SERIES IEF
INSERTION ELECTROMAGNETIC FLOW TRANSMITTER
FLOW
Field Congurable, High Accuracy, BACnet or Modbus® Protocol
5-53/64
[148.0]
®
YEAR LIMITED
WARRANTY
Shown with
A-IEF-VLV-BR**
accessory valve kit
E
O
D
I
V
O
N
L
I
N
The Series IEF Insertion Electromagnetic Flow Transmitter is an adjustable
insertion owmeter featuring electromagnetic technology that accurately and reliably
measures uid velocity in addition to providing several continuous signal outputs.
This series is specically designed to offer superior performance paired with simple
installation and use. One unit is adjustable to t pipe sizes from 4 to 36˝ (102 to
914 mm), and offers several output options including selectable BACnet MS/TP or
Modbus® RTU communications protocol over 2-wire RS-485 in addition to the standard
analog, frequency and alarm outputs.
FEATURES/BENEFITS
• Field congurable setup displays (-LCD integral option or remote accessory
A-IEF-DSP) allow for ultimate exibility by accommodating a variety of application
congurations with one model through multiple display congurations i.e. pipe
size, pipe material, liquid type, analog output, pulse/frequency output, alarm outputs,
communication outputs, damping, and calibration factor.
• High performance accuracy is maintained through changes in temperature, density
or viscosity.
• Setup Wizard and installation tool are simple to use allowing for quick and precise
installation.
• Accessory setup kit A-IEF-KIT ensures exact installation application depth with
included thickness gage and measuring tape.
• Long Life Cycle and minimal maintenance requirements with no moving parts to
wear or break and electrodes that discourage fouling.
• Isolation valve accessory options allow for installation in operational systems via
hot-tap kit or easy removal without system downtime.
• NIST traceable pass/fail verication certicate included standard for Carbon Steel
Schedule 40 pipes sized 4˝ (102 mm), 6˝ (150 mm), 8˝ (200 mm), and 10˝ (250 mm)
with high accuracy option; 10˝ (250 mm) with standard option.
APPLICATIONS
• Boiler feed water
Adjustable Insertion
• Chilled water
• Open and closed loop condenser water
• Irrigation system
Flow Transmitters, Electromagnetic,
• Municipal water distribution
• Process and coolant ow
• Ground water remediation
• Chemical processing
• Pump protection
• Wastewater
• Mining
MODEL CHART
Example IEF -H N -CND -LCD IEF-HN-CND-LCD
Series IEF Insertion electromagnetic ow transmitter
Accuracy L
Process
Connection
Housing
Electrical
Connection
G
S
F
I
E
T
H
N
B
CND
PG
10
Options LCD
Note: For CC option, must provide completed conguration paperwork.
Note: For maximum performance select -LCD option or setup display accessory.
DWYER INSTRUMENTS, INC. 292
Standard accuracy <10˝ (250 mm) pipe; 1% FS
Standard accuracy >10˝ (250 mm) pipe; 1% FS
Standard accuracy 4 to 36˝ (100 to 900 mm) pipe; 1% FS
High accuracy 4˝ (100 mm) pipe; 1% of reading
High accuracy 6˝ (150 mm) pipe; 1% of reading
High accuracy 8˝ (200 mm) pipe; 1% of reading
High accuracy 10˝ (250 mm) pipe; 1% of reading
High accuracy 4 to 10˝ (100 to 250 mm) pipe; 1% of reading
1˝ male NPT
1˝ male BSPT
1/2˝ female NPT conduit connection without cable
PG gland without cable
PG gland with 10´ (3 m) cable
Integral LCD display
COM
BACnet or Modbus
NIST
Six point NIST traceable calibration certicate
FC
Factory calibration certicate for 0.5% of reading at single point
CC
Custom congured for specic installation
NW
NSF certied
®
communication protocol (display selectable)
-LCD option shown
A-IEF-KIT
SPECIFICATIONS
Service: Compatible clean or dirty non
coating, conductive liquids.
