• Dependent ON/OFF control
If rh8=ono and rh0=dEP, output 3 works as in Independent ON/OFF control, but output 4 works as follows: If ch3=dir, output 4 will connect when HS >= Sh1+Sh2+rh2 and will disconnect when HS <= Sh1+Sh2.
Humidity
Sh1+Sh2+rh2
Sh1+Sh2
Output 4 ON
ch1
Time
If ch3=Inv, output 4 will connect when HS <= Sh1+Sh2-rh2 and will disconnect when HS >= Sh1+Sh2. ch1 is the minimum stop time.
Humidity
Sh1+Sh2
Sh1+Sh2-rh2
Output 4 ON
ch1
Time
• Neutral zone control
If rh8 = NEu output 3 connects when HS >= Sh1+rh3 and disconnects when HS <= Sh1, while output 4 connects when Hs1 <= Sh1-rh3 and disconnects when HS >= Sh1.
Humidity
Sh1+rh3
Sh1
Sh1-rh3
Output 3 ON
Output 4 ON
Time
• Control with probe errors
If reading of humidity probe fails the output 3 works following 10 minutes cycles, with a percentage of connection time given by Ch4. Output 4 is carried out in the same way with parameter Ch5.
• Humidity alarms
If HS >= Sh1+Ah1, the controller will indicate maximum humidity alarm for (AHH) and the alarm will remain activated until HS <= Sh1+Ah1-Ah0. If HS <= Sh1-Ah2, the controller will activate minimum humidity alarm for (ALH), and it will remain activated until HS >= Sh1-Ah2­Ah0. Program Ah3 to indicate the alarm check time between alarm event and indication of an alarm event. The alarm is indicated by a message on the display and activating the alarm output if present (alarm can be silenced pressing UP+DOWN keys or CLEAR in the IR remote control).
Humidity
Sh1+Ah1
Sh1+Ah1-Ah0
High Alarm ON
Humidity
Sh1-Ah2
Sh1-Ah2+Ah0
Low Alarm ON
• Probe options
If the probe is not placed in the exact point to control, use a standard hygrometer to determine the offset and set it by Ph0.
Set Ph1 to select if the decimal point is shown or not in the display. Set Ph2 to set the probe type (0-1V, CRPH03 or 4-20mA). If a 4-20mA probe is used, use Ph3 to set the humidity value for 4mA and Ph4 to set the value for 20mA.
General parameters
H1,H2,H3 are general parameters that can be accessed from both temperature and humidity parameters. Setting H1 to yES the set points (St1,St2,Sh1,Sh2) cannot be changed. To unblock this protection, press SET T or SET H for 8 seconds and introduce the code in the same way as is done when entering parameters. H2 sets the communication address for the controller. H3 sets the access code to parameters.
Led indication and display messages
The four OUT leds indicate the of the four outputs (when the correspondent led is ON the output is connected and when the led is OFF the output is disconnected).
In normal operation, the left display will show the temperature measured by probe 1 and the right display the relative humidity. In order to display the temperature measured by probe 2 press SET T + UP keys.
In case of alarm or error, the following messages can be shown:
Err = Memory reading error
ErP = Error in the temperature probe 2
• AHt = High temperature alarm (probe 1)
• ALt = Low temperature alarm (probe 1)
• AHh = High humidity alarm
• ALh = Low humidity alarm
• ooo = Open Probe Error
• --- = Short Circuit Probe Error
Maintenance, cleaning and repair
After final installation of the unit, no routine maintenance is required.
Clean the surface of the display controller with a soft and damp cloth. Never use abrasive detergents, petrol, alcohol or solvents.
All repairs must be made by authorised personnel.
THC Series Temperature and Humidity Controller
Specification and Operating Instructions
Description
The THC is a temperature and humidity digital controller. The temperature control can be ON-OFF, neutral zone and refrigeration modes. It is possible to set a second temperature probe for defrosting control. Humidity control can be ON-OFF and neutral zone modes. The humidity probe can be 0-1V, 0-3V THC-P and 4­20mA types.
Model references
The model reference is given by: THC-YZ
Each sufix can take the following values:
Y Supply Voltage 1=115VAC, 2=230VAC Z Temp. Units 0=ºF, 1=ºC
Installation
NOTE: Unit must be mounted away from vibration, impacts, water and corrosive gases.
Cut hole in panel 131 .15 x 3.97 inches).
Remove the rear cover to wire the unit.
