Specications - Installation and Operating Instructions
[91.3]
TABLE OF CONTENTS
Dimensions
Specications ..............................1
Getting Started ..............................2
Model Identication ..........................2
Installation .................................2
Wiring ...................................3-5
Front Panel Functions ......................6-7
Home Display ...............................7
Security Level Selection ......................7
Lead/Lag Operation ..........................7
Analog Retransmission Operation .............7
Serial Communication Operation ...............8
Menu Selections ............................8
Secondary Menu ............................8
Secure Menu ............................9-12
Alarm Type and Action ...................10-11
Diagnostic Error Messages ..................12
Programming Chart .........................13
Programming Example ......................14
................................1
17/32 [13.5]
3-25/32
[95.9]
SPECIFICATIONS
Inputs: 0 (or 4)-20 mA DC or 0 (or 2.0)-10.0 VDC
selectable.
Input Impedance: Current input: 10 Ω, Voltage input:
5K Ω.
Output Ratings: Control relays: SPDT, rated 10A @
240 VAC res., 1/4 hp @120 VAC, 1/3 hp @ 240 VAC;
Alarm relays: SPST, 3A @ 240 VAC res., 1/10 hp @
120 VAC; Other: 15 VDC @ 20 mA for output one and
output two.
Control Type: On/off, reverse or direct acting.
Power Requirements: 100-240 VAC nominal, +10%-
15%, 50 to 400 Hz, single phase; 132 to 240 VDC
nominal, +10%-15%.
Power Consumption: 7.5 VA max.
Accuracy: ±0.25% of span, ±1 least signicant digit.
Display: Two 4-digit, 7 segment 0.56˝ high LED’s.
Display Resolution: 1 count.
Memory Backup: Nonvolatile memory (no batteries
required).
Serial Communications: Optional RS-232 or RS-485
with Modbus
Ambient Operating Temperature / RH: 14 to
131°F (-10 to 55°C) / 0 to 90% up to 104°F (40°C)
non-condensing, 10 to 50% at 131°F (55°C) noncondensing.
Weight: 16 oz (454 g).
Front Panel Rating: Meets UL type 4X (IP66).
Loop Power Supply (Isolated): 24 VDC @ 50 mA,
regulated.
Alarm On-Off Differential: 1 count.
Set Point Range: Selectable.
Power Voltage Stability: 0.05% over the power
voltage range.
Temperature Stability: 100 PPM/°C typical, 200
PPM/°C max.
Common Mode Rejection: 140 db minimum at 60
Hz.
Normal Mode Rejection: 65 db typical, 60 db at 60
Hz.
Isolation: Relay: 1500 VAC to all other inputs and
outputs; 24 VDC loop power: 500 VAC to other inputs
and outputs; Process output: 500 VAC to other inputs
and outputs.
Storage Temperature: -40 to 176°F (-40 to 80°C).
Agency Approvals: UL 508.
®
protocol.
3-25/32 [95.9]
DWYER INSTRUMENTS, INC.
1
GETTING STARTED
1. Install the control as described on page 2.
2. Wire the control following the instructions on pages
3 through 5. Page 3 contains basic wiring for the
control. If using the Series MPCJR’s transmitter power
supply follow the additional directions on page
4. Wiring instructions for the 232 and 485 series
communication options is included on page 5.
3. Familiarize yourself with the front key pad functions
and read the menu structure prior to starting the
programming process. A programming chart with the
menu structure and spaces to write your programming
values is included on page 13. This chart can be a
helpful tool to save time in programming. For further
assistance programming examples are included on
page 14.
MODEL IDENTIFICATION
Model MPCJR -
Options
OPTIONS
232
RS-232 Modus
Allows remote computer to read and write all
control parameters.
485
RS-485 Modbus®-RTU Serial Communications.
Allows remote computer to read and write all
control parameters.
RV
Analog retransmission of input, 0-10 VDC.
RC
Analog retransmission of input, 0 (or 4)-20 mA.
Input Ranges
Process Input Types
The 0-20 mA DC, 4-20 mA DC, 0-10 VDC, and 2-10
VDC inputs are fully scalable from a minimum of 100
count span placed anywhere within the range of -1999
to +9999. Decimal point position is adjustable from the
zero place (9999), tenths (999.9), hundredths (99.99), or
thousandths (9.999).
INSTALLATION
Mount the instrument in a location that will not be subject
to excessive temperature, shock, or vibration (see
Specications for specic tolerances). All models are
designed for mounting in an enclosed panel.
Select the position desired for the instrument on the
panel. Prepare the panel by cutting and deburring the
required opening.
From the front of the panel, slide the housing through
the cut out. The housing gasket should be against the
housing ange before installing.
From the rear of the panel slide the mounting collar over
the housing. Hold the housing with one hand and using
the other hand, push the collar evenly against the panel
until the springs are compressed. The ratchets will hold
the mounting collar and housing in place.
®
-RTU Serial Communications.
