MODEL VP2
100 MM VANE THERMO-ANEMOMETER PROBE
Wireless, Measures Velocity, Flow, Humidity, and Temperature
16-25/32
[426.08]
2 [50.80]
1-5/32
[29.31]
[106.65]
5/16
[7.95]
FEATURES/BENEFITS
• Allows for one handed operation for ladder use safety
• Stable 50 ft (15 m) wireless range
APPLICATIONS
• Building Commissioning
• Building HVAC test and balance
1-41/64
[41.62]
DWYER INSTRUMENTS, INC. | 168
6-3/64
[153.66]
SPECIFICATIONS
Service: Dry, clean air.
Temperature Limits: Process: -20 to
212°F (-29 to 100°C); Ambient: 5 to
125°F (-15 to 51°C).
Range: Air Velocity: 40 to 5000 FPM
(0.2 to 25 m/s); Volumetric Air: 999,999
in selected ow units; Temperature:
-20 to 212°F (-29 to 100°C); Relative
Humidity: 0 to 100% RH.
Accuracy: Air Velocity: 0.25 to 10
m/s: ±1.5% of reading ±20 FPM (±0.1
m/s); 10 to 20 m/s: 1.5% of reading
±40 FPM (±0.2 m/s); 20 to 25 m/s:
±1.5% of reading ±60 FPM (±0.3 m/s);
Temperature: ±0.54°F @ 77°F (±0.3°C
@ 25°C); Relative Humidity: ±2% @
77°F (25°C) (10 to 90% RH); ±4% (0 to
10% RH and 90 to 100%).
MODEL CHART
Model Description
VP2 Wireless 100 mm vane thermo-anemometer probe for use with the Model
UHH handheld meter and the Mobile Meter
Mobile App
Response Time: Air Velocity and Air
Volume: 1 s; Temperature and Relative
Humidity: 1.5 s.
Probe Length: 8˝ (203 mm) insertion.
Battery Charging Limits: 32 to 113°F
(0 to 45°C). (Wireless Only).
Power Requirements: 3.7 V YT562447
Lithium ion battery, installed functional,
user replaceable. (Note: Intended to be
operated with power cables less than 3
m in length). (Wireless Only).
Maximum Wireless Distance: 50´
(15 m). (Wireless Only).
Handle Enclosure: Thermoplastic
elastomer over polycarbonate.
Supplied With: Wrist strap.
Weight: 13.6 oz (385 g).
Agency Approvals: CE (not while
charging), FCC compliant.
®
Software Test Instrument