The wiring diagram is shown in the unit label.
Apply silicone (or rubber gasket) around the perimeter of the hole
Insert the unit in the panel hole. Replace the rear cover.
Place removable fitting clips from the back of the until it is secured
to the panel.
Fit the clip in the panel and then press to fit the other side in the
unit.
x 101 mm (5
Wiring Diagram
OUT4 OUT3 OUT2 OUT1
RX TX GND IN VCC
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
SUPPLY
Sd1 Sd2 SH
Technical Data
Supply voltages 115 VAC10%, 230 VAC10%
Supply powers 7VA (230V)
Storage temperature -20ºC to 80ºC (-4 to 176ºF)
Operating temperature 0ºC to 70ºC (32 to 158ºF)
Temperature probe PTC1000 (25ºC - 1000 Ohm)
Temperature probe range -50ºC to 150ºC (-58 to 302ºF)
Temperature accuracy Better than 0,5
Temperature resolution
0.1º (3 digits)
Humidity probe 0-1V, 0-3V THC-P 4-20mA
Humidity probe range 0 to 100% RH
Humidity accuracy Better than 5
Humidity resolution 1% (3 digits)
Displays 3-digit and sign (x2)
Outputs SPDT relay 250Vac 8A RL
Dimensions 134x105x61mm (5.3x4.1x2.4 in)
Front Protection IP65
% of full scale
,
% of full scale
%H
LOVE CONTROLS DIVISION Phone: 219/879-8000 www.love-controls.com DWYER INSTRUMENTS, INC. Fax: 219/872-9057 e-mail:love@love-controls.com P.O. BOX 338 - MICHIGAN CITY, Lit-By Fax: 888/891-4963 INDIANA 46361, U.S.A.
ETDT1076L_060705 ETDT1076L_060705
Temperature Probe 1 (Sd1) in terminals 18 - 17 Temperature Probe 2 (Sd2) in terminals 19 - 17 Humidity Probe (SH) in terminals 20-21-17
Note: DO NOT INSTALL PROBE CABLES NEAR POWER
CABLES.
LOVE CONTROLS DIVISION Phone: 219/879-8000 www.love-controls.com DWYER INSTRUMENTS, INC. Fax: 219/872-9057 e-mail:love@love-controls.com P.O. BOX 338 - MICHIGAN CITY, Lit-By Fax: 888/891-4963 INDIANA 46361, U.S.A.
List of temperature parameters
Description Units Range
St1 Temperature set point 1 Degrees rt4 to rt6 St2 Temperature set point 2 Degrees rt5 to rt7 rt0 St1 and St2 dependency Range Ind / dEP rt1 Differencial for St1 Degrees 0.1 to 20.0 rt2 Differencial for St2 Degrees 0.1 to 20.0 rt3 Band differencial Degrees 0.1 to 20.0 rt4 Minimum value for St1 Degrees -99.9 to rt6 rt5 Minimum value for St2 Degrees -99.9 to rt7 rt6 Maximum value for St1 Degrees rt4 to 302 rt7 Maximum value for St2 Degrees rt5 to 302 rt8 Operation mode Range ono/rEF/nEU dt0 Defrosting type Range fRES/InV dt1 Max. defrosting temperature Degrees -99.9 to 302 dt2 Max. defrosting time Minutes 0 to 240 dt3 Defrosting interval time hh:mm 0.0 to 18.0 dt4 Defrosting displayed temp. Range off/on/-d­At0 Alarm differencials Degrees 0.1 to 20.0 At1 Maximum probe 1 alarm Degrees 0.1 to 99.9 At2 Minimum probe 1 alarm Degrees 0.1 to 99.9 At3 Alarm check time hh:mm 0.0 to 18.0 ct0 Minimum stop time output 1 Minutes 0 to 240 ct1 Minimum stop time output 2 Minutes 0 to 240 ct2 Operation output 1 Range DIr/Inv ct3 Operation output 2 Range DIr/Inv ct4 Default operation output 1 %ON 0 to 100 ct5 Default operation output 2 %ON 0 to 100 ct6 Continuous cycle time Minutes 0 to 240 Pt0 Temp. probe adjustment Degrees -20.0 to 20.0 Pt1 Decimal point Option no/yES Pt2 Temperature units Range ºC/ºF Pt3 Number of temp. probes Range 1 / 2 H0 Set default settings Command H1 Keypad protection Option no/yES H2 Communication setup Numeric 0 to 999 H3 Access code to parameters Numeric 0 to 999
Temperature parameter programming
Set Points (St1,St2) are the only parameters the user can access without code protection.
