is a good case for placing receiving antennas as far from noise sources (such as power lines) as possible.
Ground System
The four DXE-RSEAV-1 Active Elements work well with just a single 6’ x 5/8” copper ground rod used as the ground mount. A separate mounting pipe can be used with optional clamps as the element ground if the pipe is an adequate ground. Depending on soil conductivity, you can expect better performance with multiple ground rods spaced a few feet apart. Increasing ground rod depth beyond 5 feet rarely improves RF grounding because skin effect in the soil prevents current from flowing deep in the soil. Avoid ground rods less than 5/8" OD. A good ground system improves the array performance and enhances lightning survivability. It is important that each ground system be the same for each active antenna in the array.
You can test ground quality by listening to a steady local signal. Attach 15 feet of wire laid in a straight line (away from the coaxial feedline) to the initial 4 foot to 6 foot ground rod. If you observe a change in signal or noise level, you need to improve the ground. A second rod spaced a few feet away from the first one may correct the problem or 10 to 12 ground radials, each 15 feet long, should provide a sufficient ground system for most soil conditions. If a good ground cannot be established, use an optional DXE-RFCC-1 Receive Feedline Current Choke that will further decouple the feedline from the antenna and reduce common mode current and associated noise from the feedline.
Lightning Protection
While amateur radio installations rarely suffer damage from lightning, the best protection is to disconnect electrical devices during storms. The key to lightning survival is to properly ground feedlines and equipment and to maintain the integrity of shield connections. A proper installation improves lightning protection and enhances weak signal receiving performance.
10
Consult lightning protection and station grounding information in the ARRL handbooks, or by referring to the NEC (National Electric Code). The DX Engineering website also has technical and product information listed under “Lightning Protection and Grounding. Use lightning surge protectors for the coaxial cable feedline and control lines.
Sizing the Array
When using active elements, the array side length can be as small as 1/10 wavelength and up to about 1/2 wavelength on the highest frequency to be used. Sizes below 1/10 wavelength result in unusable array sensitivity in the most desired bands. Making side lengths larger than 1/2 wavelength on the highest frequency will split the main lobe and cause pattern and front-to-back degradation. Determine the size of the array by considering the availability of appropriate space, frequency coverage desired and the near proximity to undesirable noise sources, transmitting antennas and other structures.
If there are no space constraints, follow the array side length recommendations in Table 2 for excellent performance. Side lengths longer than the optimal lengths shown will move the peak sensitivity of the array toward the lower frequency. For example, if you are most interested in 160m performance with occasional use on 80m, make the side lengths longer than the optimal 98 feet shown for 160m and 80m. This will improve 160m performance, reduce sensitivity on 80m somewhat, but less than sizing the array exactly for 160m.
Band
Freq. - MHz
Optimal Side
Length in Ft
Min. Side
Length in Ft
Max. Side
Length in Ft
160
1.83
135
54
270
80
3.60
70
28
140
40
7.10
35
14
70
160, 80
1.83, 3.60
98
40
192
80, 40
3.60, 7.10
50
20
98
160, 80, 40
1.83, 3.60, 7.10
70
28
137
Table 2 - Array Side Lengths
If you have limited space, a carefully installed and amplified DXE-RFS can be used on multiple bands with very small side lengths. At smaller side lengths, careful construction using precise measurements is critical. On this type of fixed-size array, as frequency is decreased, the array signal output decreases along with array sensitivity. Eventually the received ambient noise signal level will decrease to a point where it is below your receiver’s noise floor. This comes from two effects:
Elements become electrically shorter, reducing element sensitivity Element spacing becomes smaller in electrical degrees, reducing array sensitivity
Side lengths at 1/10 wavelength on 40 m would only be 14 feet. Although usable, amplification would be required. In addition, the construction of a very small array is extremely critical. Side lengths must be perfectly symmetrical. The delay lines must be directly measured for electrical length and cut to exact lengths. The ground system must be effective. Even at this small spacing, the array will have useful front-to-rear performance and directivity!
11
Four Square Layout
The array antenna elements should be arranged in a square, use Table 2 for guidance in choosing the best combination of frequency coverage and side length dimensions.
The diagonal corners of the square should point in the most desirable receiving directions.
Element 1 is the default forward element, Element 3 is the rear or null element
Performance of the RFS-3 can noticeably decrease if structures radiating even small
amounts of noise or signals are within 1-wavelength of the array
Measure side-to-side and then corner-to-corner to ensure the element locations are square Normally the RFS-3 phasing unit is installed near the center of the four array elements,
above any standing water, with the connector side facing down. The placement of the RFS-3 unit is not critical, however, the feedlines to each of the active elements must be equal in length
If you mount the RFS-3 on a wood post, it should be grounded to a separate ground rod
Figure 2 - Layout of the DXE-R4S-SYS-V3 Four Square System
System Operational Overview
The DXE-R4S-SYS-V3 system is comprised of the DXE-EC-4 BCD Control Console and the DXE-RFS-3 Control Unit. These units interconnect and work together using factory default
settings.
