Series TUF Ultrasonic Energy Meter
4´ RETURN PIPE TEMP SENSOR
Specications - Installation and Operating Instructions
[108.00]
4´ FLOW PIPE TEMP SENSOR
4´ RETURN PIPE TEMP SENSOR
4´ 4-CORE WIRE
[2 COMMUNICATION, 2 POWER]
H
2X D
THREAD
Model
TUF-150-XX
TUF-200-XX
TUF-250-XX
TUF-320-XX
TUF-400-XX
Dimensions in [mm] Flow Rate GPM [LPM]
4-21/64 [110.00]
5-1/8 [130.00]
6-19/64 [160.00]
7-3/32 [180.00]
7-7/8 [200.00]
G3/4B
G1B
G11/4B
G11/2B
G2B
3-31/32 [101.00]
3-31/32 [101.00]
4-11/64 [106.00]
4-29/64 [113.00]
4-49/64 [121.00]
Max Flow
(Qs)
13 [50]
22 [83]
31 [117]
53 [200]
88 [333]
DNXX
L
Nominal Flow
Range (Qp)
6.6 [25]
11 [42]
15 [58]
26 [100]
44 [167]
Bulletin F-TUF
2.8´ WATER-IN
FLOW SENSOR
2.8´ WATER-OU
FLOW SENSOR
Min Flow
(Qi)
0.1 [0.5]
0.2 [0.8]
0.3 [1.2]
0.5 [2]
0.9 [3.3]
Weight
lb [kg]L D H
3.1 [1.4]
3.1 [1.4]
4.1 [1.8]
5.2 [2.3]
6.6 [3.0]
4´ FLOW PIPE TEMP SENSOR
[2 COMMUNICATION, 2 POWER]
Dimensions in [mm] Flow Rate GPM [LPM]
Model
TUF-500-XX
TUF-650-XX
TUF-800-XX
TUF-1000-XX
TUF-1250-XX
The Series TUF Tennant Ultrasonic BTU Flowmeter is a MID/EN1434 approved
highly accurate and stable energy meter. It utilizes ultrasonic technology to measure
heating and cooling energy consumption. The Series TUF incorporates a owmeter,
temperature meter, and a calculator into a single, compact unit. The size and lack of
moving parts means the Series TUF requires minimal maintenance. The 8-digit LED
display enables easy reading of the meter’s recorded values; including temperature,
ow-rate, energy consumption, etc. These features make it ideal for installation on
chillers, boilers, and individual apartment piping. With the optional couplings it is
capable of being used with either NPT or BSPT pipe sizes. It is the perfect meter for
tenant billing applications.
FEATURES
• Lower maintenance costs with local parameter display and no moving parts
• Serial communication output allows for easy transfer of data
• Flow and temperature monitor in one unit eliminates the need for multiple units
Model
TUF-150-XX
TUF-200-XX
TUF-250-XX
TUF-320-XX
TUF-400-XX
TUF-500-XX
TUF-650-XX
TUF-800-XX
TUF-1000-XX
TUF-1250-XX
Process
Connection
G-3/4
G1
G1-1/4
G1-1/2
G2
GB9119 Flange
GB9119 Flange
GB9119 Flange
GB9119 Flange
GB9119 Flange
7-7/8 [200]
7-7/8 [200]
8-55/64 [225]
9-27/32 [250]
9-27/32 [250]
Corresponding
Pipe Fitting
1/2˝ NPT or BSPT
3/4˝ NPT or BSPT
1˝ NPT or BSPT
1-1/4˝ NPT or BSPT
1-1/2˝ NPT or BSPT
2˝ DN 50 PN 16 Flange
2-1/2˝ DN 65 Flange
3˝ DN 80 Flange
4˝ DN 100 Flange
5˝ DN 125 Flange
6-1/2 [165.00]
7-9/32 [185.00]
7-7/8 [200.00]
8-21/32 [220.00]
9-27/32 [250.00]
9-27/32 [250]
10-7/16 [265]
11-1/32 [280]
12-13/64 [310]
12-63/64 [330]
2.8´ WATER-IN FLOW SENSOR
4´ 4-CORE WIRE
L
4-59/64 [125.00]
5-45/64 [145.00]
6-19/64 [160.00]
7-3/32 [180.00]
8-17/64 [210.00]
SPECIFICATIONS
Service: Clean, compatible liquids.
Wetted Materials: Brass and 316L SS.
Range: See chart.
Display: 8-digit LED.
Accuracy: BTU: EN1434/CJ128 Class 2; Flow: ±(2+(0.02 Qp / Q))%; Temperature:
0.18°F (±0.1°C).
Power Requirements: 24 VDC or 3.6 V ER26500 lithium metal battery, user
supplied and installed, battery acts as back-up if power is lost.
