Dwyer Instruments TUF-200-BN User manual

Page 1
Bulletin F-TUF-B
4´ RETURN PIPE TEMP SENSOR
[2 COMMUNICA
4´ FLOW PIPE TEMP SENSOR
2.8´ WATER-IN FLOW SENSOR
4-1/4
L
T
2.8´ WATER-IN
®
Series TUF Ultrasonic Energy Meter with BACnet Communication
Specications - Installation and Operating Instructions
Model TUF-500-XX
TUF-650-XX TUF-800-XX TUF-1000-XX TUF-1250-XX TUF-1500-XX TUF-2000-XX
TUF-150-XX TUF-200-XX TUF-250-XX TUF-320-XX TUF-400-XX TUF-500-XX TUF-650-XX TUF-800-XX TUF-1000-XX TUF-1250-XX
[108.00]
4´ FLOW PIPE TEMP SENSOR
4´ RETURN PIPE TEMP SENSOR
4´ 4-CORE WIRE
[2 COMMUNICATION, 2 POWER]
H
2X D
THREAD
4´ 4-CORE WIRE TION, 2 POWER]
L
Dimensions in [mm] Flow Rate GPM [LPM]
Model TUF-150-XX
TUF-200-XX TUF-250-XX TUF-320-XX TUF-400-XX
Dimensions in [mm] Flow Rate GPM [LPM]
11-13/16 [300.00] 11-13/16 [300.00] 13-25/32 [350.00] 13-25/32 [350.00] 13-25/32 [350.00] 11-13/16 [300.00] 11-13/16 [350.00]
MODEL CHART
Model
6-1/2 [165.00] 7-9/32 [185.00] 7-7/8 [200.00] 8-21/32 [220.00] 9-27/32 [250.00] 11-7/32 [285.00] 13-25/64 [340.00]
Process Connection
G-3/4
G1
G1-1/4 G1-1/2
G2
GB9119 ange GB9119 ange GB9119 ange GB9119 ange GB9119 ange
6-57/64 [175.00] 7-23/32 [196.00] 8-1/2 [216.00] 9-11/64 [233.00] 10-25/64 [264.00] 11-29/64 [291.00] 13-21/32 [347.00]
Corresponding Pipe Fitting Power Model
1/2˝ NPT or BSPT 3/4˝ NPT or BSPT 1˝ NPT or BSPT 1-1/4˝ NPT or BSPT 1-1/2˝ NPT or BSPT 2˝ DN 50 PN 16 ange 2-1/2˝ DN 65 ange 3˝ DN 80 ange 4˝ DN 100 ange 5˝ DN 125 ange
4-21/64 [110.00] 5-1/8 [130.00] 6-19/64 [160.00] 7-3/32 [180.00] 7-7/8 [200.00]
4-59/64 [125.00] 5-45/64 [145.00] 6-19/64 [160.00] 7-3/32 [180.00] 8-17/64 [210.00] 9-29/64 [240.00] 11-39/64 [295.00]
24 VAC/VDC 24 VAC/VDC 24 VAC/VDC 24 VAC/VDC 24 VAC/VDC 24 VAC/VDC 24 VAC/VDC 24 VAC/VDC 24 VAC/VDC 24 VAC/VDC
G3/4B
3-31/32 [101.00]
G1B
3-31/32 [101.00]
G11/4B
4-11/64 [106.00]
G11/2B
4-29/64 [113.00]
G2B
4-49/64 [121.00]
45/64 [18.00] 45/64 [18.00] 45/64 [18.00] 45/64 [18.00] 45/64 [18.00] 55/64 [22.00] 55/64 [22.00]
TUF-150-XX-DC TUF-200-XX-DC TUF-250-XX-DC TUF-320-XX-DC TUF-400-XX-DC TUF-500-XX-DC TUF-650-XX-DC TUF-800-XX-DC TUF-1000-XX-DC TUF-1250-XX-DC
Process Connection
G-3/4
G1
G1-1/4 G1-1/2
G2
GB9119 ange GB9119 ange GB9119 ange GB9119 ange GB9119 ange
2.8´ WATER-OUT FLOW SENSOR
Max Flow (Qs)
13 [50] 22 [83] 31 [117] 53 [200] 88 [333]
Max Flow (Qs)
4
132 [500]
4
220 [833]
8
352 [1333]
8
528 [2000]
8
881 [3333]
8
1321 [5000]
12
2202 [8333]
FLOW SENSOR
2.8´ WATER-OU FLOW SENSOR
´N´ NO. OF HOLES
[SEE TABLE]
H
ØD1 B.C.
