
Series BTT Temperature Transmitter
Specications - Installation and Operating Instructions
2X ø13/64
[ø5.08]
SLOT
ø3-5/16
[ø84.07]
mount
Duct
Immersion mount
The Series BTT Temperature Transmitter can be used for the following
applications: monitoring the temperature inside air ducts for HVAC, transmitting
temperature inside water lines for chillers, or measuring the outside air temperature
of any new or existing facility. Mounting congurations include duct, immersion, and
outside air. For duct and immersion models, probes can be ordered from 2.5˝ up to 18˝
in length. The OSA models can be ordered with an optional radiation shield that allows
the sensor to be mounted in direct sunlight.
MODEL CHART
Example BTT -D 04 -1 BTT-D04-1
Series BTT Temperature transmitter
Mounting
Conguration
Probe Length* 25
Output 1
Options Blank
*For BTT-I models, actual probe length is approximately 0.75˝ longer than listed
probe length to ensure maximum immersion into thermowells.
D
I
O
R
04
06
08
12
18
2
Duct mount
Immersion mount
Outside air
Outside air with radiation shield
2.5˝ (required for “O” and “R” models)
4˝
6˝
8˝
12˝
18˝
4-20 mA
0-10 V
None
FC
Factory calibration certicate
NIST
NIST calibration certicate
Outside air with
radiation shield
[130.00]
Outside air without
radiation shield
Bulletin T-BTT
4-19/64
[109.29]
4-3/64
[102.94]
BALL CHAIN
CONNECTOR
Ø3-5/16
[84.14]
BALL CHAIN
CONNECTOR
5-1/8
3-45/64
94.00
6-47/64
170.90
SPECIFICATIONS
Temperature Sensor: Pt1000 RTD.
Range: -40 to 140°F (-40 to 60°C) or
32 to 212°F (0 to 100°C) depending on
model.
Temperature Limits: Ambient: -40 to
140°F (-40 to 60°C); Process: -40 to
140°F (-40 to 60°C) or 32 to 212°F (0 to
100°C) depending on model.
Accuracy: ±0.5°C @ 25°C.
Thermal Effect: ±0.01%/°C.
Response Time: 100 msec.
Wetted Materials: All models: 304
SS (probe), polycarbonate (housing);
Duct and immersion models: Neoprene
(gasket); Outside air models: Nylon
(insert), silicone (O-ring).
Process Connection: 1/2˝ NPS
(immersion models only).
INSTALLATION
WARNING
in accordance with the job wiring diagram and in accordance with national and local
electrical codes. Use copper conductors only.
Use electrostatic discharge precautions (e.g., use of wrist straps) during installation
and wiring to prevent equipment damage.
Avoid locations where severe shock or vibration, excessive moisture or corrosive
fumes are present. NEMA Type 4X (IP66) housings are intended for outdoor use
primarily to provide a degree of protection against wind-blown dust, rain, and hosedirected water.
2-51/64
[71.09]
2-13/16
[71.44]
1/8 [Ø3.18]
GASKET
2-15/64
Disconnect power supply before installation to prevent electrical
shock and equipment damage. Make sure all connections are
[56.60]
27/32
[21.50]
2X ø13/64
[ø5.00]
3-7/64
[79.00]
PROBE
LENGTH
1/8 [3.30]
GASKET
4-21/64
[109.93]
Ø47/64
[18.65]
1/2 NPS
7-3/32
[180.18]
4-17/32
[115.00]
115
79
90
Electrical Connection: Removable
terminal block.
Conduit Connection: PG11 and PG16
knockout.
Probe Lengths: 2.5 to 18˝ (depending
on conguration).
Power Requirements: 13-36 VDC for
current models, 13-36 VDC or 16-28
VAC for voltage models.
Output Signal: 4-20 mA or 0-10 VDC
(depending on model).
Enclosure Rating: NEMA 4X (IP66)
(immersions models require thermowell).
