Dwyer Instruments SERIES I2-4 Catalog Page

2-1/4
[57.15]
4-1/16
[103.21]
2X Ø0.743˝ [18.87 MM] 3/8˝ NPT CONDUIT KNOCKOUTS
3/8˝ NPT
L [L = 7.000˝ FOR 6˝ THERMOWELL L = 5.000˝ FOR 4˝ THERMOWELL]
3X Ø0.896˝ [22.76 MM] 1/2˝ NPT CONDUIT KNOCKOUTS
Series
3-31/32
[101.00]
2-7/32
[56.16]
4X ø0.896˝ [22.76 MM] 1/2˝ NPT CONDUIT KNOCKOUTS
3-3/32 [78.74]
1/4
[6.35]
L L = 7.000˝ FOR 6˝ THERMOWELL
L= 5.000˝ FOR 4˝ THERMOWELL
FOR 1/2˝ NPT THERMOWELL CONNECTION
I2-4
Weather-Proof Immersion Temperature Sensor
TEMPERATURE
The Series I2-4 Weather-Proof Immersion Temperature Sensor is ideal for
monitoring hot and chilled water lines feeding Air Handlers and Cooling Towers. The plastic housing has a 1/4 tur n twist off cover to reduce installation time. The multiple knockouts allow for easy conduit access to any side of the housing. The Series I2-4 can be ordered with a choice of 11 output options that allow it to communicate to any standard building control system.
Note: A Series IW2 Thermowell must be used on pressurized air and water lines to prevent leakage around the probe.
Temperature Sensors
Model I2-41062 I2-42062 I2-43062 I2-44062 I2-45062 I2-46062 I2-47062 I2-48062 I2-49062 I2-4A062 I2-4B062
Thermowells
Model IW2-262 IW2-242
Sensor Type
Pt 100 Ω RTD PT 1000 Ω RTD Ni 1000 Ω RTD Balco 1000 Ω RTD 10K Ω Type II Thermistor 3K Ω Thermistor 5K Ω Thermistor 100K Ω Thermistor 20K Ω Thermistor 2252 Ω Thermistor 10K Ω Type III Thermistor
Material
304 SS 304 SS
DWYER INSTRUMENTS, INC.
Insertion Length
6˝ 4˝
Insertion Length
6˝ 6˝ 6˝ 6˝ 6˝ 6˝ 6˝ 6˝ 6˝ 6˝ 6˝
Twist Off Cover, Multiple Conduit Holes
Sensor Type
Pt 100 Ω RTD PT 1000 Ω RTD Ni 1000 Ω RTD Balco 1000 Ω RTD 10K Ω Type II Thermistor 3K Ω Thermistor 5K Ω Thermistor 100K Ω Thermistor 20K Ω Thermistor 2252 Ω Thermistor 10K Ω Type III Thermistor
Model I2-41042 I2-42042 I2-43042 I2-44042 I2-45042 I2-46042 I2-47042 I2-48042 I2-49042 I2-4A042 I2-4B042
Platinum RTD: ±0.6% @ 32°F (0°C); Nickel RTD: ±0.5°F @ 32°F (0°C); Balco RTD: ±0.1% @ 32°F (0°C); Thermistors: ±0.36°F from 32 to 158°F (0 to 70°C).
Insertion Length
4˝ 4˝ 4˝ 4˝ 4˝ 4˝ 4˝ 4˝ 4˝ 4˝ 4˝
Operating Temperature: -32 to 240°F (-35.5 to 115.5°C).
Probe Diameter: 1/4˝ (6.3 mm). Cable Length: 8˝. Probe Material: 304 SS. Mounting: 1/2˝ threaded connection to
fit Series IW2 thermowell.
Loading...