ØD2
Nominal Flow Range (Qp)
6.6 [25] 11 [42] 15 [58] 26 [100] 44 [167]
Nominal Flow Range (Qp)
66 [250] 110 [417] 176 [667] 264 [1000] 440 [1667] 660 [2500] 1101 [4167]
Corresponding Pipe
Fitting Power
1/2˝ NPT or BSPT 3/4˝ NPT or BSPT 1˝ NPT or BSPT 1-1/4˝ NPT or BSPT 1-1/2˝ NPT or BSPT 2˝ DN 50 PN 16 ange 2-1/2˝ DN 65 ange 3˝ DN 80 ange 4˝ DN 100 ange 5˝ DN 125 ange
Min Flow (Qi)
0.1 [0.5]
0.2 [0.8]
0.3 [1.2]
0.5 [2]
0.9 [3.3]
Min Flow (Qi)
0.7 [2.5]
1.1 [4.2]
1.8 [6.7]
2.6 [10]
4.4 [17]
6.6 [25] 11 [42]
Weight lb [kg]L ØD H ØD1 ØD2 N
30.8 [14]
30.2 [13.7]
37.5 [17]
41.8 [19]
57.3 [26]
70.5 [32] 141 [64]
24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC 24 VDC
ØD
Weight lb [kg]L D H
3.1 [1.4]
3.1 [1.4]
4.1 [1.8]
5.2 [2.3]
6.6 [3.0]
The Series TUF Ultrasonic Energy Meter is a highly accurate and stable energy meter that utilizes ultrasonic technology to measure heating and cooling energy
consumption. The Series TUF is a compact meter with a owmeter and energy
calculator in one, making it great for installation on chillers and boilers.
FEATURES/BENEFITS
• Serial communication output allows for easy transfer of data
• Flow and temperature monitor in one unit eliminates the need for multiple units
APPLICATIONS
• Heat metering
• Utilities billing
• Tenant billing
• Monitoring of water heating or cooling: radiators, fan coils
INSTRUCTIONS FOR ORDERING
• Choose 1 ultrasonic energy meter model
• Choose 2 pipe tting models given the appropriate tting size (for DN15 to DN40
only)*
Example: TUF-150-MD, Fitting Size: A, select pipe tting Model WM-ACC-C01 or WM-ACC-C11. Note: Series TUF units are factory set for supply line installation. (Can be modied in the eld via communication protocol.)
SPECIFICATIONS
Service: Clean, compatible liquids.
Wetted Materials: Brass and 316L SS.
Range: See chart.
Display: 8-digit LED.
Accuracy: BTU: EN1434/CJ128 Class 2; Flow: ±(2+(0.02 Qp / Q))%; Temperature: ±0.1°C . Power Requirements: 24 VAC/VDC (model dependent)* or 3.6 V ER26500
lithium metal battery, user supplied and installed, battery acts as back-up if power is lost.
Power Consumption: 1 W. Temperature Limits: Ambient: 41 to
131°F (5 to 55°C); Process: 36 to 203°F (2 to 95°C). Humidity Limit: < 93%.
*Power supply must be oating, not grounded. Model numbers ending in “-DC” are for DC only applications.
**M-BUS available upon request.
Pressure Limits: 232 psi (16 bar) for DN15 to DN40; 362 psi (25 bar) for >DN50. Pressure Drop: < 1.5 psi (10 kPa).
Process Connection: See chart. Serial Communications: Modbus
or BACnet MSTP (model selectable)**.
Enclosure Rating: IP65. Enclosure Material: Plastic. Repeatability: Flowmeter: 1%. Electrical Connections: 3 ft (0.91 m)
4x0.2 mm2 cable with terminal block.