•Press SET T. Current value of St1 appears flashing and led OUT 1 flashes.
•The value can be modified with the UP and DOWN arrows.
•Press SET again to confirm St1. Current value of St2 appears flashing and led OUT 2 flashes.
•The value can be modified with the UP and DOWN arrows.
•Press SET to enter St2 value and exit.
Access to all code protected parameters.
•Press SET T for 8 secs. The access code value 0 is shown on the display (unit comes with code set at 0 from factory).
• Select the correct code with the UP and DOWN arrows.
•Press SET T to enter the code. If the code is correct, the first parameter label is shown on the display (St1).
• Move to the desired parameter with the UP and DOWN.
•Press SET T to view the value on the display.
• The value can be modified with the UP and DOWN arrows.
•Press SET to enter the value.
• Repeat until all necessary parameters are modified.
•Press SET and DOWN at the same time to quit programming or wait one minute and the display will automatically exit programming mode.
*The keyboard code can be reset to ZERO by turning off the controller and turning it on again while keeping the SET T key depressed.
Set default settings
• Access parameter H0 as explained. 0 will appear.
• Press SET T or SET H for 8 seconds. Pro will appear on the display if the Set Point is correct and Epr will appear if it is not correct.
• Press SETT+DOWN or SETH+DOWN to exit or wait 1 minute.
Temperature control process
• Independent ON/OFF control
If rt8=ono and rt0=Ind, each output is associated to a particular Set. If ct2=dir, output 1 will connect when TS1 >= St1+rt1 (where TS1 is the temperature of probe 1) and will disconnect when TS1 <= St1.
Temperature
St1+rt1
St1
Output 1 ON
ct0
Time
ct0 is the minimum stop time. Once the output is disconnected, it is not connected again until ct0 minutes later. If ct2=Inv, output 1 will connect when TS1 <= St1-rt1 and will disconnect when TS1 >= St1.
Temperature
St1
St1-rt1
Output 1 ON
ct0
Time
The output 2 is handled in the same manner but controlled by St2, using rt2 as differential, ct3 as indicator of direct or reverse connection, and ct1 as minimum stop time.
• Dependent ON/OFF control
If rt8=ono and rt0=dEP, output 1 works as in Independent ON/OFF control, but output 2 works as follows: If ct3=dir, output 2 will connect when TS1 >= St1+St2+rt2 (where TS1 is the temperature of probe 1) and will disconnect when TS1 <= St1+St2.
Temperature
St1+St2+rt2
St1+St2
Output 2 ON
ct1
Time
ct1 is the minimum stop time. If ct3=Inv, output 2 will connect when TS1 <= St1+St2-rt2 and will disconnect when TS1 >= St1+St2.
Temperature
St1+St2
St1+St2-rt2
Output 2 ON
ct1
Time
• Cooling control
If rt8=rEF the temperature is regulated by output 1 as in ON/OFF control, while defrosting is triggered by output 2. Three defrosting methods are available:
1.Switch off the compressor (dt0=re)
2.Switch off the compressor and connect a heat resistor to output 2 (dt0=re)
3.Switch on the compressor and connect an electro-valve to output 2 to reverse the cycle (dt0=in)
Probe 1
Probe 1
Probe 1
Probe 1
Defrosting is performed at time periods indicated by dt3. If dt3 is zero, no defrosting is performed periodically. Defrosting is deactivated when TS2 (temperature of probe 2) reaches dt1 value or when the maximum defrosting time dt2 is reached. Defrosting can also be activated and deactivated from the keypad, pressing the UP arrow for 8 seconds, or IR remote control. Defrosting can not be activated if a continuous cold cycle is activated, unit is in auxiliary adjustment mode, TS2 >=dt1 or dt2=0. With dt4 parameter we can choose that during the defrosting and one hour after a message -d- is displayed until the temperature raises the initial defrosting temperature. It is also possible to show the initial temperature during the defrosting or to show the actual temperature all the time.
• Continuous cold cycle
A continuous cold cycle maintains the compressor (output 1) in operation for a period of time given by ct6. These cycles are activated from the keypad, keeping the DOWN arrow pressed for 8 seconds, and end when the time is finished or an order is given from the keypad (pressing DOWN for 8 seconds again). The cycle will not commence if the unit is in heat control mode or i auxiliary adjusting mode (due to memory failure) or if defrosting is activated.