12
The DXE-EC-4 BCD Control Console supplies the nominal +12 Vdc operational voltage as well as the +12 Vdc BCD control voltage. The operational voltage powers the DXE-RFS-3 Control Unit which subsequently powers the active receive elements. The BCD switching voltages cause the DXE-RFS-3 to change the receiving direction of the array.
The DXE-EC-4 Control Console is configured by default to output the BCD control voltages needed by the DXE-RFS-3. The default direction for the array (toward Element 1) is selected when LED 1 on the DXE-EC-4 is illuminated. When positions 2 to 4 are selected on the EC-4, the array switches directions. Refer to Diagram 1 for default connection details.
The DXE-RFS-3 distributes the operating power to the active elements through the individual element feedlines. The active elements do not work without power. Cutting power to the DXE-RFS-3 also cuts power to the active elements which causes the DXE-AVA-3 to ground the vertical element. Operating with the optional DXE-TVSU-1B Sequencer (inserted into the EC-4 "C" to the RFS-3 "C" terminal) makes this power switching function automatically.
An alternate configuration (refer to Appendix A) which uses the feedline coaxial cable for either the operational power or the directional control voltages, can be used. This configuration requires internal jumper changes in the DXE-RFS-3, along with additional hardware to couple the proper voltage to the feedline. For directional control through the feedline, the DXE-RFS-3 requires +12 Vdc, ─12 Vdc and 12 Vac. The DXE-FVC-1 Voltage Coupler can be used to supply these voltages.
In any alternate configuration, do not use coaxial cable or other conductor for more than one simultaneous use. Refer to Diagram 2 for connection details of one of several alternate configurations.
The only reason for using an alternate configuration is to make use of existing 2 or 3 conductor control cable. Otherwise inexpensive four conductor control cable (COM-CW-4) and the default configuration is recommended.
Installation
The DXE-RFS-3 Control Unit can be mounted to a galvanized pipe driven into the ground. The DXE-RFS-3 unit has been pre-drilled to accommodate up to a 2 inch OD pipe using the included DXE-SSVC-2P Stainless Steel V-Bolt Saddle Clamp for 1" to 2" OD pipe. If smaller pipe mounting is desired, the optional DXE-CAVS-1P V-Bolt Saddle clamp for pipe from 3/4" to 1-3/4" inches OD is recommended. The controller can also be mounted on a sturdy wooden post, but provision for grounding the DXE-RFS-3 unit must be made. Note: JTL-12555 Jet-Lube SS-30 Anti­Seize must be used on all clamps, bolts and stainless steel threaded hardware to prevent galling and to ensure proper tightening.
The DXE-RFS-3 is designed to be used with the DX Engineering Receive Short Element Active Vertical Antennas. It can also be used with passive elements for a dedicated mono-band array. The user manual included with the DXE-RSEAV active elements has instructions for assembly and installation. As noted in that manual, the active elements should be installed as close to the ground
13
as possible but above any high water line. Ground the ANT– (negative) terminal to an adequate
ground.
Station Feedline, Active Antenna Feedline and Delay Lines
The weakest link in an antenna system, such as the DXE-R4S-SYS-V3, is often the coaxial cable connections. All connections must be high quality and weather tight to prevent contamination and corrosion, which can cause the feedline impedance to change. This can affect the signal-to-noise ratio and the directivity of the array. In addition, the DXE-RFS-3 uses the shield as a ground return path for the active element power.
Note: The total loop resistance of the ground path must be under 30 Ω for reliable operation.
If the resistance of the shield increases due to contamination, the active elements may not function properly. Any splices in the feedline should be high quality and entirely weather tight. Do not use splices in the delay line cables. The DXE-R4S-SYS-V3 system has been designed to use only 75 Ω coaxial cable.
Included with the DXE-R4S-SYS-V3 package is high quality, flooded 75 Ω RG6U quad shield type coaxial cable. The DXE-RG6UFQ-1000 flooded coaxial cable automatically seals small accidental cuts or lacerations in the jacket. Flooded coaxial cable also prevents shield contamination and can be direct-buried.
Included with the DXE-R4S-SYS-V3 package is the coaxial cable preparation tool, part number DXE-CPT-659, that readies the coaxial cable for connectors in one operation and comes with an extra cutting cartridge. To ensure weather tight connections, use DXE-EX6XL-25 compression style F connectors are also included. DXE- EX6XL-25 contains 25 compression F connectors, enough for the entire array plus some spares. The compression F connectors cannot be installed with normal crimping tools or pliers, so you also receive the installation tool DXE-SNS-CT1, from DX Engineering with the DXE-R4S-SYS-V3 package for proper connector installation.