Flow Direction: Unidirectional. Mounting Orientation: Horizontal or
vertical.
Weight: See chart. Agency Approvals: CE.
®
RTU
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Page 2
ELECTRICAL WIRING
NEXT
TO
NOTICE
NOTICE
and Air-Conditioning Engineers, Inc., 2010.
NOTICE
Figure 1 shows how to connect the TUF in a network containing a common power
supply. Use a cable containing two twisted pairs. One pair is to be used for RS 485/ BACnet [+] and [-]. The other pair is used for power and common. This conguration is suitable for AC and DC supplies. Care should be taken that there are not too many
devices powered from the same supply as voltage drops will occur in the wiring. If you
have many devices, or have long cable runs, the local supply conguration may be a
better choice.
Figure 2 also shows how to connect the TUF in a network containing individual local supplies. Use a cable containing a twisted pair and a single conductor. The pair is to
be used for [+] and [-]. The single conductor is to be used for common.
All devices in the network should be daisy chained. Star connections and T connections
are not permitted.
PREVIOUS DEVICE
[+] [-] PWR
COM
Wiring should comply with Electrical Characteristics of Generators and Receivers for Use in Balanced Digital Multipoint Systems, TIA/ EIA-485-A-1998, Telecommunications Industry Association, 1998.
Wiring should comply with ANSI/ASHRAE Standard 135-2010 BACnet A Data Communication Protocol for Building Automation and Control Networks, American Society of Heating, Refrigerating
Communications wiring must be in a daisy-chain fashion. Star connections are not permitted.
TO
DEVICE
[+] [-] PWR
COM
Figure 1: Common local power supply
PROGRAMMING MENUS
Programing Via BACnet MS/TP Communication Protocol
Supported BACnet Communication Protocol MS/TP Conguration
Supported Baud Rates Data Size Parity Stop Bits
38400 8 None 1
BACnet Communication Protocol Object Overview The device Supports the following objects
Object Type
Device Analog Input Analog Input Analog Input Analog Input Analog Input Analog Input Analog Input Analog Input Analog Input Analog Input Analog Input Analog Input Analog Value Analog Value Analog Value Analog Value Analog Value
Device Information
The default device object identier is 32001. The object identier will change as the MS/TP MAC address changes.
Dynamically
Creatable
No No No No No No No No No No No No No No No No No No
Dynamically Deletable
No No No No No No No No No No No No No No No No No No
Object Identier
32001 AI0 AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8 AI9 AI10 AI11 AV0 AV1 AV2 AV3 AV4
Object Name
TUF
Inlet Water Temperature Outlet Water Temperature
Flow velocity
Power
TUF Communication Status Total Flow Total Heat Total Cool
The Status of Write The Version of TUF The Version of SSU SSU ID
Meter Mode
Balance Sheet Date Local Date
Local Time
TUF Address
NOTICE
[+] [-]
COM
+-
Figure 2: Local power supply
The TUF meter is provided standard with a 3 ft (0.91 m) cable with 4 x 0.2 mm that are Red, Black, Green and Yellow. As displayed in Figure 3, the Red wire is Power [+], Black wire is Common [-], and the Green and Yellow wires are for RS 485 BACnet Communication where Green is [-] and Yellow is [+].
RS 485/BACNET YELLOW [B+] GREEN [A-]
Figure 3: Cable labels
24 V RED+ BLACK-
[+] [-]
COM
2
wires
Accessing the Measurements
The analog input object AI1 through AI4 are for viewing the pressure measurement in
the desired engineering units. The object property tables for these analog input objects
can be found in Appendix III.
Analog value object AV1 through AV4 are for viewing the Air Velocity or Air Flow
calculated values in the desired engineering units. The object property tables for the
analog value objects can be found in Appendix IV.
Accessing the Measurements
The analog input object AI0 through AI2 and AI5 through AI7 are for viewing unit measurements in specic engineering units. The object property tables for these analog input objects with appropriate engineering units can be found in Appendix II.