Weight: 5.11 oz (145 g) (duct/
immersion); 8.4 oz (238 g) (OSA without
radiation shield); 1 lb 7.4 oz (663.4 g)
(OSA with radiation shield).
Agency Approvals: CE.
ø5-7/64
[ø129.59]
50
2-15/64
[56.63]
3-55/64
[98.06]
8-51/64
[223.58]
Do not exceed ratings of this device, permanent damage not covered by warranty may
result. The 4-20 mA models are not designed for AC voltage operation.
The Series BTT Temperature Transmitters offer multiple conduit openings. When
removing the appropriate knock out, take care not to damage any circuit components.
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com

Duct Mount
The transmitter should be mounted in a location that receives adequate air ow for
proper operation. The transmitter should be mounted such that the conduit connection
points down to prevent moisture from entering.
1. Drill a 0.26˝ diameter hole into the duct at the desired location.
2. Insert the transmitter probe through the hole such that the mounting ange is ush
to the duct.
3. Use two #8 x 1/2˝ pan head sheet metal screws to attach the mounting ange to the
duct. Do not over tighten.
4. Twist off the top cover to access wiring terminals.
5. Proceed with wiring according to Figure 1 or Figure 2.
6. Replace top screw cover.
Immersion Mount
The transmitter should be mounted to a thermowell since the process connection is
not sealed against water ingress. It should also be mounted such that the conduit
connection points down to prevent moisture from entering.
1. Before mounting the transmitter, mount the thermowell to the pipe.
2. Slide the temperature sensor into the thermowell.
3. Hand tighten the plastic threaded connection of the sensor into the thermowell.
4. Twist off the top cover to access the wiring terminals.
5. Proceed with wiring according to Figure 1 or Figure 2.
6. Replace top screw cover.
OSA (Outside Air)
The transmitter should be mounted under an eave, shield, or in an area that is out of
the elements or direct sunlight. The transmitter should be mounted with the sensor
pointing down to prevent water collection in the sensor cavity.
1. Remove the cover plugs from the face of the unit and the top cover.
2. Position the transmitter where it is to be mounted and mark the mounting holes in
each corner of the housing.
3. Drill or punch out marked locations.
4. Place the transmitter box over mounting holes on wall and align. Install wall mount
screws (not provided) in mounting holes.
5. Proceed with wiring according to Figure 1 or Figure 2.
6. Replace cover and cover plugs on the face of the unit.
Wiring
The Series BTT Temperature Transmitter can be ordered for current or voltage outputs.
For current output models, the supply power must be between 13-36 VDC and the unit
should be wired as shown in Figure 1.
Figure 1
For voltage output models, the power requirement must be between 13-36 VDC or
16-28 VAC. The unit should be wired as shown in Figure 2.
OSA (Outside Air with Radiation Shield)
1. Position the transmitter where it is to be mounted and mark the mounting holes.
2. Drill or punch out marked locations.
3. Place the transmitter box over mounting holes on wall and align. Install wall mount
screws (not provided) in mounting holes.
4. Remove the cover plugs from the face of the unit and the top cover.
5. Proceed with wiring according to Figure 1 or Figure 2.
6. Replace cover and cover plugs on the face of the unit.
Figure 2
MAINTENANCE/REPAIR
Upon nal installation of the Series BTT Temperature Transmitter no routine
maintenance is required. The Series BTT Temperature Transmitter is not eld
serviceable and should be returned if repair is needed. Field repair should not be
attempted and may void warranty.
This symbol indicates waste electrical products should not be disposed
of with household waste. Please recycle where facilities exist. Check with
your Local Authority or retailer for recycling advice.
WARRANTY/RETURN
Refer to “Terms and Conditions of Sales” in our catalog and on our website. Contact
customer service to receive a Return Goods Authorization number before shipping the
product back for repair. Be sure to include a brief description of the problem plus any
additional application notes.
©Copyright 2020 Dwyer Instruments, Inc. Printed in U.S.A. 6/20 FR# 444138-00 Rev. 9
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com