Active Antenna Feedlines
Use the included 75 Ω coaxial cable to make F connector assemblies to run from each antenna element to the DXE-RFS-3. The four feedlines from the DXE-RFS-3 phasing unit to the active elements can be any length needed to accommodate the size of the array, but they must all be the same length, velocity factor and type. Note the orientation and numbering of the elements by using Figure 2. Be sure the appropriate antenna element is connected to the proper ANT connector on the phasing unit. The default (zero control voltage) forward direction is towards Element 1. Element 3 is the default rear or null direction.
Delay Lines
The DXE-RFS-3 uses a time delay system, not a traditional phasing system. Delay line lengths are dictated by array dimensions rather than operating frequency. This results in phase being correct for a rearward null at any frequency. This system is especially effective when used with DX Engineering DXE-RSEAV-4 active vertical elements. User-supplied passive elements can also provide exceptional performance for single band operation where high dynamic range is required.
14
The DXE-RFS-3 phasing unit has three sets of delay line connections marked DLY1, DLY2 and DLY3. Each of these connection pairs will have a specific length of coaxial cable acting as a jumper between the two connectors. Jumper electrical length is critical. Careful measurements and the use of 75 Ω coaxial cable (included in this package system) with a known Velocity Factor (VF) is very important.
If you are not using the included DXE-RG6UFQ-1000 quad shield coaxial cable, keep in mind that solid Teflon® or polyethylene dielectric coaxial cable has a VF of approximately 0.66. Foamed coaxial cable cables typically range anywhere between 0.75 and 0.90 VF, depending on the ratio of air-to-dielectric material in the cable core. If you do not know the VF of the coaxial cable you are using, you must directly measure the electrical length of the coaxial cable you have or obtain cable with a known VF. The included DX Engineering DXE-RG6UFQ-1000 75 Ω quad shield coaxial cable has a nominal VF of 0.82. For best performance, the coaxial cable for the delay lines should be from the same batch or spool.
The first step is to determine the required electrical length of DLY3. This is based on the corner­to-corner or diagonal distance between two diagonal corner elements of the square forming the array. You can directly measure this distance, or it can be calculated by multiplying the side length of the array by 1.4142. The electrical length of delay line DLY3 should be slightly shorter than the actual physical distance between the two diagonal corners of the array. An electrical length 95% of the physical distance works well (diagonal distance times 0.95). Table 3 shows these calculations for three common side lengths.
Side Length in
Feet
Diagonal
Physical Length
in Feet
Factored 0.95
Electrical Length
in Feet
DLY3 Physical Length
in Feet (0.82 VF)
135 (160m)
190.9
181.4
148.8
98 (160m & 80m)
138.6
131.7
108.3
70 (80m)
99.0
94.0
77.1
Table 3 - Examples of DLY3 Required Length
After calculating the required electrical length, you must include the VF of the coaxial cable being used when determining the correct physical length of DLY3. Multiply the factored electrical length by the VF. The result is the correct physical length for DLY3. See Figure 3 and the sidebar for an example. Note: These calculations are in feet, not feet and inches.
Figure 3 - Array Diagonal Dimension
To find the physical length of DLY3, calculate the diagonal length of the array by either directly measuring the diagonal or by multiplying the array side length by 1.4142. DLY3 will be significantly shorter than the actual physical length. The diagonal length is first multiplied by 0.95. This gives the factored electrical length for DLY3. Next, multiply the DLY3 electrical length by the VF of the delay line coaxial cable. The result is the correct physical length for DLY3.
15
For Example: An array with 90 foot side spacing, the diagonal length is 127.3 feet. The 0.95
factored physical length for DLY3 electrical length is 120.9 feet. Multiply 120.9 feet. by 0.82 (the VF of DX Engineering 75 Ω quad shield coaxial cable).
The correct physical length for DLY3 is 99.14 feet, or 99 feet, 1-5/8 inches.
Delay lines DLY1 and DLY2 must be half the length of DLY3. Make DLY1 and DLY2 as close to half the physical length of DLY3 as possible. To avoid performance degradation due to inconsistent coaxial cable construction, all the delay line coaxial cable should be cut from the same spool.
Delay line cables can be neatly coiled in a 1-1/2 foot diameter coil. Support the weight of the cables by taping or securing them to the support pole or mast rather than allowing them to hang from the connectors. It is important to use 75 Ω feedline to the operating position from the DXE-RFS-3. Do not use amplifiers, combiners, filters or splitters that are not optimized for 75 Ω systems.
Control and Power Connections
If you have the DXE-R4S-SYS-V3 system, with the DXE-EC-4 Control Console, no other equipment is needed for powering the DXE-R4S-SYS-V3, the active elements or controlling the receive direction of the DXE-R4S-SYS-V3. The DXE-R4S-SYS-V3 has been factory-set to work with the DXE-EC-4 using four conductor control cable such as COM-CW4.
J12 is the 5-terminal connector plug on the front panel of the DXE-RFS-3. It is labeled G A B C G.
The DXE-RFS-3 uses a two part green connector and the top part can be removed by pulling it straight off. This will allow easier wire replacement or servicing as needed. When pushing the connector back in place, ensure you press straight inward.