Panel cut-out:
3.620 x 3.620 in,
+0.032/-0.000
(92 x 92 mm,
+0.8/-0.0)
Figure 1: Panel cut out dimensions
CAUTION
chassis is removed from the housing, you must follow
industry standard practice for control and protection
against Electro-Static Discharge (ESD). Failure to
exercise good ESD practices may cause damage to the
instrument.
It is not necessary to remove the
instrument chassis from the housing
for installation. If the instrument
2
WIRING
CURRENT
TED
-
Do not run transmitter wiring or other Class 2 wiring in
the same conduit as power leads. Use only the probe or
transmitter for which the control has been programmed.
Maintain separation between wiring of sensor, auxiliary
in or out, and other wiring. See the “Secure Menu” for
input selection.
Supply connections should be made in accordance with
the National Electrical Code per Article 300, and local
regulations. All line voltage output circuits must have a
common disconnect and be connected to the same pole
of the disconnect.
Input wiring for probe or transmitter is rated CLASS 2.
Control wiring is as shown in Figure 2 below.
OPTION RV, RC
+
VOLTAGE
ALARM 1
CONTACTS
ALARMS 2
CONTACTS
1
2
3
4
5
6
7
8
9
10
22 23
21
N.O.
COM.
N.O.
COM.
24 25
CURRENT
26
RELAY
AND SSR
N.C.
COM.
N.O.
N.C.
COM.
N.O.
323130292827
11
12
13
14
15
16
17
18
19
20
24 VDC
@ 50 MA
ISOLA
PUMP 1
OUTPUT
PUMP 2
OUTPUT
PUMP1
COM.
NOTE:
1. FOR SUPPLY CONNECTIONS
2. MAXIMUM AMBIENT TEMPERATURE
3. USE COPPER CONDUCTORS ONLY
4. TERMINALS 1-5, 10-12, AND 21-32
15 VDC
USE NO. 16 AWG OR LARGER
WIRES RATED FOR AT LEAST 75C,
OR IN ACCORDANCE WITH AN
EQUIVALENT NATIONAL STANDARD.
RATING 131F [55C]
ARE CLASS 2 'SELV'.
PUMP2
Figure 2: Wiring
LINE INPUT
100 TO 240 VAC
50 - 400 HZ. SINGLE PH
132 TO 240 VDC 5VA
MAX. OUTPUT RATINGS:
RELAY: 10A. @ 240 VAC RES.
1/4 HP @ 120 VAC
1/3 HP @ 240 VAC
ALARM: 3A. @ 240 VAC RES.
P.D. 240VA, 120/240 VAC
SW. VOLT.: 15 VDC @ 20 MA
290-3126
3
WIRING FOR TRANSMITTER INPUTS USING
USE OF A FUSE
[1/8A
IS RECOMMENDED
THE CONTROL
OR MOT
9/16 THICK
CHARACTERISTICS [TYPICAL]
INTEGRAL POWER SUPPLY
Wire power and outputs as shown on previous page.
Wiring for two-wire transmitters shown below in Figure 3.
All wiring shown in Figure 3 is Class 2.
FAST-BLOW] IN THE LOOP
For three or four wire transmitters follow the wiring
instructions provided with your transmitter.
WARNING
will result.
USE OF SNUBBERS WITH INDUCTIVE LOADS
COIL OF RELAY
OR STARTER
TO PROTECT
INPUT CIRCUITRY.
CONNECT TRANSMITTER
MINUS [-] TO TERMINAL 5
LEVEL
TRANSMITTER
Figure 3: Transmitter wiring
DO NOT wire the 24 V Power Supply
across the input of the control.
Damage to the control input circuitry
SNUBBER
SWITCHED AC
[FROM CONTROLLER]
CONNECT JUMPER BETWEEN TERMINALS 3 AND 12
CONNECT TRANSMITTER PLUS [+] TO TERMINAL 11
1-1/4
22 23
1
21
2
3
4
5
6
7
8
9
10
2827
29
7/8
SNUBBER PHYSICAL
242526
30
11
12
13
14
15
16
17
18
19
3231
20
3/8
4
A snubber is a resistance/capacitance device that is used
to reduce or eliminate high voltage spikes generated
from inductive loads. For best effect, the snubber should
be mounted as close to the coil as physically possible.
Electrical and typical physical characteristics are shown
above.
CAUTION
contact wear.
Failure to use a snubber on an
inductive load may cause erratic
operation and/or premature relay
4
WIRING FOR 485 AND 232 SERIAL COMMUNICATION
DB-25 WIRING [VIEWED FROM WIRE SIDE]
]
OPTIONS
Wire power and outputs as shown on page 3. Wiring
for options is shown in Figure 4 below. All wiring shown
below is Class 2. Shielded twisted pair is recommended
for Option 485.
WARNING
to the control circuitry will result.
DO NOT run signal wiring in the
same conduit or chase as the power
wiring. Erratic operation or damage
*For half-duplex operation wire only A and B. Do not connect to Y and Z.
