Dwyer Instruments SERIES APM, SERIES MPM, SERIES PPM Catalog Page

SERIES APM, MPM & PPM
1-49/64
4
[61.2]
DUAL LINE CONFIGURABLE PANEL METERS
1/8 DIN Process and Flow / Rate Totalizers
[45.0]
3-5/8 [92.0]
PROCESS CONTROL
These 1/8 DIN digital panel meters accept signals from various transmitters and
owmeters and displays them on a six-digit, dual line display in engineering units. These meters will also provide power to the eld device and include a NEMA 4X
front panel. Free, USB based programmnig sofware is resident on the meter. Options
include up to four relays and a 4-20 mA output.
The Series MPM Dual Line Congurable Panel Meter is a general purpose process
meter that is eld selectable for a 4-20 mA or 0-10 V input signal. It provides 24 VDC
to power the transmitter. The dual line display can display the process variable on the upper line and engineering units on the lower line. Or, in dual scale mode, the process variable can be displayed in one units (like height) on the upper display and another (like volume) on the lower display. The meter also has an automatic Round Horizontal
Tank function a well as 32 point linearization.
The Series APM Dual Line Congurable Panel Meter and Series PPM Dual Line Congurable Panel Meter are ow / rate totalizers for analog or pulse inputs. The
most useful feature of these products is their dual line display which allows rate
and total to be displayed at the same time. A non-resetable grand total can also be
programmed. Total can be reset either from the front panel or by connecting a remote
switch to the F4 terminal at the rear of the meter.
The Series APM accepts either a 4-20 mA or 0-10 V input signal and provides the 24 VDC to power the owmeter. Other features of the APM include square root extraction for DP ow, and programmable exponents for open channel ow.
The Series PPM accepts a pulse input signal and provides either 5, 10 or 24 VDC to power the owmeter. Adding the 4-20 mA output option converts the pulse into a signal
that can be run long distances to a PLC or other device.
Indicators
Panel Meters/
FEATURES/BENEFITS
• NEMA 4X / IP65 front panel
• Powers the transmitter / owmeter
• Dual line 6 digit display
• Free USB based programming software
• Display rate and total at the same time
• Two or four relays and isolated 4-20 mA output options
APPLICATIONS
• Level monitoring
• Pump control
• Flow rate indication
• Flow totalization
• Open channel ow monitoring
• Process control
5-3/64 [128.0]
4-49/64
[121.0]
2-13/32
SPECIFICATIONS
Input: APM and MPM: 0-20 mA, 4-20 mA, 0-5 V, or ±10 V inputs; PPM: Field selectable: Pulse or square wave 0-5 V, 0-12 V, or 0-24 V @ 30 kHz; TTL; open collector 4.7 k Ω pull-up to 5 V @ 30 kHz; NPN or PNP transistor, switch contract 4.7 k Ω pull-up to 5 V @ 40 Hz. Input impedance: 50 to 100 Ω. Accuracy: ±0.03% of calibrated span ±1 count. Display: Red LED, Dual-line 6-digit display, 0.60 in and 0.46 in.
Transmitter / Flowmeter Power: 85-
265 VAC models: 200 mA @ 24 VDC; 12-24 VDC models: 100 mA @ 24 VDC; Second supply with 4-20 mA output models: 40 mA @ 24 VDC. Power Requirements: 85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max or 12-24 VDC ±10%, 15 W max.
FREE USB PROGRAMMING SOFTWARE AND CABLE
The PM Series meters come preloaded with free programming software that connects and installs directly to your PC with a standard USB cable, also provided free with each instrument. This eliminates the need to insert CDs, install drivers, or download
datalog a PM Series meter using your PC. Just simply connect the meter to your PC with the USB cable and within seconds you will be programming it.
UNIQUE LEVEL MONITORING CAPABILITIES
The MPM meter is particularly well suited for level monitoring, controlling and alarming applications. For instance, the meter can be programmed to display any two of these
parameters on its dual line display: height, volume or percent full. Its six digit display allows it to display volumes up to 999,999 gallons, liters, or any other volume. The meter also has a Round Horizontal Tank function which requires the user to enter only
the height and length of a round horizontal tank and the meter will display in volume. Up to four relays are available for alarm and control applications, and the relays can even be programmed to alternate for pump control applications.
25/64 [10.0]
4-13/32 [112.0]
Temperature Limits: Operating: -40 to 149°F (-40 to 65°C); Storage: -40 to 185°F (-40 to 85°C).
Front Panel: NEMA 4X, IP65 front. Output Signal (option): Isolated 4-20
mA. Switch Rating (option): 2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A) external; rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP @ 125/250 VAC for inductive loads. Time Delay: 0 to 999.9 s, on and off relay time delays; programmable and
independent for each relay.
Shipping Weight: 9.5 oz (269 g). Agency Approvals: CE, UL. Programming Software: Free, USB
based. Resident on meter, nothing to download.
4-11/6
[106.0]
MODEL CHART Model Model Model Power Output 1 Output 2
APM-100 APM-101 APM-120 APM-121 APM-140 APM-141 APM-200 APM-201 APM-220 APM-221 APM-240 APM-241
MPM-100 MPM-101 MPM-120 MPM-121 MPM-140 MPM-141 MPM-200 MPM-201 MPM-220 MPM-221 MPM-240 MPM-241
PPM-100 PPM-101 PPM-120 PPM-121 PPM-140 PPM-141 PPM-200 PPM-201 PPM-220 PPM-221 PPM-240 PPM-241
85-265 VAC 85-265 VAC 85-265 VAC 85-265 VAC 85-265 VAC 85-265 VAC 12-24 VDC 12-24 VDC 12-24 VDC 12-24 VDC 12-24 VDC 12-24 VDC
DWYER INSTRUMENTS, INC. 352
None None
2 relays 2 relays 4 relays 4 relays
None None
2 relays 2 relays 4 relays 4 relays
None
4-20 mA
None
4-20 mA
None
4-20 mA
None
4-20 mA
None
4-20 mA
None
4-20 mA
ACCESSORIES Model Description
PMA-01 PMA-03 PMA-04 PMA-05 PMA-06 PMA-07 PMA-08 PMA-09 PMA-10 PMA-11 PMA-12
RS-232 serial adapter RS-422/485 serial adapter RS-232 to RS-422/485 isolated converter RS-232 to RS-422/485 non-isolated converter USB to RS-232 non-isolated converter USB to RS-422/485 isolated converter USB to RS-422/485 non-isolated converter
Snubber DIN rail mounting kit for two modules
4 relay expansion module 4 digital inputs and 4 digital outputs module
Loading...