16
The DXE-EC4 uses an internal terminal plug labeled “G 1 2 3”.
DXE-EC-4
DXE-RFS-3
G
to
G
1
to
A
2
to
B
3
to
C
Direct Wire connections between the DXE-EC-4 and DXE-RFS-3
For systems that have 1/2-wavelength or greater spacing between the receive four square array and any transmitting antenna, the optional TVSU-1B is not be needed. The wiring diagram above shows wiring between the DXE-EC-4 and the DXE-RFS-3. If you are using the optional DXE-TVSU-1B, the wiring connections are shown in Diagram 1 - Default Configuration.
Control lines (usually BCD ) can normally use good quality CAT5e cable (4 twisted pairs of 24 AWG wire) for runs up to 1000 feet. Typical DX Engineering BCD control lines requirements are +12 VDC at 25 milliamps.
Depending on the number of control lines needed (usually 3 or 4) you can double up the twisted pairs of CAT5e cable, or use control wire that is at least 22 AWG, allowing runs up to 1500 feet. If you use a cable with more conductors, it is a good idea to tie the unused conductors to ground.
For longer runs of control cable, use a line loss calculator to ensure you supply the proper control levels needed.
Approximate BCD Control Line Lengths.
Minimum Copper
Wire Gage (AWG)
Length
24
1,000 feet
22
1,500 feet
20
2,000 feet
Active antenna circuitry needs a good voltage supply to operate properly. When supplying power to an active antenna, you want to have +12 VDC, 40 milliamps at each active (under load).
17
CAT5e cable is not recommended when making long runs to power an active antenna since the line loss in CAT5e cable may not supply the proper operational voltages required for active antennas.
Depending on the required length of your power wire, you will want to use a line loss calculator (voltage drop with various wire gages) to ensure your power supply (normally +13.6 well filtered DC) will supply a minimum of +12 VDC, 40 milliamps at each active antenna (under load).
A DX Engineering 4 Square or 8 Circle will require approximately 250 milliamps (only 4 actives are powered at any one time).
When calculating line length, take into consideration the total number of active antennas being powered at any one time in your line length calculations.
Approximate Active Antenna Power Line Lengths (4 active antennas on at any one time).
Minimum Copper
Wire Gage (AWG)
Length
18
300 Feet
16
500 feet
12
1,200 feet
10
2,000 feet
Default Configuration
The DXE-R4S-SYS-V3 default configuration, as shown in Diagram 1, uses terminals A & B for the BCD directional
control interface and terminal C for operational and active element power. The DXE-EC-4 provides the operational power as well as the 2-bit BCD interface used for directional control. A user-supplied 4-conductor cable is needed to connect the DXE-RFS-3 and the DXE-EC-4 with the optional DXE-TVSU-1B Time Variable Sequencer Unit switching the active antenna power conductor.
The switch positions on the DXE-EC-4 control the directivity of the received signal in the DXE-R4S-SYS-V3.
As shown in the diagram to the right, position one favors the NE direction, position 2 favors the SE direction, position 3 favors the SW direction and position 4 favors the NW direction when the array is positioned as shown.
18
Diagram 1 Default Configuration for the DXE-R4S-SYS-V3
Shown with optional items. Accessory DC power cables omitted for clarity.
19
Optimizing the Array
To determine if the antenna system output level is the limiting factor, tune the receiver to the lowest band at the quietest operating time. This is usually when propagation is poor but some signals are heard. Disconnect the antenna and set the receiver to the narrowest selectivity you expect to use. Receiver noise power is directly proportional to receiver bandwidth (going from 2.5 kHz selectivity to 250 Hz selectivity reduces noise by 10 dB). Connecting the antenna should result in a noticeable increase in noise. If so, the array signal level is sufficient, then further optimization or amplification is not be needed.
If the array is used only 160m or below, the Active Antenna internal gain jumper can be reset as discussed shown in the DXE-AVA-3 manual. If the array still lacks sensitivity on the low bands, then a preamplifier with high dynamic range can be used to compensate for the low signal level. However, using a preamplifier when sufficient signal is already present may result in amplification of the noise along with the signal. It is always best to use the least gain possible. Depending on conditions, using a preamplifier can cause receiver overload; either use an input RF attenuator or bypass the preamplifier.
The DXE-RPA-2 HF Preamplifier has better dynamic range than most receivers and can be used to compensate for the decrease in array signal output. The DXE-RPA-2 preamplifier is automatically bypassed when power is removed.
Operation
When using the DXE-RFS-3, positions 1 through 4 on the EC-4 BCD Control Box will phase the appropriate active vertical elements to give you excellent receiving capabilities.
The front to back signal to noise ratio of the active vertical elements in the four phase array allow you to not only enhance the desired received signal, but also to decrease an unwanted receive signal by selecting a position that will drastically reduce or eliminate it.