Figure 4: Wiring for options
5
FRONT PANEL FUNCTIONS
PUMP
ON LAMP
ALARM LAMPS
PUMP
ON LAMP
LEVEL
DISPLA
1
2
Y
1ST SET
POINT
DISPLAY
Key functions are as follows:
INDEX: Pressing the INDEX key advances
the display to the next menu item. May also be used
in conjunction with other keys as noted below.
UP ARROW: Increments a value, changes a
menu item, or selects the item to ON. The maximum
value obtainable is 9999 regardless of decimal
point placement.
UP ARROW AND ENTER: Pressing these keys
simultaneously brings up the secondary menu
starting at the SP1H menu item. Pressing these keys
for 5 seconds will bring up the secure menu.
DOWN ARROW: Decrements a value, changes a
menu item, or selects the item to OFF. The
minimum value obtainable is -1999 regardless of
decimal point placement.
ENTER: The ENTER key is used to store
the value of menu items once they are changed to
a new value. If the ENTER key is not pressed
after changing the value the item will revert to the
previously stored value.
6
INDEX and DOWN ARROW: Pressing these
keys simultaneously will allow backing up one menu
item, or if at the rst menu item they will cause the display
to return to the primary menu. If an alarm condition has
occurred, these keys may be used to reset the alarm.
INDEX and ENTER: Pressing these keys
simultaneously and holding them for 5 seconds allows
recovery from the various error messages. The following
Correct the problems associated with the above
conditions before using these reset keys. More than one
error could be present. Caution is advised since several
items are reset at one time.
The Home Display
The home display is the normal display while the control
is operating. If no errors or functions are active, the
HOME display will indicate the Process Variable (the
level that is being measured) on the top display and the
SP1H value, Pump 1 On Set Point, on the bottom display.
Error messages may over-ride the HOME display. See
ERROR MESSAGES on page 12.
While in the Secondary Menu, if no key is pressed for
a period of 30 seconds, the display will return to the
HOME position displaying the process value. While in
the Secure Menu, if no key is pressed for a period of
60 seconds, the display will return to the HOME position
displaying the process value. Outputs are disabled
(turned off) when the Secure Menu is active.
Security Level Selection
Three levels of security are provided. The SECr menu
item security level may be viewed or changed at any time
regardless of the present security level in the Secure
menu. The display shows the current security level. To
change security levels change the password value using
the UP ARROW or DOWN ARROW keys and
pressing the ENTER key. Refer to the password
table (following) for the correct value to enter for the
security level desired.
To set the access level to, for example, 2, at the SECr
menu item press the UP ARROW key until the upper
display shows the password, 1101. Press the ENTER
key. The display will blink, and return with the level value,
2, in the upper display.
The password values shown in the table cannot
be altered. Retain a copy of these pages for future
reference. This is the only reference made to password
values in this instruction book.
PASSWORD TABLE
Menu
Secondary
Secure
Secondary
Secure
Secondary
Secure
Security
Level
Status
Locked
Locked
Unlocked
Locked
Unlocked
Unlocked
Displayed
Value
When Viewed
2
3
4
Password
Value To
Enter
1101
1011
111
LEAD/LAG OPERATION
The Mercoid
to easily operate a pair of pumps in the most efcient
manner possible. The controller has a ‘lead/lag’ feature
that allows two pumps to operate in an alternating
fashion to minimize wear.
The Mercoid® MPCJR pump controller has a pair of
set points each for pump 1 and pump 2. If the lead/lag
feature is turned off, SP1H and SP1L control pump 1 and SP2H
and SP2L control pump 2. If the lead/lag feature is turned
on, pumps 1 and 2 will be controlled in the alternating
fashion described below. In all cases the P1 lamp will
indicate activity of pump 1 and the P2 lamp will indicate
activity of pump 2. The lead/lag operation is set in the
Secure menu with the item LdLg.
Lead/Lag On
After installation, set the SP1H to the high level (pump on
point) for standard operation. Set SP1Lto the low level
(pump off point). Set the SP2H to the level where you want
BOTH pumps to turn on (emergency pump on). Set the
SP2L to the level where you want the second pump to turn
off (emergency pump off).
The controller will not allow you to set SP1H below SP1L,
SP1L above SP1H, SP2H below SP2L, or SP2L above SP2H. The
controller will not allow you to set any set point or alarm
point above or below the programmed scale. No error
messages are generated. The displayed value will stop
at an allowable point just above (or below, as the case
may be) the maximum or minimum allowed.
In normal operation, when the SP1H point is reached, one
of the pumps will turn on. When lead/lag is turned on,
pumps 1 and 2 will alternate. If the level reaches the SP2H
point, both pumps will be turned on until the SP2L point is
reached, where one of the pumps will turn off. When SP1L
is reached, remaining running pump will turn off. The last
pump off will not be the next pump on.