Power Consumption: 1 W.
Temperature Limits: Ambient: 41 to 131°F (5 to 55°C); Process: 36 to 203°F (2 to
95°C).
Humidity Limit: <93%.
Pressure Limits: 232 psi (16 bar) for DN15 to DN40; 362 psi (25 bar) for >DN50.
Pressure Drop: <1.5 psi (10 kPa).
Process Connection: See chart.
Serial Communications: Modbus
Enclosure Rating: IP65.
Enclosure Material: Plastic.
Repeatability: Flowmeter: 1%.
Electrical Connections: 3 ft (0.91 m) 4x0.2 mm2 cable with terminal block.
Flow Direction: Unidirectional.
Mounting Orientation: Horizontal or vertical.
Weight: See chart.
Agency Approvals: CE.
45/64 [18.00]
45/64 [18.00]
45/64 [18.00]
45/64 [18.00]
45/64 [18.00]
2.8´ WATER-OUT FLOW SENSOR
´N´ NO. OF HOLES
[SEE TABLE]
H
ØD1 B.C.
ØD2
Max Flow
(Qs)
4
132 [500]
4
220 [833]
8
352 [1333]
8
528 [2000]
8
881 [3333]
®
RTU or BACnet MSTP (selectable)**.
Nominal Flow
Range (Qp)
66 [250]
110 [417]
176 [667]
264 [1000]
440 [1667]
Min Flow
(Qi)
0.7 [2.5]
1.1 [4.2]
1.8 [6.7]
2.6 [10]
4.4 [17]
ØD
Weight
lb [kg]L ØD H ØD1 ØD2 N
30.8 [14]
30.2 [13.7]
37.5 [17]
41.8 [19]
57.3 [26]
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Phone: 219/879-8000
Fax: 219/872-9057
www.dwyer-inst.com
e-mail: info@dwyermail.com

INSTALLATION INSTRUCTIONS
1. Install the meter as shown in either Figure 1 or Figure 2.
2. Mount the temperature sensor with the blue tag on the corresponding return pipe on
application. The sensor with the red tag has already been installed in the meter.
3. Flush the system in the proper direction until:
• No impurities remain in the lter and pipe.
• No water leaks when pressure is added to the system.
• The humidity inside the enclosure containing the meter does not exceed 93%.
4. After ushing for a period of time; close the ball valves on either side of the meter
and ush the impurities out of all lters.
*3.6 V ER26500 battery may be purchased separately to power display only.
INSTALLATION REQUIREMENTS
NOTICE
measuring accuracy.
1. Ensure that there is a 10 diameter straight run of pipe upstream and a 5 diameter
straight run of pipe downstream form the meter.
2. See the installation positions in Figure 3, in which A and B are the proper installation
positions, while C and D are the improper positions.
3. If the meter is installed on the horizontal pipe, it must be oriented at least 45° from
horizontal (see Figure 4). If the meter’s face is horizontal, then debris accumulation
can increase inaccuracies (see gure 5 for correct and incorrect orientations). There
is no special requirement when installing on the vertical pipe work.
4. Handle display with care. LCD display may damage with force.
Note: the meter can be installed on the return pipe or the supply pipe according to
user’s needs, but it should be selected in advance.
If the following requirements are not followed, then large air
particles and impurities in the pipe could inuence the meter’s
INSTALLATION NOTES
NOTICE
CAUTION
optional battery could cause the battery to explode and cause injury to people and
damage the meter.
1. Avoid tugging on the temperature probe’s cables.
2. Ensure the water is owing in the direction indicated by the arrow on the meter’s
body.
3. If several meters are installed on the same vertical pipe work, each meter should be
separated from the others to avoid pipe leakage or fallen debris that could affect the
other meters’ operation.
Do not directly weld the meter on to the pipe; the extreme heat
will damage the BTU meter’s internal elements.
Do not install the meter near a high temperature heat source
such as during electro gas welding. Doing so after installing an
STRAIGHT
JOINT
FILTER
PIPEPIPEPIPE PIPE PIPE
10D
UNION NUT
WATER RETURN
BALL
VALVE
BUTTERFLY
VALVE
RETURN WATER
TEMPERATURE
SENSOR
10D
BUTTERFLY
FILTER
VALVE
WATER SUPPLY
WATER RETURN
VALVE
WATER SUPPLY
STRAIGHT
VALVE
PIPE PIPE
D
5D
UNION NUT
BUTTERFLY
VALVE
JOINT
Figure 1: Installation Diagram for TUF-150/400
SENSOR
SLEEVE
5D
SUPPLY WATER
Figure 2: Installation Diagram for TUF-500/2000
Figure 3: Installation Positions
45° MIN.
45° MIN.
Figure 4: Mounting Rotation