20
Normal Receive Four Square Operation
When the Receive Four Square system is functioning properly, low or medium power daytime AM Broadcast ground wave signals should be alternately attenuated or improved with directional switching. However, strong sky wave signals arriving at high angles of propagation will show very little signal level change as different directions are selected on the Receive Four Square.
Although some low band signals may be received at very low levels, they are heard more easily due to far less noise received by the non-resonant array. If necessary, the use the DXE-RPA-2, Receiver Preamplifier - an in-shack pre-amplifier with exceptionally low-noise and high dynamic range characteristics. The DXE-RPA-2 will enhance the intelligibility of the weak DX signals, without adding the noise that plagues many of the pre-amps that are built into modern transceivers.
The Receive Four Square array pattern is designed to enhance forward low angle signals, and reject rearward and high angle signals. The Receive Four Square system provides superior signal-to-noise results that allow you to hear signals that are impossible to copy on much noisier transmit antennas, for greatly improved weak signal DX operations.
Receive Four Square Troubleshooting
There are several possible causes for a malfunction of a DX Engineering Receive Four Square System. Testing the system is not difficult and can be completed in an hour or so. Separate circuits for directional switching, Active Vertical Antenna power, and antenna phasing can each be affected by a variety of cabling, connection and or component problems. If you are troubleshooting a new system or using a replacement RFS-3 unit, check that the internal jumpers are set correctly for your system control and voltage configuration.
Here are the most common causes of Receive Four Square malfunction, especially in a system that was previously functioning properly:
21
A) Broken and/or shorted conductors due to animal, weather or other damage, including chewed,
punctured, stretched and broken control and power lines and/or feedlines for the system and
each antenna. Also, screws in the green removable connectors can inadvertently be tightened
onto the insulation of control or power conductors.
B) Regressed center conductors in the feedlines causing disengagement from the female center
capture pin of the F connector. This can happen in delay lines as well as in antenna or main
feedline connections. Many times a compression F connector that seems to have a long enough
center conductor when it was made, has regressed to the point that it is not long enough to
Start
Check Internal
Jumpers
A
Broken/Shorted
Conductors
Animals, Chewed,
Punctured, Stretched
or Broken.
Green Connector may have
broken a wire or is tightened
against insulation - not bare wire.
B
Center
Conductors
slipped
Check all F connector
center conductor
wires. They may have
pulled inward.
C
Shorted/Open
conductors due
to water
Check feedlines and
control cable.
D
Zapped by
lightning pulse or
RF overload.
80% of all Receive Four Square
malfunctions are caused by
A, B or C
Make sure units are at least 1/2
wavelength, on the lowest frequency,
away from any transmit antenna.
May want to use optional DXE-
TVSU-1B Time Variable
Sequence Unit for AVA units.
E
RFS-3 damaged
due to lightning.
Rare, but can happen
F
Damaged by
animals/insects.
Animals have been known to
relieve themselves on the units
and the urine will corrode and
damage electronics.
Insects getting inside
units and shorting out
electronics.
22
make proper contact. A properly installed F connector should have the center conductor
protruding 1/4 inch beyond the shell when viewed from the side. Check all F connectors! C) Shorted or opened conductors caused by water migration into a control line or a feedline.
Over 80% of all Receive Four Square malfunctions have been caused by the above system
problems. A thorough inspection and subsequent testing of each control cable, RF cable, and
their respective connections, will uncover the cause of most RFS troubles. Here are a few other
causes for RFS malfunction: D) One or more burned out Active Vertical Antenna units, models AVA-3, AVA-2 or AVA-1, due
to lightning pulse or high power RF overload. One-half wavelength on the lowest frequency is
the minimum distance between the Active antennas and any transmit antennas. If that distance
is less and high power is used, then the optional Time Variable Sequence Unit, model DXE-
TVSU-1B must be used to interrupt power to the active elements. E) Damaged RFS-3 unit due to lightning. This has been reported only a couple of times and is not
very likely. F) Active units that were damaged by animals. Once we received actives damaged by an animal
that relieved themselves on the antenna whips and AVA units, as if they were “trees”. The above items are the most common failure points in the system that need to be checked. If necessary, the following further troubleshooting procedure may assist in finding the malfunction.
Receive Four Square Control Troubleshooting Procedure
1) Test the DXE-EC-4 BCD Control Console unit, which should be
connected only to the control lines of the Receive Four Square
System. When the EC-4 is connected to the control cable, do all of
the selected switch position LEDs light normally?
2) When rotating the Control Console switch from position 1, 2, 3 and 4, if all LEDs
light normally, measure BCD output voltages. Normally, +12 for the EC-4 is
output on the green connector terminals located inside the unit. Connections 1, 2
and 3, reference to the ground pin G as shown below. The selected position will
supply the BCD logic voltage as shown in the chart below.
