Dwyer Instruments SERIES SCD-8 Catalog Page

Series
2-1/2 [63.50]
4-21/64 [109.86]
3-35/64
[89.92]
Multi-Loop DIN Rail Mount Temperature Controller
Up to 8 Control Loops, Optional Display
Shown with optional display and additional inputs and outputs.
The Series SCD-8 Multi-Loop DIN Rail Mount Temperature Controller can be used
to control up to 8 independent PID control circuits. The base unit comes standard with 4 thermocouple or 3 RTD input channels. Additional input cards can be purchased if needed, but the additional inputs must be of the same type as the inputs that came with the base unit. If more than 8 loops are required or to mix input types, SCD-2000 slave modules can be added without wiring additional power or communications cables. Each loop can be programmed either through the standard RS-485 serial communications or an optional plug in LED display module. Each control loop will have two outputs and a single input. The outputs can be configured for dual loop control or for a control loop and an alarm. One of the two outputs for each control loop must be a relay or pulsed voltage output.
Base Units
Input/Output Modules
TEMPERATURE
For Factory Configured Models, Relay Outputs are standard on Output Sub1 (and Sub2 if 8 inputs selected).
Example Construction
Input Selection
Controllers
Output 1 Card Selection
Temperature/Process
Output 2 Card Selection
Options
Model SCD-8000 SCD-8100
Model SCD-4T SCD-3R SCD-42 SCD-43 SCD-45 SCD-46
Input Type
Thermocouple RTD
Input/Output Type
4 Thermocouple Inputs 3 RTD Inputs 4 Pulse Voltage Outputs 4 Relay Outputs 4 Current Outputs 4 Linear Voltage Outputs
X
SCDM-8 SCDM-8
X
0 1 2 3
0 2 3 5 6
SPECIFICATIONS Input: Thermocouple: RTD (depending on model, see chart). Display: Optional, single row 7 segment LED display, 4 bit PV = Red, SV = Green. Supply Voltage: 24 VDC, isolated switching power supply. Power Consumption: 10W + (3W x # of SCD-2000 modules). Operating Temperature: 32 to 122°F (0 to 50°C). Memory Backup: Non-volatile memory. Control Output Ratings:
Relay output: SPST, 3A @ 250 VAC resistive; Voltage pulse: Output: 24 VDC max, 40 mA; Current output: 4 to 20 mA (resistive load < 500 Ω) (output 1 or 2 only); Linear voltage: 0 to 10 VDC (resistive load > 1000 Ω) (output 1 or 2 only).
Communications: RS-485 Modbus Weight: 10 oz (425 g). Agency Approvals: CE, cUL, UL.
ACCESSORIES SCD-PS, 100 to 240 VAC/VDC to 24 VDC Power Supply SCD-LED, Optional LED Display Module MN-1, Mini-Node™ USB/RS-485 converter A-600, R/C snubber SCD-SW, Configuration Software
See Series SCD on page 269 for slave modules.
X
X
SCDM-8XXX-X Multi-Loop DIN Rail Mount Temperature Controller 4 Thermocouple Inputs 3 RTD Inputs 8 Thermocouple Inputs 6 RTD Inputs None Pulsed Voltage Relay Current
0 2 3 5 6
Linear Voltage None Pulsed Voltage Relay Current Linear Voltage
LED
LED Display
PV
Pulsed Voltage on Alarm Output Sub 1 & Sub 2
Input Sensor Types
Temperature measurement resistance (Cu50) Platinum resistance (Pt100) Platinum resistance (JPt100)
Thermocouple TXK type Thermocouple U type Thermocouple L type Thermocouple B type Thermocouple S type Thermocouple R type Thermocouple N type Thermocouple E type Thermocouple T type Thermocouple J type Thermocouple K type
Note: The default setting in SCD-8000 is “thermocouple K type”. The default setting in SCD­8100 is “Pt100”.
Modbus® is a registered trademark of Schneider Automation, Inc.
®
A-5-11/RTU communication protocol.
SCD-8100/SCD-3R
SCD-8000/SCD-4T
Range
-50 to 150°C
-200 to 600°C
-20 to 400°C
-200 to 800°C
-200 to 500°C
-200 to 850°C 100 to 1800°C 0 to 1700°C 0 to 1700°C
-200 to 1300°C 0 to 600°C
-200 to 400°C
-100 to 1200°C
-200 to 1300°C
268
DWYER INSTRUMENTS, INC.