Analog value object AV0 through AV21 are for viewing additional information such as
meter mode, balance sheet and time. The object property table for the analog value
objects with appropriate units and formats can be found in Appendix III and IV.
ADDITIONAL NOTES:
1. The communication write status features a power off save, where the last communicated information will be saved upon powering off the unit.
2. Information is accessed at a rate of 1 per minute.
3. Communication time is linked to the meter clock, and will automatically reset on power on. If the time needs to be corrected and is updated via the communications the meter clock will automatically update.
4. With respect to the accumulative heating capacity, accumulative cooling capacity and accumulative ow in the variable table, when this information is transferred
via communication only whole numbers will be uploaded. The decimal portion of
the reading will only be displayed on the TUF meter LCD screen.
Changes to Max Master and Max Info frames require a power cycle/reset to take effect.
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Page 3
INSTALLATION INSTRUCTIONS
BALL
BALL
D
TEMPERATURE SENSOR
1. Install the meter as shown in either Figure 1 or Figure 2.
2. Mount the temperature sensor with the blue tag on the corresponding return pipe on application. The sensor with the red tag has already been installed in the meter.
3. Flush the system in the proper direction until:
• No impurities remain in the lter and pipe.
• No water leaks when pressure is added to the system.
• The humidity inside the enclosure containing the meter does not exceed 93%.
4. After ushing for a period of time; close the ball valves on either side of the meter and ush the impurities out of all lters. *3.6 V ER26500 battery may be purchased separately to power display only.
INSTALLATION REQUIREMENTS
NOTICE
1. Ensure that there is a 10 diameter straight run of pipe upstream and a 5 diameter
straight run of pipe downstream form the meter.
2. See the installation positions in Figure 3, in which A and B are the proper installation positions, while C and D are the improper positions.
3. If the meter is installed on the horizontal pipe, it must be oriented at least 45° from horizontal (see Figure 4). If the meter’s face is horizontal, then debris accumulation can increase inaccuracies (see gure 5 for correct and incorrect orientations).
There is no special requirement when installing on the vertical pipe work. Note: the meter can be installed on the return pipe or the supply pipe according to
user’s needs, but it should be selected in advance.
If the following requirements are not followed, then large air
particles and impurities in the pipe could inuence the meter’s
measuring accuracy.
INSTALLATION NOTES
NOTICE
using digital communication protocols.
NOTICE
CAUTION
people and damage the meter.
1. Avoid tugging on the temperature probe’s cables.
2. Ensure the water is owing in the direction indicated by the arrow on the meter’s
body.
3. If several meters are installed on the same vertical pipe work, each meter should be separated from the others to avoid pipe leakage or fallen debris that could affect
the other meters’ operation.
If not specied at time of order, refer to appendix III to change from
supply to return programming. Change from supply to return, and vice-versa, is only possible
Do not directly weld the meter on to the pipe; the extreme heat will damage the BTU meter’s internal elements.
Do not install the meter near a high temperature heat source such as during electro gas welding. Doing so after installing an option­al battery could cause the battery to explode and cause injury to
STRAIGHT
VALV E
PIPE PIPE
D
5D
UNION NUT
BUTTERFLY
VALV E
JOINT
Figure 1: Installation diagram for TUF-150 to TUF-400
5D
SUPPLY WATER
Figure 2: Installation diagram for TUF-500 to TUF-2000
SENSOR
SLEEVE
STRAIGHT
JOINT
FILTER
PIPEPIPEPIPE PIPE PIPE
10D
UNION NUT
WATER RETURN
BALL
VALV E
BUTTERFLY
VALV E
WATER RETURN
RETURN WATER TEMPERATURE SENSOR
10D
BUTTERFLY
FILTER
VALV E
WATER SUPPLY
VALV E
WATER SUPPLY
45° MIN.
Figure 3: Installation positions
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Figure 4: Mounting rotation
45° MIN.