Forward Direction
EC-4 Switch
Position
BCD Terminal
EC-4 LED
Illuminated
1 2 3
Element 1 (Default)
1
0 0 1
# 1
Element 2
2
1 0 1
# 2
Element 3
3
0 1 1
# 3
Element 4
4
1 1 1
# 4
BCD Directional Control Matrix, “1” Equals +12 Vdc (Default)
The numbered terminals of the 4-pin green connector correspond to the numbers in the table
above, with voltage measured as referenced to the G ground terminal.
23
3) If the voltages are not normal, less than +10 to 18 Vdc, with the control line connected, then
disconnect the control line and retest the Control Console. If voltages that were not correct, are
now okay, that indicates a short in the control line or a problem in or beyond the RFS-3
Receive Four Square relay unit.
4) If the EC-4 has only a couple LEDs lit with the control cable disconnected, then it may have
sustained lightning pulse damage and will need to be repaired or replaced. A new DXE-EC-4
is available from DX Engineering.
Continue troubleshooting the array control with a good EC-4 or by using a 1A fused power source.
5) Determine if the control line is intact by resistance or voltage testing each conductor for shorts
with the far end of the control cable disconnected from the RFS-3 unit.
6) With a good EC-4 or other power source connected, measure A, B and C control conductor
voltages at the RFS relay unit with the control cable connected, and again at the end of the
control cable that is disconnected from the RFS relay unit. If measured voltages are not
between +10 to 18 Vdc on the selected line, a resistive, short or open circuit problem exists in
the control line or in the RFS relay unit or antenna feedlines. Normal voltages on the connected
control line will cause relays to switch inside the RFS unit. If switching voltages are correct,
lack of system directivity or gaps in reception may be due to antenna, feedline or delay line
issues.
7) Test the Active Antennas by feeding a voltage on the tested control line A and/or B
conductor(s) to select one direction of RFS unit operation. Simultaneously feed normal
operating voltage on the tested conductor that powers the Active Verticals for reception. If a
low value fuse blows, then a short circuit may be isolated by disconnecting antennas and
reconnecting them one at a time.
If no fuses have blown and connected voltages stay near the nominal +12 Vdc levels, then:
8) Test for active operating voltage at the end of each antenna feedline. If all are good, proceed. If
not, repair feedlines and/or connectors. If voltage is present on the power line to the RFS relay
unit, but is not measured at the end of good feedlines, inspect inside RFS-3 relay unit to
determine if there is an obvious reason that Active Vertical Antenna power is not making it out
the antenna ports. A bad connection outside of the RFS relay unit is usually the problem, and
rarely has a component failure inside the RFS relay unit been discovered. If the system
previously functioned properly, then the internal jumpers would have been previously set in
their proper positions for your system configuration. If you are troubleshooting a new system
or using a replacement unit, check that the internal jumpers in the RFS-3 unit are set correctly
for your system control and voltage configuration.
Proper Receive Four Square phasing requires that each Active Vertical Antenna, and its
respective equal length feedline, actually provides the same signal level to the RFS unit.
Use a steady, non-fading ground wave signal from a low or medium power daytime AM
Broadcast station that is over 10 miles away, on a frequency high in the band, or another
constant signal source on 160 or 80 meters, well away from the array, to test that each Active
24
Vertical receives the same signal level. Do not use sky wave or night signals for these signal
level tests.
9) Test reception of each Active Vertical Antenna by connecting each antenna feedline, one at a
time, to an activated port on the RFS-3. This assumes that a good port has been identified and
is functioning properly. Normal reception must be confirmed from each antenna. If any antenna
is not providing the proper RF signal level, move the AVA unit to a known good feedline
position to rule out the possibility that a bad feedline is attenuating the RF. If one or more
Active Receive Verticals produce a low or no signal, then the AVA unit at the base of that
antenna may not be receiving power. Retest for DC power at the antenna end of that feedline. If
+ 10 to 18 Vdc is found, then the Active unit may need to be serviced or replaced. New DXE-
AVA-3 units are available separately by calling DX Engineering.
10) If all Active Verticals tested provide the same signal level, then change switching voltages to
activate the other ports, one at a time, and test each RFS unit port, using one of the good
antennas, testing for the same level of reception. If one or more ports is dead or has diminished
reception, there may be a problem in a delay line or in the RFS unit.
11) Using tested or replaced delay lines and connectors, if one or more ports is dead or has
diminished reception, the RFS unit may require service or replacement.
At this point, the problem in your system should have been identified.
If you need additional assistance from DX Engineering, feel free to call 330-572-3200 or e-mail (DXEngineering@DXEngineering.com). Detailed discussions of system function, connections, and troubleshooting is best handled by telephone, Monday through Friday, 8:30 am to 4:30 pm Eastern Time.
25
Appendix A
Alternate Configurations – ONLY for distant arrays with very long feedlines and control cables, to minimize control and power cable conductor count
An alternate configuration which uses the feedline coaxial cable for either the operational power or the directional control voltages, but not simultaneously, can be used. This configuration requires internal jumper changes in the DXE-RFS-3, along with additional hardware to couple the proper voltage to the feedline.