Lead/Lag Off
If lead/lag is turned off, SP1H and SP1L control pump 1 and
SP2H and SP2L control pump 2. There is no alternating
function.
OPERATION RV, RC ISOLATED ANALOG
RETRANSMISSION
The analog retransmission option allows the Process
Variable or the Set Variable to be sent as an analog
signal to an external device. The signal may be either
0-10 VDC (option RV) or 0 (or 4)-20 mA DC (option RC).
The output may be changed in the eld from one to the
other by the toggle switch located on the top printed
circuit board.
®
MPCJR pump controller is designed
Wire the output as shown on page 3.
To set up the analog retransmission, rst determine the
scale range that the analog signal will represent. The
maximum scale is 9999 counts. In the Secondary Menu
set POL for the the scale value that will be represented by
the low end of the analog signal (0 V or 0 mA). Set POH for
the scale value that will be represented by the high end
of the analog signal (10 V or 20 mA).
If you require a suppressed scale or output, you may use
the following equations to determine the proper settings
for POL and POH.
desired analog signal) *K) + Highest desired
analog reading.
POL = Lowest desired scale reading - ((Minimum desired
analog output) *K).
Operation is automatic. There are no further programming
steps required.
7
OPTION 232, 485 SERIAL COMMUNICATION
OPERATION
The serial communications options allow the control to
be written to and read from a remote computer or other
similar digital device. Communication is allowed either
through a RS-485 (Option 485) port, or a RS-232 (Option
232) port.
Wire the communication lines as shown on Page 7.
Wiring for the RS-485 is run from control to control in
a daisy chain fashion with a termination resistor (120
Ω) across the transmit and receive terminals of the last
control in the chain. Set the RS-485 DIP switch for half
or full duplex as appropriate for your application. The DIP
switch is located on the communications board plugged
into the center of the bottom board of the control.
Select the control address and communication baud
rate with the Addr and bAUd menu items in the Secure
Menu. THE BAUD RATE AND ADDRESS MENU ITEMS
WILL TAKE EFFECT ON THE NEXT POWER UP OF
THE CONTROL. BE SURE TO POWER CYCLE THE
CONTROL BEFORE USING THE NEW BAUD RATE
AND ADDRESS.
In operation, you have the option of preventing a write
command from the host computer. To prevent the host
from writing to the control change the LOrE menu item
in the Secondary Menu to LOC. To allow the host to write
commands to the control set LOrE to rE. (The host does
have the ability to change the LOrE state, but it is not
automatic.)
If your system depends on constant reading or writing
to and from the host, you may wish to set the No Activity
Timer (nAt) to monitor the addressing of the control.
When the LOrE is set to rE and the nAt is set to any value
other than OFF, the control will expect to be addressed
on a regular basis. If the control is not addressed in the
time set by the value of nAt, then the control will display
the error message CHEC LOrE. To clear the message set
LOrE to LOC.
MENU SELECTIONS
Notation Conventions for the Menus
Because of the number of features available in this
control, information is included that may not apply to your
specic control. All usable features are included in this
book, but may not be used in your process. To increase
clarity the following conventions are used:
1. Certain features or functions shown in this book are
contextual. This means that Menu Items may or may
not appear, depending on other Menu Item
selections. Whenever this occurs, a notation is made
in the Menu Item that “controls” or “directs” other
menu items. If you are looking for a particular menu
item and can’t nd it, check the menu item that is its
“control” for proper setting.
2. The “#” symbol is used in two ways. It is used inside
a group of characters to indicate which set point
function (SP1 or SP2) is being affected. It is also used
before a group of characters of a menu item to
indicate that there may be more than one selection or
value for that menu item.
Secondary Menu
Press the UP ARROW and Enter keys to start
the menu. Press INDEX to advance to the next menu
item. Press UP ARROW or DOWN ARROW to
change the value in the display. Press ENTER to
retain the value.
SP1H Pump 1 On Set Point. Factory Default 23.1 (feet).
SP1L Pump 1 Off Set Point. Factory Default -5.7 (feet).
SP2H Pump 2 On Set Point. Factory Default 23.1 (feet).
SP2L Pump 2 Off Set Point. Factory Default -5.7 (feet).
A1Hi Alarm 1 High: Factory Default 23.1 (feet).
A2Lo Alarm 2 Low: Factory Default 2.0 (feet).
8
Secure Menu
Press the
Seconds to start the menu. Press INDEX to advance
to the next menu item. Press UP ARROW or
DOWN ARROW to change the value in the display.
Press ENTER to retain the value. OUTPUTS ARE
DISABLED (TURNED OFF) WHILE CONTROL IS IN
THE SECURE MENU.
SECr Security Code: See the Security Level Selection
InP Input Type: Select one of the following. Refer to the
Curr DC Current Input 0.0-20.0 or 4.0-20.0 mA.UOLt DC Voltage Input 0.0-10.0 or 2.0-10.0 V.