Page 4
FEATURES
• Works with both heating and cooling systems
• High accuracy The high quality ultrasonic transducer and advanced electronic measurement
technology work together to ensure the meter’s high accuracy and stability
• No moving parts
This decreases the maintenance cost and ensures that the meter is resistant to dirty water
• PT1000 platinum thermisters
• Low starting ow-rate The U-shaped acoustic path widens the dynamic ow-rate measurement range and
increases the accuracy of low and high end measurements where other, more narrow ranged, devices are inaccurate
• Horizontal or vertical installation
• Communication output ports can be used for automated meter reading
• Automatic diagnostic function. An error code will be displayed on the screen to
indicate the problem
• Ability to install an optional 3.6 V battery that can last up to 6 years
Yellow A+ (BACnet or Modbus)
Green B- (BACnet or Modbus)
Black- (DC24V)
Red+ (DC24V)
Temp Sensor In
Temp Sensor Out
Flow Sensor Out
Flow Sensor In
DISPLAY
1. Switching Between Information
Holding down the button for > 1s will switch the sections from curren information ▲, to monthly information ▲▲, and then to other information ▲▲▲. Once in the
desired section, pressing the key will switch the information shown for the given section.
2. Display Units Energy is displayed in kW•h, power is displayed in kW, ow volume is displayed as
m3, and ow-rate is displayed in m3/h.
3. Display Details a. “Monthly Reading Date” is displayed as “Pd= XX”, in which XX is the end date of the current month’s energy summation. The factory default value is 31,
meaning that the monthly recording period ends at midnight on the 31st day
of the month. At this time the current month’s cumulated energy will be stored and the system will begin to record the next month’s energy.
b. The meter can store and display the recordings from the past 18 months.
c. The units for “Sum of Working Time” (hours) is displayed as h.
d. “Software and Protocol Editions” are displayed as “UEr.X.X X.X”. The rst X.X is the software edition code and the second X.X is the communication
protocol edition code.
e. “Leaving-factory serial number” is the meter’s identication number, which is the same as the one in the external label. This serial number is a unique
number set by the factory; it is also the secondary address in M-BUS system.
f. Battery Voltage displays “UCC=X.XX” (the default unit is Volts). When the battery’s voltage capacity is lower than 2.9±0.1 V, “ ” will appear on the
display. This symbol will not appear if no battery is installed.
g. If there are any unresolved errors, the start date will display as normal but the
end date will display “00-00-00”, and then the error message will be displayed.
NOTES
1. If meter is not in use during freezing conditions, drain all water from the connecting pipe. Low temperatures will cause the water to freeze in the pipe and damage the meter.
2. This device is intended to be used with clean water. While dirty water will not
damage the meter, it will cause errors in the reading.
3. A lter should be mounted near the meter and cleaned regularly.
4. If the heat exchanging system is operating normally, but the instantaneous ow­ rate of the heat meter reduces signicantly, then there is too much dirt in the lter. This will narrow the pipe and reduce the ow. Cleaning the lter will x the problem.
5. To protect the meter and avoid damage from harsh conditions, it is recommended
that the meter be encased in an enclosure.
6. Primary Address: rst 2 digits of Manufacturer ID
7. Secondary Address: later 8 digits of Manufacturer ID
8. Company Code: BAS (08 33)
• Version: 54
Error Message Table Error
Messages Explanation
IN—CLOSE IN—OPEN OU—CLOSE OU—OPEN FL-OPEN
COD=XXXX
Temperature sensor of water supply is in closed state Temperature sensor of water supply is in open state Temperature sensor of return water is in closed state Temperature sensor of return water is in open state
Flow sensor failure. (Could be caused by air in the meter, the absence of water, or water owing in the wrong direction) There is an error in malfunction record. “XXXX” is the error code
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Page 5
4. Display Menus
Current Information Monthly Information Other Information
Hold button
Sum of cooling
energy
Sum of heating
energy
Power
Sum of flow rate
Flow velocity
Forward temperature
Press button
Press button
Press button
Press button
Press button
Monthly reading
date
Current date
Sum of monthly
energy
History reading
date 1
History reading
energy 1
Sum of flow rate 1
Press button
Press button
Press button
Press button
Press button
Press button
Hold button
Current: Year,
month, date
Current: Hour,
minute, second
Sum of current
working time
LCD segment test
Protocol version
Primary address
Press button
Press button
Press button
Press button
Press button
Press button
Return temperature
History reading
date 2
Temperature
difference
WARRANTY/RETURN
Refer to “Terms and Conditions of Sale” in our catalog and on our website. Contact customer service to receive a Return Goods Authorization number before shipping the
product back for repair. Be sure to include a brief description of the problem plus any additional application notes.
