Series TSW Dual Stage Digital Temperature Switch
2-19/32
[
65.53]
3
-5/8
[92.08]
6
-21/32
[
168.91]
Specifications - Installation and Operating Instructions
Bulletin T-TSW-2
he Series TSW Digital Temperature Switch combines the trusted, reliable TS
T
amily of temperature controls and an installation friendly weatherproof enclosure.
f
y using the same programming parameters as our Series TS2 and Series TSS2,
B
set up can be quickly completed using the front keys or by using the TS2-K configuration key. In order to prevent tampering from unauthorized users, a parameter lock physical jumper and software passcode security are standard in the unit.
The bright, easy-to-read LED display shows the current output status and the temperature measurement.
The multiple conduit knockouts on the Series TSW give flexibility to the installer to
determine the best location for the conduit entry. Another installation friendly feature of the Series TSW is the ability to quickly jumper the line voltage to the common of the output relay using fast tabs.
INSTALLATION
NOTICE: The thermostat must be installed by authorized professionals. It should
be located in a place free of vibrators, impacts, and corrosive gases.
NOTICE: Protective plastic overlay should be peeled off after final installation.
SPECIFICATIONS
Probe Range:
TC: -58 to 302°F (-50 to 150°C).
P
NTC: -58 to 230°F (-50 to 110°C).
Input: PTC (1000 Ω @ 25°C)/NTC (10KΩ @ 25°C).
Output: R1 SPDT Relay Resistive Load: 20A @ 240 VAC; R2 SPDT Relay
Resistive Load: 8A @ 240 VAC, Inductive Load: 3A @ 240 VAC.
Horsepower Rating: R1 2HP @ 240 VAC.
Control Type: On/Off.
Power Requirements: 90 to 255 VAC or 12 to 24 VAC/VDC (±10%) depending
on model.
Power Consumption: 3.6VA.
Accuracy: ±1% FS.
Display: 3 digits plus sign.
Resolution: .1° < 100°; 1° ≥ 100°.
Memory Backup: Non-volatile memory.
Ambient Temperature: 32 to 104°F (0 to 40°C).
Weight: 1.2 lbs (544 g).
Front Protection: NEMA 4X (IP66).
Agency Approvals: CE, UL, cUL.
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A. Fax: 219/872-9057 e-mail: info@dwyermail.com
IRING INSTRUCTIONS
PROBE
INPUTS
1 2 3 4 5 6 7 8 9 10 11
OUTPUTS
OUT 2
Sd2 Sd1
TS2-K
O
UT 1
POWER
SUPPLY
W
iring diagram is displayed on the inside cover of the unit and in figure 1.
W
OTICE: If the length of the probe cables measures more than 100 meters, a recal-
N
ibration adjustment must be made (parameter P1).
ressing SET and UP keys simultaneously will display the temperature of the probe
P
ot selected by P4 will be displayed. When the probe not selected by P4 is dis-
n
layed, it alternates its value with message Sd1 or Sd2 depending if it is probe 1 or
p
robe 2. Pressing SET and DOWN keys simultaneously will cancel. The display
p
blinks when waiting for a value confirmation.
NOTICE: Avoid installing the probe cables in proximity with any power cables.
Figure 1
ROGRAMMING PARAMETERS
P
n order to adjust parameter values, parameter lock jumper must be set in unlocked
I
osition (see figure 2).
p
Locked Unlocked
igure 2
F
Access only to Set Points SP1 and SP2 (without code protection):
• Press SET key. Out1 LED and out1 set point value will flash on the
display.
• Modify the out1 set point value using the UP and DOWN keys.
• Press SET key to store the out1 set point value and advance to out2
set point value.
• Modify the out2 set point value using the UP and DOWN keys.
• Press SET key to store the value and return to home screen.
Access to all parameters (code protected):
• Press SET for 8 seconds. The access code value 0 is shown on the
display.
• Using the UP and DOWN buttons, set the code (factory-set code is
0).
• Press SET to confirm the code. If it is correct, the first parameter label will be
shown on the display (SP1).
• Move to the desired parameter with the UP and DOWN keys.
• Press SET to see the value of the parameter.
• Modify the value with the UP and DOWN keys.
• Press SET to store value.
• Press SET and DOWN to quit programming, or wait 1 minute for the TIMEOUT.