InPC Input Correction: Select ±500 counts. This feature
sensor error.
Note: InPC is reset to zero when the input type is
LdLg Lead / Lag: Select On or OFF. Factory default is On.
On The Lead/Lag function is enabled. The
OFF The Lead/Lag function is disabled.
OSUP Zero Suppression: Select On or OFF. Factory default
is OFF.OFF The input range will start at 0 (zero) Input.On The input range will start at 4.00 mA or 2.00
dPT Decimal Point Positioning: Select 0, 0.0, 0.00, or
0.000. All Menu items related to the input will be
PEA The Peak feature stores the highest input the control
UAL The Valley feature stores the lowest input the
UP ARROW and Enter keys for 5
and the Password Table on page 7, in order to
enter the correct password. Factory Default is 4.
Input wiring section for the proper wiring. Factory
Default is Curr.
- - - - Reserved
allows the input value to be changed to agree
with an external reference or to compensate for
changed, or when decimal position is changed.
(See page 7).
outputs of SP1 and SP2 will alternate.
V.
affected. Factory default is 0.0.
has measured since the last reset or Power On. At
Power On PEA is reset to the present input. To
manually reset the value PEA must be in the lower
display. Press the ENTER key to reset. PEA will
be reset and display the present input value
Controller has measured since the last reset or
Power On. At Power On UAL is reset to the present
input. To manually reset the value UAL must be in
the lower display. Press the ENTER key. UAL will
be reset and display the present input value.
SCAL Scale Low: Select 100 to 9999 counts below SCAH.
The total span between SCAL and SCAH must be
within 11998 counts. Maximum setting range is
-1999 to +9999 counts. Factory Default is -5.7.
SCAH Scale High: Select 100 to 9999 counts above SCAL.
The total span between SCAL and SCAH must be
within 11998 counts. Maximum setting range is
-1999 to +9999 counts. Factory Default is 23.1.
SPL Set Point Low: Select from the lowest input range
value to SPH value. This will set the minimum SP1L
or SP2L value that can be entered. The value for SP1L or SP2L will stop moving when this value is
reached. Factory Default is -5.7.
SPH Set Point High: Select from the highest input range
value to SPL value. This will set the maximum SP1H
or SP2H value that can be entered. The value for SP1H or SP2H will stop moving when this value is
reached. Factory Default is 23.1.
S1St Set Point 1 State: Select P in or POut. Factory
default is POut.
P in Pump In (Direct Action). As the input
increases the output will increase.
POut Pump Out (Reverse Action). As the input
increases the output will decrease.
5ILP P1 Lamp: Select 0 on or OoFF. Factory default is 0 on.
0 on Lamp ON when Output is ON.OoFF Lamp OFF when Output is ON.
S2St Set Point 2 State: Select P In, POut or OFF. Factory
default is POut.P in Pump In (Direct Action). As the input
increases the output will increase.
POut Pump Out (Reverse Action). As the input
increases the output will decrease.
52LP P2 Lamp: Select 0 on or OoFF. Factory default is 0 on.
0 on Lamp ON when Output is ON.
OoFF Lamp OFF when Output is ON.
9
ALARM TYPE AND ACTION
HIGH
D
D
CAUTION
safety, a redundant limit controller is required.
When setting an alarm value for an absolute alarm (A1t =
AbS or A2t = AbS), simply set the value at which the alarm
is to occur.
When setting the alarm value for a deviation alarm (A1t
= dE or A2t = dE), set the difference in value from the Set
Point (SP1H) desired.
Since the input for the MPCJR is driven from a transmitter,
the input display can be programmed in different ways.
Regardless of the position of the decimal point, a change
of one in the right most digit is referred to as a count.
For example, if there were no decimal point selected, a
change from 235 to 236 is a change of one count. If the
decimal point were selected at 0.0, a change of 23.5 to
23.6 is a change of one count.
The following diagram (below) shows the action and
reset functions for both absolute and deviation alarms.
HIGH ALARMS
LOW ALARMS
AND LOW
ALARM
In any critical application where
failure could cause expensive
product loss or endanger personal
A#HI
D
A#LO
D
HIGH AND LOW
A#LO
A#HI
HIGH ALARMS
LOW ALARMS
ALARM
D
A#LO
A#HI
SP
D
SP
A#HI
Absolute alarmsDeviation
When setting up an alarm for deviation the deviation is
set in counts. For example if a low alarm is required to
be 5 counts below the SP1H, then set A#Lo to -5. If a high
alarm is required 20 counts above the SP1H, then set A#Hi
to +20. If SP1H is changed, the alarm will continue to hold
the same relationship as originally set.
When Alarm Power Interrupt, A#Pi, is programmed ON
and Alarm Reset, A#rE, is programmed for Hold, the
alarm will automatically reset upon a power failure and
subsequent restoration if no alarm condition is present.