Press button
History reading
energy 2
Sum of flow rate 2
-History reading date 2
-History reading energy 2
-Sum of flow rate 2
Press button
Press button
Press button
-Error 4 message
-Error 4 beginning time
-Error 4 ending time
Secondary address
Battery voltage
Error 1 message
Error 1 beginning
time
Error 1 ending time
Press button
Press button
Press button
Press button
Press button
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Page 6
APPENDIX I: DEVICE OBJECT PROPERTY TABLE Property Default Value Property Data Type Access
Object Identier Object Name
Object Type System Status
Vendor Name Vendor Identier Model Name Firmware Revision Application Software Version Description Protocol Version Protocol Revision Protocol Services Supported Protocol Object Types Supported
Object List
Maximum APDU Length Accepted
Segmentation Supported
32001
Ultrasonic BTU Meter
DEVICE (8) Operation (0) Dwyer Instruments, Inc. 607 TUF-XX-BN “X.X” “X.X” Basic Protocol Converter
1
5 Read Property; write property; who-is Analog Input, Analog Value, Device
See Table on page 3
50 NO_SEGMENTS (3)
BACnetObjectIdentier CharacterString (32) BACnetObjectiveType BACnet Device Status
CharacterString Unsigned CharacterString CharacterString CharacterString
CharacterString (32)
Unsigned Unsigned
BACnet ServicesSupported BACnetObjectTypes Supported BACnetArray
Unsigned
BACnet Segmentation
Read/Write Read/Write Read Read Read Read Read Read Read Read/Write Read Read Read
Read Read Read
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Page 7
APPENDIX II: ANALOG INPUT OBJECT PRODUCT TABLE Property Default Value Property Data Type Access
Object Identier Object Name
Object Type
Present Value
Status Flags Event State Units
AI0 Inlet Water Temperature ANALOG_INPUT (0) Current Reading 0 NORMAL (0) Celsius (62)
BACnetObjectIdentier
CharacterString
BACnetObjectType Real BACnetStatusFlags BACnetEventState BACnetEngineeringUnits
Read Read Read Read Read Read Read
APPENDIX II: ANALOG INPUT OBJECT PRODUCT TABLE Property Default Value Property Data Type Access
Object Identier Object Name
Object Type
Present Value
Status Flags Event State Units
AI6
Total Heat
ANALOG_INPUT (0) Current Reading 0 NORMAL (0) Kilowatt hours (19)
BACnetObjectIdentier
CharacterString
BACnetObjectType Real BACnetStatusFlags BACnetEventState BACnetEngineeringUnits
Read Read Read Read Read Read Read
APPENDIX II: ANALOG INPUT OBJECT PRODUCT TABLE Property Default Value Property Data Type Access
Object Identier Object Name
Object Type
Present Value
Status Flags Event State Units
APPENDIX II: ANALOG INPUT OBJECT PRODUCT TABLE Property Default Value Property Data Type Access
Object Identier Object Name
Object Type
Present Value
Status Flags Event State Units
APPENDIX II: ANALOG INPUT OBJECT PRODUCT TABLE Property Default Value Property Data Type Access
Object Identier Object Name
Object Type
Present Value
Status Flags Event State Units
APPENDIX II: ANALOG INPUT OBJECT PRODUCT TABLE Property Default Value Property Data Type Access
Object Identier Object Name
Object Type
Present Value
Status Flags Event State Units
AI1 Outlet Water Temperature ANALOG_INPUT (0) Current Reading 0 NORMAL (0) Celsius (62)
AI2 Volume ANALOG_INPUT (0) Current Reading 0 NORMAL (0) Cubic meter per hour (135)
AI3 Power ANALOG_INPUT (0) Current Reading 0 NORMAL (0) Kilowatts (48)
AI4
TUF Communication Status
ANALOG_INPUT (0) Current Reading 0 NORMAL (0) No units (95)