Resetting the parameter pass code
The parameter code can be set to zero by holding the SET key and turning the controller off then on again.
LED INDICATIONS
Out1: Indicates relay 1 On or Off as per parameter H2. If H2=dir, with relay 1 On,
LED lit, if H2=inv, with relay 1 On, LED off. It blinks when SP1 is displayed.
Out2: Indicates relay 2 On or Off as per parameter H3. If H3=dir, with relay 2 On,
LED lit, if H3=inv, with relay 2 On, LED off. It blinks when SP2 is displayed.
Silence the Buzzer
ressing the SET and DOWN keys simultaneously silences the buzzer. The mes-
P
age of alarm continues appearing in the display.
s
esetting Parameters to Factory Values
R
• Access parameter H0 as explained in programming parameters.
• Value 0 will be displayed.
• Press SET for 8 seconds. Pro will be displayed if they have been setup
orrectly.
c
Press SET + DOWN to exit setup or wait for 1 minute.
•
arameter List
P
Range
Description
et point 1
S
P1
S
et point 2
S
P2
S
Dependency SP1 to SP2
r0
Differential for SP1
r1
Differential for SP2
r2
Band differential
r3
owest value for SP1
L
4
r
owest value for SP2
L
5
r
ighest value for SP1
H
6
r
Highest value for SP2
r7
Regulation or Operating Mode
r8
Alarm Differential
A0
Maximum alarm probe 1
A1
aximum alarm probe 2
M
2
A
Minimum alarm probe 1
A3
Minimum alarm probe 2
A4
Alarm verification time
A5
Alarm probe 1 selection
A6
Alarm probe 2 selection
A7
Minimum relay stop time
c0
Operation relay 1
c1
Operation relay 2
c2
Fail Safe Operation relay 1
c3
Fail Safe Operation relay 2
c4
Temperature Units Selection
P0
Calibration Probe 1
P1
Calibration Probe 2
P2
Decimal Point
P3
Probe to be displayed
P4
Number of Probes
P5
Factory Reset Values
H0
Keypad tamper protection
H1
Operation of Out1 LED
H2
Operation of Out2 LED
H3
Address for serial communication
H4
Access code to parameters
H5
Probe Type Selection
H6
(*) h-m are data in format XX.Y where XX are hours and Y tens of minutes.
Units
egrees
D
egrees
D
Option
Degrees
Degrees
Degrees
egrees
D
egrees
D
egrees
D
Degrees
Option
Degrees
Degrees
egrees
D
Degrees
Degrees
h-m(*)
Option
Option
Minutes
Option
Option
Option
Option
Option
Degrees
Degrees
Option
Option
Option
Option
Option
Option
Option
Range
Range
Option
4 to r6
r
5 to r7
r
Ind or dep
0.1 to 20.0
0.1 to 20.0
0.1 to 20.0
99.9 to r6
-
99.7 to r7
4 to 302
r
r5 to 302
On1, On2, nEU
0.1 to 20.0
0.1 to 99.9
.1 to 99.9
0
0.1 to 99.9
0.1 to 99.9
0.0 to 18.0
AHL, Ano, AH, AL
AHL, Ano, AH, AL
0 to 240
dir or inv
dir or inv
Opn or Clo
Opn or Clo
°C or °F
-20 to 20
-20 to 20
no or yes
sd1 or sd2
1 or 2
0
no or yes
dir or inv
dir or inv
0-999
0-999
Ptc or ntc
Factory
alue
V
0.0
1
0.0
1
ind
1.0
1.0
1.0
99.9
-
99.9
02
3
302
On1
0.1
99.9
9.9
9
99.9
99.9
18.0
AHL
AHL
O
dir
dir
Opn
Opn
°C
0.0
0.0
yes
sd1
1
0
no
dir
dir
0
0
PTC
Error Messages
Under normal operation, the temperature of the probe selected by P4 will be displayed, the following messages may also appear:
• Err Memory reading error.
• ErP Error of the probe not shown on the display.
• AH1 Maximum temperature alarm, probe 1.
• AL1 Minimum temperature alarm, probe 1.
• AH2 Maximum temperature alarm, probe 2.
• AL2 Minimum temperature alarm, probe 2.
• ooo Open probe.
• --- Shorted probe.