If Alarm Inhibit, A#iH, is selected ON, an alarm condition
is suspended upon power up until the process value
passes through the alarm set point once. Alarm inhibit
can be restored as if a power up took place by pressing
both the INDEX and ENTER keys for 5 seconds.
10
WARNING
HIGH ALARM, RESTORATION OF POWER WILL NOT
CAUSE THE ALARM TO OCCUR IF THE PROCESS
VALUE DOES NOT FIRST DROP BELOW THE HIGH
ALARM SETTING. DO NOT USE THE ALARM INHIBIT
FEATURE IF A HAZARD IS CREATED BY THIS
ACTION. BE SURE TO TEST ALL COMBINATIONS OF
HIGH AND LOW ALARM INHIBIT ACTIONS BEFORE
PLACING CONTROL INTO OPERATION.
The following menu items apply only to the alarms.
AL 1 Alarm 1 function: Select OFF, Lo, HI, or HILo, Factory
default is Hi.
OFF Alarm 1 is disabled. No Alarm 1 menu items
appear in the Secondary or Secure menus.
Lo Low Alarm Only. A1Lo appears in the
Secondary Menu.
HI High Alarm Only. A1Hi appears in the
Secondary Menu.
HiLo High and Low Alarms. Both A1Lo and A1Hi
If AL1 is set to OFF, go to AL2.
ALt Alarm 1 Type: Select AbS or dE. Factory default is
AbS.AbS Absolute Alarm that may be set anywhere
independent of SP1H.
dE Deviation Alarm that may be set as an offset
A1rE Alarm 1 Reset: Select OnOF or Hold. Factory default is
OnOF.OnOF Automatic Reset.Hold Manual Reset. Reset (acknowledge) by
A1Pi Alarm 1 Power Interrupt: Select On or OFF. Factory
default is OFF.
On Alarm Power Interrupt is On.OFF Alarm Power Interrupt is OFF.
A1iH Alarm 1 Inhibit: Select On or OFF. Factory default is
OFF.
On Alarm Inhibit is On. Alarm action is suspended
until the process value rst enters a non-
alarm condition.
OFF Alarm Inhibit is OFF.
A1St Alarm 1 Output State: Select CLOS or OPEn. Factory
default is CLOS.CLOS Closes Contacts at Alarm Set Point.OPEn Opens Contacts at Alarm Set Point.
A1LP Alarm 1 Lamp: Select O on or OoFF. Factory default
is O on.O on Alarm Lamp is ON when alarm contact is
closed.
OoFF Alarm Lamp is OFF when alarm contact is
AL2 Alarm 2 function: Select OFF, Lo, Hi, or HiLo.
Factory default is Lo.OFF Alarm 2 is disabled. No Alarm 2 menu items
appear in the Secondary or Secure menus.
Lo Low Alarm Only. A2Lo appears in the
Secondary Menu.
Hi High Alarm Only. A2Hi appears in the
Secondary Menu.
HiLo High and Low Alarms. Both A2Lo and A2Hi
IF INHIBIT IS ON AND A POWER
FAILURE OCCURS DURING A
appear in the Secondary Menu, and share
the same Alarm 1 Relay output.
within the values of SCAL and SCAH and is
from SP1H. As SP1H is changed the Alarm Point
will track with SP1H.
simultaneously pressing the INDEX and
DOWN ARROW keys for 5 seconds.
closed.
appear in the Secondary Menu, and share
the same Alarm 2 Relay output.
If AL2 is set to OFF the remaining A2, alarm 2, menu items
do not appear.
A2t Alarm 2 Type: Select AbS or dE. Factory default is
AbS.AbS Absolute Alarm that may be set anywhere
within the values of SCAL and SCAH and is
independent of SP1H.
dE Deviation Alarm that may be set as an offset
from SP1H. As SP1H is changed the Alarm Point
will track with SP1H.
A2rE Alarm 2 Reset: Select OnOF or Hold. Factory default is
OnOF.OnOF Automatic Reset.Hold Manual Reset. Reset (acknowledge) by
simultaneously pressing the INDEX and
DOWN ARROW keys for 5 seconds.
A2Pi Alarm 2 Power Interrupt: Select On or OFF. Factory
default is OFF.
On Alarm Power Interrupt is ON.OFF Alarm Power Interrupt is OFF.
A2 iH Alarm 2 Inhibit: Select On or OFF. Factory default is
OFF.On Alarm Inhibit is On. Alarm action is suspended
until the process value rst enters a non-
alarm condition.
OFF Alarm Inhibit is OFF.
A2St Alarm 2 Output State: Select CLOS or OPEn.
Factory default is CLOS.CLOS Closes Contacts at Alarm Set Point.OPEn Opens Contacts at Alarm Set Point.
A2LP Alarm 2 Lamp: Select O on or OoFF. Factory default
is O on.O on Alarm Lamp is ON when alarm contact is
closed.
OoFF Alarm Lamp is OFF when alarm contact is
closed.