BACnetObjectIdentier
CharacterString
BACnetObjectType Real BACnetStatusFlags BACnetEventState BACnetEngineeringUnits
BACnetObjectIdentier
CharacterString
BACnetObjectType Real BACnetStatusFlags BACnetEventState BACnetEngineeringUnits
BACnetObjectIdentier
CharacterString
BACnetObjectType Real BACnetStatusFlags BACnetEventState BACnetEngineeringUnits
BACnetObjectIdentier
CharacterString
BACnetObjectType Real BACnetStatusFlags BACnetEventState BACnetEngineeringUnits
Read Read Read Read Read Read Read
Read Read Read Read Read Read Read
Read Read Read Read Read Read Read
Read Read Read Read Read Read Read
APPENDIX II: ANALOG INPUT OBJECT PRODUCT TABLE Property Default Value Property Data Type Access
Object Identier Object Name
Object Type
Present Value
Status Flags Event State Units
APPENDIX II: ANALOG INPUT OBJECT PRODUCT TABLE Property Default Value Property Data Type Access
Object Identier Object Name
Object Type
Present Value
Status Flags Event State Units
APPENDIX II: ANALOG INPUT OBJECT PRODUCT TABLE Property Default Value Property Data Type Access
Object Identier Object Name
Object Type
Present Value
Status Flags Event State Units
APPENDIX II: ANALOG INPUT OBJECT PRODUCT TABLE Property Default Value Property Data Type Access
Object Identier Object Name
Object Type
Present Value
Status Flags Event State Units
AI7
Total Cool
ANALOG_INPUT (0) Current Reading 0 NORMAL (0) Kilowatt hours (19)
AI8 The Status of Write ANALOG_INPUT (0) Current Reading 0 NORMAL (0) No units (95)
AI9
The version of TUF
ANALOG_INPUT (0) Current Reading 0 NORMAL (0) No units (95)
AI10
The version of SSU
ANALOG_INPUT (0) Current Reading 0 NORMAL (0) No units (95)
BACnetObjectIdentier
CharacterString
BACnetObjectType Real BACnetStatusFlags BACnetEventState BACnetEngineeringUnits
BACnetObjectIdentier
CharacterString
BACnetObjectType Real BACnetStatusFlags BACnetEventState BACnetEngineeringUnits
BACnetObjectIdentier
CharacterString
BACnetObjectType Real BACnetStatusFlags BACnetEventState BACnetEngineeringUnits
BACnetObjectIdentier
CharacterString
BACnetObjectType Real BACnetStatusFlags BACnetEventState BACnetEngineeringUnits
Read Read Read Read Read Read Read
Read Read Read Read Read Read Read
Read Read Read Read Read Read Read
Read Read Read Read Read Read Read
APPENDIX II: ANALOG INPUT OBJECT PRODUCT TABLE Property Default Value Property Data Type Access
Object Identier Object Name
Object Type
Present Value
Status Flags Event State Units
AI5
Total Flow
ANALOG_INPUT (0) Current Reading 0 NORMAL (0) Cubic meters (80)
BACnetObjectIdentier
CharacterString
BACnetObjectType Real BACnetStatusFlags BACnetEventState BACnetEngineeringUnits
Read Read Read Read Read Read Read
APPENDIX II: ANALOG INPUT OBJECT PRODUCT TABLE Property Default Value Property Data Type Access
Object Identier Object Name
Object Type
Present Value
Status Flags Event State Units
AI11 SSU ID ANALOG_INPUT (0) Current Reading 0 NORMAL (0) No units (95)
BACnetObjectIdentier
CharacterString
BACnetObjectType Real BACnetStatusFlags BACnetEventState BACnetEngineeringUnits
Read Read Read Read Read Read Read
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Page 8
APPENDIX III: ANALOG VALUE OBJECT PROPERTY TABLE Property Default Value Property Data Type Access
Object Identier Object Name
Object Type
Present Value
Status Flags Event State Units
APPENDIX III: ANALOG VALUE OBJECT PROPERTY TABLE Property Default Value Property Data Type Access
