Series
10-23/64
[263.13]
1/2 NPT
ø1/4
[ø6.35]
4-15/32
[113.51]
1/2 NPT
2-23/32
[69.06]
3-29/32
[99.22]
1/2 NPT
4-9/32
[108.74]
TTE
Explosion-Proof RTD Temperature Transmitter
User Selectable Ranges, Optional LCD Display
*Shown with optional LCD display
The Series TTE Explosion-Proof RTD Temperature Transmitter is the
ideal product for hazardous temperature measurement applications. The TTE
series has seven pre-programmed temperature ranges that are selectable via an
internal dip switch. For those applications that need a custom range, the
transmitter can be easily configured for any range between -30 to 250°F with a
minimum span of 40°F. The span and zero can be quickly adjusted with a simple
push button design. The compact housing allows for the transmitter to be
mounted in virtually any application.
Model
TTE-104-W
TTE-106-W
TTE-109-W
TTE-112-W
TTE-115-W
TTE-118-W
TTE-104-W-LCD
TTE-106-W-LCD
TTE-109-W-LCD
TTE-112-W-LCD
TTE-115-W-LCD
TTE-118-W-LCD
Stem Length
4˝
6˝
9˝
12˝
15˝
18˝
4˝
6˝
9˝
12˝
15˝
18˝
LCD Display
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
SPECIFICATIONS
Temperature Sensor: Pt1000, 0.00385 DIN.
Output Temperature Ranges: User selectable – any range between -30
to 250°F with a minimum span of 40°F.
Temperature Limits: Ambient: 0 to 158°F (-18 to 70°C); Process: -30 to
250°F (-34.4 to 121.1°C).
Accuracy: Transmitter ±0.1% FS; Probe ±0.3% FS.
Thermal Drift Effects: ±0.02%/°C max.
Response Time: 250 ms.
Wetted Materials: 316 SS.
Process Connection: 1/2˝ male NPT.
Conduit Connection: 1/2˝ female NPT.
Probe Length: 2˝ to 18˝ (depending on model).
Pressure Limits: 2000 psi (137.9 bar).
Power Requirements: 10 to 35 VDC.
Output Signal: 4 to 20 mA (two wire loop powered).
Optional Display: 2 lines X 8 character LCD.
Enclosure Rating: NEMA 4X (IP66) and explosion-proof for Class I,
Groups B, C, D; Class II, Groups E, F, G; Class III.
Weight: 2 lb 8 oz (1134 g).
Agency Approvals: CE, FM.
TEMPERATURE
ACCESSORY
A-287, Mounting bracket for pipe or surface mounting
(Includes bracket and two 2˝ U-bolts)
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
Field-Selectable Ranges
40 to 90°F (4.4 to 32.2 °C)
-20 to 140°F (-28.9 to 60°C)
0 to 100°F (-17.8 to 37.8°C)
30 to 240°F (-1.1 to 115.6°C)
32 to 212°F (0 to 100°C)
32 to 122°F (0 to 50°C)
-30 to 65°C (-1.1 to 18.3°C)
Custom range between -30 to 250˚F (-34.4 to 121.1˚C)
281
Transmitters
Temperature