For directional control through the feedline, the DXE-RFS-3 requires +12 Vdc, ─12 Vdc and 12 Vac. The DXE-FVC-1 Voltage Coupler can be used to supply these voltages. In any alternate configuration, do not use coaxial cable or other conductor for more than one simultaneous use. Refer to Diagram 2 for connection details of one of several alternate configurations.
The only reason for using an alternate configuration is to make use of existing 2 or 3 conductor control cable. Otherwise inexpensive four conductor control cable (COM-CW-
4) and the default configuration is recommended.
Any alternate configuration requires changing the internal jumpers from their default settings. Be very careful about changing the default jumper settings. You must not jumper the DXE-
RFS-3 so that power and directional control are done on the same conductor. This will damage the RFS-3 or the RSEAV-1 active elements and is not covered under warranty.
Supplying Power Using the Feedline
If you use the feedline to supply operational power, then directional control for the RFS-3 must be done using the J12 connector. There are two ways to do directional control through J12 when using the coaxial cable for power:
2 bit BCD style control voltage using terminals 1 & 2.
See Table 4. This requires at least a 2 conductor cable. Economically priced COM-CW-4 is
a 4 conductor Shielded Control Wire which may be used. The feedline shield can be used for the
ground return provided it is grounded at the common power source.
Forward Direction
Rear Direction
A B C
EC-4 LED Illuminated
Element 1 (Default)
Element 3 (Default)
0 0 1
# 1
Element 2
Element 4
1 0 1
# 2
Element 3
Element 1
0 1 1
# 3
Element 4
Element 2
1 1 1
# 4
Table 4 - BCD Directional Control Matrix, “1” Equals +12 Vdc (Default)
26
Differential voltages (+/–12 Vdc & 12 Vac) using terminal C. This can be done using a 1 or
2 conductor cable. Economically priced COM-CW-4 is a 4 conductor control wire which may
be used. See Table 5 for the control matrix. The optional DXE-FVC-1 can be used to
generate the required differential voltages using a 1 or 2 conductor cable. Feedline shield can be used as the ground return.
Forward
Direction
Rear
Direction
Voltage on Coax or
J12 Term C
Direction
Shift
Element 1
Element 3
None
Element 2
Element 4
+12 Vdc
90°
Element 3
Element 1
-12 Vdc
180°
Element 4
Element 2
12 Vac
270°
Table 5 - Differential Voltage Control Matrix
If you choose to use the feedline to provide power to the DXE-RFS-3, you will have to supply your own bias tee coupling circuit to insert the required +12 Vdc on the feedline.
Directional Control Using the Feedline
If you use the feedline for directional control, then you must provide power for the DXE-RFS-3 using terminal C of the J12 connector. Terminals A & B are not used. A single conductor cable is needed to power the DXE-RFS-3 and active elements. Station power (nominal +12 Vdc) can be used provided a 1A in-line fuse is used. Diagram 2 illustrates the coaxial cable being used for directional control and the use of station power.
Using the feedline for directional control requires differential voltages to switch directions. Use Table 5 for the control matrix. The optional DXE-FVC-1 can be used to generate and couple the required differential voltages to the feedline or a single conductor cable. The DXE-FVC-1 can be controlled with a EC-4 with a simple switch closure-to-ground scheme. The DXE-FVC-1 provides only the directional control voltages. Study the configuration diagrams on the next pages and the Internal Jumper Settings in Figure 5 before making any changes to the default settings. Diagram 2 shows the DXE-FVC-1 and the DXE-EC-4 used for directional control.
27
Diagram 2 - Alternate Configuration
All Element feedlines, delay lines and station feedlines must be 75 coaxial cable. RFS-3 internal jumper changes are
required. Element feedlines can be any length, but must be equal. Accessory DC power cables omitted for clarity.
28
Diagram 3 - Alternate Configuration
Using a manual switch connected to the optional DXE-FVC-1 for directional control
All Element feedlines, delay lines and station feedlines must be 75 Ω coaxial cable. Requires RFS-3 internal jumper
changes. Element feedlines can be any length, but must be equal. Accessory DC power cables omitted for clarity.
29
DXE-RFS-3 and Active Element Power
The DXE-RFS-3 phasing unit uses and distributes the voltage to power the active antenna elements. For all four active elements, a nominal +12-15 Vdc at 200 mA current is required. The default configuration uses Terminal C on the 5-position plug for power.
The DXE-EC-4 is used to power and control the DXE-RFS-3. The default direction is selected when LED #1 is illuminated. This setting provides operating voltage on Terminal 3 of the DXE- EC-4, which is connected to Terminal C on the DXE-RFS-3. (The active elements do not work without power.) See Table 4; note that “3” has voltage in all four positions. If the optional TVSU- 1B Sequencer is used, it will provide keyed power to the DXE-RFS-3 for the active verticals.