Object Identier Object Name
Object Type
Present Value
Status Flags Event State Units
APPENDIX III: ANALOG VALUE OBJECT PROPERTY TABLE Property Default Value Property Data Type Access
Object Identier Object Name
Object Type
Present Value
Status Flags Event State Units
APPENDIX III: ANALOG VALUE OBJECT PROPERTY TABLE Property Default Value Property Data Type Access
Object Identier Object Name
Object Type
Present Value
Status Flags Event State Units
AV0
Meter Mode
ANALOG_VALUE (2)
1
0 NORMAL (0) No units (95)
AV1 Balance Sheet Date ANALOG_VALUE (2)
31
0 NORMAL (0) No units (95)
AV2 Local Date ANALOG_VALUE (2) Current Date 0 NORMAL (0) No units (95)
AV3
Current Time
ANALOG_VALUE (2) Current Reading 0 NORMAL (0) No units (95)
BACnetObjectIdentier
CharacterString
BACnetObjectType Real BACnetStatusFlags BACnetEventState BACnetEngineeringUnits
BACnetObjectIdentier
CharacterString
BACnetObjectType Real BACnetStatusFlags BACnetEventState BACnetEngineeringUnits
BACnetObjectIdentier
CharacterString
BACnetObjectType Real BACnetStatusFlags BACnetEventState BACnetEngineeringUnits
BACnetObjectIdentier
CharacterString
BACnetObjectType Real BACnetStatusFlags BACnetEventState BACnetEngineeringUnits
Read Read Read Read Read Read Read
Read Read Read Read Read Read Read
Read Read Read Read Read Read Read
Read Read Read Read Read Read Read
APPENDIX III: ANALOG VALUE OBJECT PROPERTY TABLE Property Default Value Property Data Type Access
Object Identier Object Name
Object Type
Present Value
Status Flags Event State Units
APPENDIX III: ANALOG VALUE OBJECT PROPERTY TABLE Property Default Value Property Data Type Access
Object Identier Object Name
Object Type
Present Value
Status Flags Event State Units
APPENDIX IV: VARIABLE TYPE/FORMAT Object Identier Description Type/Format
AI0 AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8 AI9 AI10 AI11 AV0 AV1 AV2 AV3 AV4 AV21
AV4 TUF Address ANALOG_VALUE (2)
127
0 NORMAL (0) No units (95)
AV21
Temperature Compensation Mode
ANALOG_VALUE (2) 0 0 SUPPLY (0) No units (95)
Inlet Water Temperature Outlet Water Temperature
Flow velocity
Power
TUF Communication Status Total Flow Total Heat Total Cool
The Status of Write The Version of TUF The Version of SSU SSU ID
Meter Mode
Balance Sheet Date Local Date
Local Time
TUF Address
Temperature Compensation Mode
BACnetObjectIdentier
CharacterString
BACnetObjectType Real BACnetStatusFlags BACnetEventState BACnetEngineeringUnits
BACnetObjectIdentier
CharacterString
BACnetObjectType Real BACnetStatusFlags BACnetEventState BACnetEngineeringUnits
Forward ow temperature (temperature forward) Return ow temperature (temperature return)
Flow rate of TUF
Power of TUF TUF meter: 0: success 1: failure Accumulative ow of TUF
Total heat quantity of TUF Total cold quantity of TUF
1: failure 0: success
Meter version Communication version
Communication ID 0: cold mode 1: heat mode
1~31 available
Format: year month date [Example: 151213 means 13 December 2015] Format: week hour minute second [Example: 17125630 means Sunday 12:56:30 (7 is Sunday, 1 is Monday….)] 0 to 127 0: Unit installed on supply 1: Unit installed on return 2, 3: Reserved for factory use only
Read Read Read Read Read Read Read
Read Read
Read Read Read Read Read
Modbus® is a registered trademark of Schneider Automation, Inc.
©Copyright 2021 Dwyer Instruments, Inc. Printed in U.S.A. 1/21 FR# 444246-70 Rev. 2
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
Loading...