FiLt Digital Filter: Select OFF or 1 to 99. In some cases
the time constant of the sensor, or noise could
cause the display to jump enough to be unreadable.
If this value is set too high, controllability will suffer.
Factory default is 3.
The remaining menu items appear if the corresponding
option was purchased with the control.
POL (Analog Retransmission Output, see page 8)
Process Output Low: Select -1999 counts to any
value less than POH. Factory default is -5.7.
POH (Analog Retransmission Output, see page 8)
Process Output High: Select from any value greater
than POL to 9999 counts. Factory default is 23. 1 .
LOrE (Option 232 and 485, Serial Communications)
Local / Remote Status: Select LOC or rE. Factory
default is rE.
LOC The host computer is advised not to send
11
remote commands. Any write commands
sent to the controls will be rejected.
rE The host computer is allowed to send write
commands. If the control is not addressed
within the time set in the nAt (No Activity
Timer, see Secure Menu) the CHEC LorE
error message will be displayed.
(Option 232 or 485, Serial Communications) Control
Addr
Address: Set from 1 to FF. This number (hexadecimal,
base 16) must match the address number used by
the host computer. Factory default is 32.
bAUd (Option 232 or 485, Serial Communications)
Communication Baud Rate: Select 300, 1200,
2400, 4800, 9600, or 19200. This number must
match the baud rate used by the host computer.
Factory default is 9600.
nAt (Option 232 or 485, Serial Communications) No
Activity Timer: Set from OFF or 1 to 99 minutes.
Factory default is OFF.
Display is blank. Instrument is
not getting power, or the supply
voltage is too low.
Fail test appears upon power
up if the internal diagnostics
detect a failure. This message
may occur during operation if
a failure is detected. Displays
ash.
This message appears if the
Serial Communications has
timed out.
Underow or Overow: Process
value has exceeded input range
ends.
Check calibration appears as
an alternating message if the
instrument calibration nears
tolerance edges.
Check calibration appears
as a ashing message if the
instrument calibration exceeds
specication.
This message appears if the
ambient temperature of the
control approaches the ends of
tolerance.
This message appears if the
ambient temperature of the
control is out of range or RJC
sensor is broken.
Set point
outputs inactive
Alarms inactive
Set point
outputs inactive
Alarms inactive
Set point
outputs active
Alarms inactive
Set point
outputs active
Alarms active
Set point
outputs active
Alarms active
Set point
outputs
inactive
Alarms active
Set point
outputs active
Alarm active
Set point
outputs active
Alarms active
Check that the power supply is on, or that the
external fuses are good.
The display alternates between FA1L tESt and
one of the following messages: FACt dFLt:
Memory may be corrupted. Press the ENTER
key and the DOWN ARROW key to start the
factory default procedure. Recheck controller
programming. rEt FACt: Unrecoverable error,
return to factory for service.
Restore the communications line and switch
the LorE to L0C.
Input signals may normally go above or below
range ends. If not, check input and correct.
Remove the instrument for service and / or
recalibration. To reset use the INDEX and
ENTER keys.
Remove the instrument for service and / or
recalibration. To reset use the INDEX and
ENTER keys.
Correct the ambient temperature conditions.
Ventilate the area of the cabinet or check for
clogged lters. If RJC broken, return to factory
for service.
Correct the ambient temperature conditions.
Ventilate the area of the cabinet or check for
clogged lters. If RJC broken, return to factory
for service.
12
PROGRAMMING CHART
Use the charts on this and the next page to record the values in your application. You may want to photocopy the pages
if you plan to make programming changes.