Range: 0 to 20 ft/s (0 to 6 m/s).*
Wetted Materials: Body shaft/tting: 316
SS; Electrodes: 316 SS; Electrode cap:
Polymer/Polystyrene; O-ring: Silicon.
Accuracy: High accuracy units: ±0.5%
of reading at calibrated velocity; ±1% of
reading from 2 to 20 ft/s (0.6 to 6 m/s);
±0.02 ft/s (±0.006 m/s) at < 2 ft/s (0.6
m/s); Standard accuracy units: ±1% FS.
Temperature Limits: Ambient: -20 to
160°F (-29 to 71°C); Process: 15 to
250°F (-9 to 121°C); Storage: -40 to
185°F (-40 to 85°C).
Process Connection: 1˝ NPT or BSPT
with accessory full port ball valve options.
Pressure Limits: 400 psi (27.6 bar) @
100º F (37.8°C).
Pressure Drop: < 0.1 psi at 12 ft/s in 4˝
(101.6 mm) and larger pipe.
Outputs:
(1) Analog: 4-20 mA, 0-5 V, 0-10 V or
2-10 V (display selectable);
(1) Pulse/Frequency: 0-15 V peak pulse,
0 to 500 Hz or scalable pulse output
(display selectable);
(2) Alarm: (1) Empty pipe detection or
minimum/maximum velocity, (display
selectable); (1) Reverse ow output
indication.
Power Requirements: 12-42.4 VDC, .25
A @ 24 VDC; 12-36 VAC.
*For max owrates >10 ft/s (3 m/s) order option -CC.
†
Brass ttings and pipe are not to be used with NSF Certied models.
5-53/64 [148.0]
4-51/64
[121.8]
†
®
61/64
[24.2]
22-1/64
[559.2]
Electrical Connection: Removable
terminal blocks, model selectable 1/2˝
female NPT conduit connection, PG 16
gland or PG 16 gland with (2) 10 ft (3
m) 9 conductor 22 AWG plenum rated
cables, accessory cable lengths up to
200 ft (61 m) optional.
Display (-LCD option): 2˝ ( 5.08 cm) x
2˝ (5.08 cm) graphic LCD with backlight.
Conductivity: >20 microsiemens.
Enclosure Material: Powder coated die
cast aluminum.
Enclosure Ratings: NEMA 6P (IP68)
(Non display models); NEMA 4X (IP66)
(-LCD option).
Agency Approvals: BTL, CE, NSF/ANSI
61 and 372.
COMMUNICATIONS (-COM OPTION)
Type: BACnet MS/TP or Modbus
RTU communication protocol (default
disabled, display selectable).
Supported Baud Rates: 9600, 19200,
38400, 57600, 76800, or 115200 bps
(display selectable).
Device Load: 1/8 unit load.
ADDITIONAL SPECIFICATIONS
Applicable Pipe Material: Most popular
plastic and metal pipes; i.e. Carbon steel,
SS, copper, UPVC/PVDF, galvanized
steel, mild steel, and brass.
Applicable Pipe Size: 4-36˝ (101 to 914
mm), model dependent. See model chart.
Diameter Length Requirements: >10
upstream; >5 downstream.
Glycol: 0 to 100% display selectable.
ACCESSORIES
Model Description
A-IEF-KIT
A-IEF-DSP
A-IEF-CBL-50
A-IEF-VLV-BR
A-IEF-VLV-SS
A-IEF-PA
**Brass ttings and pipe are not to be used with NSF Certied
models. Brass valves are non-RoHS compliant.
Setup kit (includes setup display, thickness
gage and measuring tape), and universal
power adapter
Setup display
Plenum rated cable 50 ft (15.2 m)
1-1/4˝ full port isolation valve brass kit**
1-1/4˝ full port isolation valve 316 SS kit
AC wall adapter
Modbus® is a registered trademark of Schneider Automation, Inc.
A-IEF Remote Display now available: See page 295