Alternatively, the coaxial cable can be used to power the elements. This requires the default jumper settings to be changed. See the next section for alternate jumper settings. You must provide a way to couple this voltage on the feedline.
Directional Control
The default configuration of the DXE-RFS-3 phasing unit uses a 2-bit, +12 Vdc BCD interface scheme to switch directions through a user-supplied 4 conductor cable connected to the DXE-EC-4.
The default direction without applied control voltage is in the direction of Element 1. Element 3 is the default rear or null direction.
Table 4 shows the array direction, the truth table for the BCD interface (A&B) and the status of the LED indicators on the DXE-EC-4 for each direction. (Terminal C is used to power the DXE-RFS-3 so it is always on.)
Forward Direction
Rear Direction
A B C
EC-4 LED Illuminated
Element 1 (Default)
Element 3 (Default)
0 0 1
# 1
Element 2
Element 4
1 0 1
# 2
Element 3
Element 1
0 1 1
# 3
Element 4
Element 2
1 1 1
# 4
Table 4 - BCD Directional Control Matrix, “1” Equals +12 Vdc (Default)
30
Internal Jumper Selection
To access the DXE-RFS-3 jumper blocks, remove the 6 screws holding the connector plate of the DXE-RFS-3 unit to the enclosure. Pull on the plate to separate it from the enclosure. The jumper blocks should be visible and oriented as shown in Figure 5.
Important Note: You cannot use coax or any other conductor for multiple functions. If you are going to use the coax for directional control, then you cannot use the coax for power-a separate cable must be used. We recommend using the default configuration.
Default Jumper Configuration Settings
Figure 5 shows the default jumper settings for the DXE-RFS-3. For JMP1 & JMP2 the center and
top pins of both are shorted. For JMP3 & JMP4, the center and bottom pins of both are shorted.
Figure 5 - Jumper Locations showing Default Settings
JMP1 Selects Power Voltage Source: Coax or J12 - Shown in default position, voltage from J12
JMP2 Selects Direction Voltage Source: Coax or J12 - Shown in default position, voltage from J12
JMP3 and JMP4 Select Directional Voltage Configuration, either Differential or BCD.
Both Jumpers must be set the same. - Shown in default position for BCD
31
NOTES
32
Technical Support
If you have questions about this product, or if you experience difficulties during the installation, contact DX Engineering at (330) 572-3200. You can also e-mail us at:
DXEngineering@DXEngineering.com
For best service, please take a few minutes to review this manual before you call.
Warranty
All products manufactured by DX Engineering are warranted to be free from defects in material and workmanship for a period of one (1) year from date of shipment. DX Engineering’s sole obligation under these warranties shall be to issue credit, repair or replace any item or part thereof which is proved to be other than as warranted; no allowance shall be made for any labor charges of Buyer for replacement of parts, adjustment or repairs, or any other work, unless such charges are
authorized in advance by DX Engineering. If DX Engineering’s products are claimed to be defective in material or
workmanship, DX Engineering shall, upon prompt notice thereof, issue shipping instructions for return to DX Engineering (transportation-charges prepaid by Buyer). Every such claim for breach of these warranties shall be deemed to be waived by Buyer unless made in writing. The above warranties shall not extend to any products or parts thereof which have been subjected to any misuse or neglect, damaged by accident, rendered defective by reason of improper installation, damaged from severe weather including floods, or abnormal environmental conditions such as prolonged exposure to corrosives or power surges, or by the performance of repairs or alterations outside of our plant, and shall not apply to any goods or parts
thereof furnished by Buyer or acquired from others at Buyer’s specifications. In addition, DX Engineeri ng’s warranties do not extend to other equipment and parts manufactured by others except to the extent of the original manufacturer’s
warranty to DX Engineering. The obligations under the foregoing warranties are limited to the precise terms thereof. These warranties provide exclusive remedies, expressly in lieu of all other remedies including claims for special or consequential damages. SELLER NEITHER MAKES NOR ASSUMES ANY OTHER WARRANTY WHATSOEVER, WHETHER EXPRESS, STATUTORY, OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS, AND NO PERSON IS AUTHORIZED TO ASSUME FOR DX ENGINEERING ANY OBLIGATION OR LIABILITY NOT STRICTLY IN ACCORDANCE WITH THE FOREGOING.
©DX Engineering 2022
DX Engineering®, DXE®, DX Engineering, Inc.®, Hot Rodz®, Maxi-Core®, DX Engineering THUNDERBOLT®, DX Engineering Yagi Mechanical®, EZ-BUILD®, TELREX®, Gorilla Grip® Stainless Steel Boom Clamps, Butternut®, SkyHawk™, SkyLark™, SecureMount™, OMNI-TILT™, RF-PRO-1B®, AFHD-4® are trademarks of PDS Electronics, Inc. No license to use or reproduce any of these trademarks or other trademarks is given or implied. All other brands and product names are the trademarks of their respective owners.
Specifications subject to change without notice.
Loading...