MenuItemDefault Set At Description
Primary
Secondary
Secure
PV SP1H
SPIH
SPIL
SP2H
SP2L
A1Hi
A2Lo
SECr
InP
InPC
LdL9
05UP
dPt
PEA
UAL
SCAL
SCAH
SPL
SPH
SISt
SiLP
525t
52LP
ALI
ALt
A IrE
A IP i
A I iH
A I ST
A I LP
AL2
A2t
A2rE
A2Pi
A2iH
A2St
A2LP
F ILt
POL
POH
LOrE
Addr
bAUd
nAt
Stor
23.1
-5.7
23.1
-5.7
23.1
2.0
4
Curr
0.0
On
OFF
0.0
XX
XX
-5.7
23.1
-5.7
23.1
POut
POut
Hi
AbS
OnOF
OFF
OFF
CLOS
O on
LO
Abs
OnOF
OFF
OFF
CLOS
Oon
3
-5.7
23.1
rE
32
9600
OFF
YES
Home Position, Process Variable and SP1H’s Value displayed
Set Point 1 value (default is in feet)
Set Point 1 off value (default is in feet)
Set Point 2 value (default is in feet)
Set Point 2 off value (default is in feet)
Alarm 1 (high) value (default is in feet)
Alarm 2 (low) value (default is in feet)
Security Selection
Input (selectable current or voltage)
Input Correction
Lead/Lag (selectable on or off)
Zero Suppression (selectable on or off)
Decimal Point Positioning
Peak, highest input value seen since last reset
Valley, lowest input value seen
Scale Low value (default is in feet)
Scale High value (default is in feet)
Set Point Low value (default is in feet) since last reset
Set Point High value (default is in feet)
Set Point 1 State (selectable POut (Pumping Out) or PIn (Pumping In))
Set Point 1 Lamp Condition when contact is closed (selectable on or off)
Set Point 2 State (selectable POut (Pumping Out), PIn (Pumping In), or off)
Set Point 2 Lamp Condition when contact is closed (selectable on or off)
Alarm 1 Function (selectable off, lo, hi, or hilo)
Alarm Type 1 (selectable abs (absolute) or de (deviation))
Alarm 1 Reset (selectable onof (auto) or hold (manual))
Alarm 1 Power Interrupt (selectable on or off)
Alarm 1 Inhibit (selectable on or off)
Alarm 1 Output State (selectable close or open)
Alarm 1 Lamp condition when contact is closed (selectable on or off)
Alarm 2 function ( selectable off, lo, hi, or hilo)
Alarm 2 Type (selectable abs (absolute) or de (deviation))
Alarm 2 Reset (selectable onof (auto) or hold (manual))
Alarm 2 Power Interrupt (selectable on or off)
Alarm 2 Inhibit (selectable on or off)
Alarm 2 Output State (selectable close or open)
Alarm 2 Lamp condition when contact is closed (selectable on or off)
Digital Filter
Process Output Low (default is in feet)
Process Output High (default is in feet)
Local/Remote for computer communications
Control Address for computer communications
Baud Rate for computer communications
No Activity Timer for computer communications
Store Menu for Hi speed writes (selectable yes or no)
52LP
AL I
A Lt
A I rE
AIPi
AI iH
AIST
AILP
AL2
A2t
A2rE
A2Pi
A2iH
A2St
A2ULP
FILt
POL
POH
23.1
0.0
23.1
0.0
23.1
2.0
4
Cur r
0.0
On
OFF
0.0
XX
XX
-5.7
23. 1
-5.7
23. 1
POut
POut
Hi
AbS
OnOF
OFF
OFF
CLOS
O on
LO
Abs
OnOF
OFF
OFF
CLOS
Oon
3
-5.7
23. 1
Set Point 1 value (default is in feet)
6.0
Set Point 1 off value (default is in feet)
3.0
Set Point 2 value (default is in feet)
12.0
Set Point 2 off value (default is in feet)
9.0
Alarm 1 (high) value (default is in feet)
20.0
Alarm 2 (low) value (default is in feet)
1.0
Security Selection
4
Input (selectable current or voltage)
Cur r
Input Correction
0.0
Lead/Lag (selectable on or off)
On
Zero Suppression (selectable on or off)
On
Decimal Point Positioning
0.0
Peak, highest input value seen since last reset
Valley, lowest input value seen
Scale Low value (default is in feet)
0.0
Scale High value (default is in feet)
25.0
Set Point Low value (default is in feet) since last reset
Set Point High value (default is in feet)
Set Point 1 State (selectable POut (Pumping Out) or PIn (Pumping In))
Set Point 1 Lamp Condition when contact is closed (selectable on or off)
Set Point 2 State (selectable POut (Pumping Out), PIn (Pumping In), or
POut
off)
Set Point 2 Lamp Condition when contact is closed (selectable on or off)
Alarm 1 Function (selectable off, lo, hi, or hilo)
Hi
Alarm Type 1 (selectable abs (absolute) or de (deviation))
AbS
Alarm 1 Reset (selectable onof (auto) or hold (manual))
OnOF
Alarm 1 Power Interrupt (selectable on or off)
OFF
Alarm 1 Inhibit (selectable on or off)
OFF
Alarm 1 Output State (selectable close or open)
CLOS
Alarm 1 Lamp condition when contact is closed (selectable on or off)
O on
Alarm 2 function ( selectable off, lo, hi, or hilo)
LO
Alarm 2 Type (selectable abs (absolute) or de (deviation))
Abs
Alarm 2 Reset (selectable onof (auto) or hold (manual))
OnOF
Alarm 2 Power Interrupt (selectable on or off)
OFF
Alarm 2 Inhibit (selectable on or off)
OFF
Alarm 2 Output State (selectable close or open)
CLOS
Alarm 2 Lamp condition when contact is closed (selectable on or off)
Oon
Digital Filter
3
Process Output Low (default is in feet)
0.0
Process Output High (default is in feet)
25.0
HIGH LEVEL ALAR
START 2
STOP 2
START 1
STOP 1
LOW LEVEL ALARM
Example:
• Keep Empty, two pump (duplex)
• Depth 25 feet
• Pump 1: Start at 6 feet
• Low level alarm: 1 foot, xed,
• High level alarm: 20 feet, xed,
• Want Lead/Lag function on
• Automatic reset of pump over .
temperature and seal failure