• Neutral zone control
If rt8 = NEu output 1 connects when TS1 >= St1+rt3 and disconnects when TS1 <= St1, while output 2 connects when TS1 <= St1-rt3 and disconnects when TS1 >= St1.
Temperature
St1+rt3
St1
St1-rt3
Output 1 ON
Output 2 ON
Time
Probe 1
• Control with probe errors
If reading of probe 1 fails the output 1 works following 10 minutes cycles, with a percentage of connection time given by Ct4. Output 2 is carried out in the same way with parameter Ct5. If reading of probe 2 fails, the defrosting ends by time.
• Temperature alarms
If TS1 >= St1+At1, the thermostat will indicate maximum temperature alarm for probe1 (Aht) and the alarm will remain activated until temperature TS1 <= St1+At1-At0. If TS1 <= St1-At2, the thermostat will activate minimum temperature alarm for probe 1 (ALt), and it will remain activated until temperature TS1 >= St1-At2-At0. Program At3 to indicate the alarm check time between alarm event and indication of an alarm event. The alarm is indicated by a message on the display and activating the alarm output if present (alarm can be silenced pressing SETT+DOWN keys or CLEAR in the IR remote control).
Temperature
St1+At1
St1+At1-At0
High Alarm ON
Probe 1
Temperature
St1-At2
St1-At2+At0
Low Alarm ON
Probe 1
• Probe options
Set Pt1 to select if the decimal point is shown or not in the display. Set Pt2 to set temperature units (Celsius of Fahrenheit).
If the probe is not placed in the exact point to control, use a standard thermometer to determine the offset and set it by Pt0.
Set Pt3 to select if 1 or 2 temperature probes are used.
List of humidity parameters
Description Units Range
Sh1 Humidty set point 1 %RH rh4 to rh6 Sh2 Humidty set point 2 %RH rh5 to rh7 rh0 Sh1 and Sh2 dependency Range Ind / dEP rh1 Differencial for Sh1 %RH 0.1 to 30.0 rh2 Differencial for Sh2 %RH 0.1 to 30.0 rh3 Band differencial %RH 0.1 to 30.0 rh4 Minimum value for Sh1 %RH 0 to rh6 rh5 Minimum value for Sh2 %RH 0 to rh7 rh6 Maximum value for Sh1 %RH rh4 to 100 rh7 Maximum value for Sh2 %RH rh5 to 100 rh8 Operation mode Range ono/nEU Ah0 Alarm differencial %RH 0.1 to 20.0 Ah1 Maximum probe alarm %RH 0.1 to 99.9 Ah2 Minimum probe alarm %RH 0.1 to 99.9 Ah3 Alarm check time hh:mm 0.0 to 18.0 ch0 Minimum stop time output 3 Minutes 0 to 240 ch1 Minimum stop time output 4 Minutes 0 to 240 ch2 Operation output 3 Range Dir/Inv ch3 Operation output 4 Range Dir/Inv ch4 Default operation output 3 %ON 0 to 100 ch5 Default operation output 4 %ON 0 to 100 Ph0 Hum. probe adjustment %RH -20 to 20 Ph1 Decimal point Option no/yES Ph2 Humidity Probe type Range 1V/3V/420 Ph3 Value for 4mA %RH 0.0 to 100 Ph4 Value for 20mA %RH 0.0 to 100 H0 Set default settings Command H1 Keypad protection Option NO/YES H2 Communication setup Numeric 0 to 999 H3 Access code to parameters Numeric 0 to 999
Humidity parameter programming
Follow the same steps as when adjusting temperature parameters but using the SET H key.
Humidity control process
• Independent ON/OFF control
If rh8=ono and rh0=Ind, each output is associated to a particular Set. If ch2=dir, output 3 will connect when HS >= Sh1+rh1 (where HS is the humidity measured) and will disconnect when HS <= Sh1.
Humidity
Sh1+rh1
Sh1
Output 3 ON
ch0 is the minimum stop time. Once the output is disconnected, it is not connected again until ch0 minutes later. If ch2=Inv, output 3 will connect when HS <= Sh1-rh1 and will disconnect when HS >= Sh1.
Humidity
Sh1
Sh1-rh1
Output 3 ON
The output 4 is handled in the same manner but controlled by Sh2, using rh2 as differential, ch3 as indicator of direct or reverse connection, and ch1 as minimum stop time.
ch0
Time
ch0
Time