SERIES EWDP
WIRELESS COMMUNICATING ADJUSTABLE DIFFERENTIAL PRESSURE SWITCH
EnOcean® Wireless Technology
PRESSURE
[99.21]
The SERIES EWDP Wireless Communication Adjustable Differential Pressure Switch
uses EnOcean
pressures. The dual scaled adjustment knob in inches of water column and pascals
allows changes to the pressure set point to be made without a pressure gage. The
battery-powered switch is equipped with radio module for frequencies of 902 MHz
or 868 MHz which sends a signal wirelessly to a Series USB-300 receiver at each
change of status. The silicone diaphragm makes this series ideal for use with air and
other non-combustible gases. The EWDP is available with settings from 0.08 in w.c.
(20 Pa) up to 20 in w.c. (5000 Pa). The compact size, adjustment knob, and wireless
capabilities make the EWDP the perfect choice for HVAC applications in temporary
installations or retrots of existing buildings.
FEATURES/BENEFITS
• Wireless ability allows for easy installation in buildings with concrete or marble walls
• No wires need to be connected, allowing for remote monitoring reduces downtime
• Dual scaled set point adjustment knob to quickly and easily set the value to activate
the switch
®
wireless technology to monitor pressure, vacuum, and differential
[85.73]
4x 11/64
[Ø4.37]
CABLE
GLAND
SPECIFICATIONS
Service: Air and non-combustible, compatible gases.
Wetted Materials: Diaphragm material: Silicone; Housing material: POM; Switch
Body: PA 6.6; Cover: Polystyrene.
Temperature Limits: Process and Ambient: 14 to 158°F (-10 to 70°C); Storage: -40
to 185°F (-40 to 85°C).
Pressure Limits: 40 in w.c. (10 kPa).
Process Connections: 5/16˝ (7.94 mm) outside diameter tubing, 1/4˝ (6.0 mm)
inside diameter tubing.
Power Requirements: (1) 3 V CR2032 lithium metal battery, installed nonfunctional, user replaceable (included).
Enclosure Rating: NEMA 3 (IP54).
Mounting Orientation: Vertically, with pressure connections pointing downwards.
Weight: 5.3 oz (150 g).
Agency Approvals: CE.
2-17/64
[57.55]
51/64
[20.24]
-
(P2)+(P1)
7/8
[22.23]
2-5/16
[58.74]
19/64
[7.54]
4
[101.60]
2-9/16
[65.09]
1-31/32
[50.01]
Ø15/64
Differential Pressure Switches
APPLICATIONS
• Monitoring air lters and ventilators
• Monitoring industrial cooling air circuits and ventilation ducts
• Overheating protection for fan heaters
• Controlling air and re protection dampers
MODEL CHART
Model Frequency
EWDP-08-2-L-N
EWDP-04-2-L-N
EWDP-03-2-L-N
EWDP-05-2-L-N
EWDP-06-2-L-N
EWDP-07-2-L-N
EWDP-08-2-L-N
EWDP-04-2-L-E
EWDP-03-2-L-E
EWDP-05-2-L-E
EWDP-06-2-L-E
EWDP-07-2-L-E
Note: For models that include an installer kit, add –C to the end of the model number. Installer kit
includes two static pressure tips and 7 ft of PVC tubing.
ACCESSORIES
Model Description
A-288
A-289
A-480
A-481
A-489
USB-300U
USB-300
902 MHz
902 MHz
902 MHz
902 MHz
902 MHz
902 MHz
868 MHz
868 MHz
868 MHz
868 MHz
868 MHz
868 MHz
“L” type metal mounting bracket with screws
“S” type metal mounting bracket with screws
Plastic static pressure tip
Installer kit. Includes 2 plastic static pressure tips and 7´ (2.1 m) of PVC tubing
4˝ straight static pressure tip with ange
USB wireless receiver, 902 MHz
USB wireless receiver, 868 MHz
Set Point Range
in w.c. (Pa)
0.08 to 1.20 (20 to 300)
0.12 to 1.60 (30 to 400)
0.20 to 2.00 (50 to 500)
0.80 to 4.00 (200 to 1000)
2.00 to 10.00 (500 to 2500)
4.00 to 20.00 (1000 to 5000)
0.08 to 1.20 (20 to 300)
0.12 to 1.60 (30 to 400)
0.20 to 2.00 (50 to 500)
0.80 to 4.00 (200 to 1000)
2.00 to 10.00 (500 to 2500)
4.00 to 20.00 (1000 to 5000)
Approx. Deadband
@ Min Set Point
in w.c. (Pa)
0.04 (10)
0.06 (15)
0.08 (20)
0.4 (100)
0.6 (150)
1.0 (250)
0.04 (10)
0.06 (15)
0.08 (20)
0.4 (100)
0.6 (150)
1.0 (250)
Approx. Deadband
@ Max Set Point
in w.c. (Pa)
0.05 (12)
0.09 (22)
0.09 (23)
0.5 (130)
0.8 (200)
1.4 (350)
0.05 (12)
0.09 (22)
0.09 (23)
0.5 (130)
0.8 (200)
1.4 (350)
EnOcean® is a registered trademark of EnOcean GmbH.