Series
19/64
[7.54]
3
[76.20]
2-3/8
[60.32]
1-3/4
[44.45]
SLD
Single Channel Leak Detection Relay
Shaft Seal Leak Protection
Series SLD Single Channel Leak Detection Relay is used to monitor the shaft seal
of a submersible pump to detect a leak before pump failure. A leak is detected by sensing
the status of a float or conductivity switch installed in the seal cavity. When this resistance
drops below the set sensitivity, the output relay energizes and the LED indicator
illuminates. The SLD offers normally open and normally closed relay contacts to energize
an alarm and de-energize the pump in the event of a leak. When the seal failure condition
clears, the relay automatically resets.
Model
SLD-ACX
SLD-ACY
SLD-ACZ
Sensitivity
470 Ω fixed
470 to 10 K Ω adjustable
4.7 k to 100 K Ω adjustable
SPECIFICATIONS
Power Requirement: 120 VAC, 50/60 Hz.
Power Consumption: 2 VA (approximate).
Isolation Voltage: 2500 V.
Temperature Limits:
Operating: -4 to 131°F (-20 to 55°C);
Storage: -40 to 185°F (-40 to 85°C).
Switch Type: DPDT.
Switch Voltage: 9 VDC.
Electrical Rating: 10 A @ 250 VAC resistive, 360 VA inductive.
Response Time:
Energize: 15 ms (approximate);
Release: 8 ms (approximate).
Indicators: Red LED illuminates when leak is detected.
Enclosure: Polycarbonate dust cover.
Mounting: 11-pin socket.
Weight: 8 oz (227 g).
Agency Approval: cUR, UR.