Dwyer Instruments SERIES EPTA Catalog Page

[85.33]
23/64 [9.13]
4-5/16 [109.54]
4-15/32
SERIES EPTA | PROXIMITY® BY DWYER
ELECTRO-PNEUMATIC TRANSDUCERS
Low Cost, Selectable Input/Output, Manual Override
[21.43]
[12.7]
23/32
3-27/64
[86.92]
3/16
[4.76]
EPTA-B EPTA-S
The Series EPTA Electro-Pneumatic Transducers convert an analog input signal to a linearly proportionate pneumatic output by modulating its control valves to regulate branch line pressure to the set point determined by the input signal. All models
incorporate two low voltage valves, an integral in-barb lter, a 0 to 30 psi analog gage, an anodized aluminum manifold, and brass barbed ttings. The EPTA offers adjustable
span and offset as well as manual override. This unit has no air consumption and is
immune to mounting orientation. Output pressure ranges include eld-selectable 0 to 10, 0 to 15, and 0 to 20 psig. Also included is an analog 0-5 VDC feedback signal indicating the resultant branch line pressure. Universal 24 VAC/24 VDC supply voltage and eld-selectable 4-20 mA, 0-5 VDC, 0-10 VDC, or 0-15 VDC inputs ensure single
unit compatibility with most systems. The standard models maintain branch pressure
on power loss while the Fail-Safe models will drop the branch pressure to 0 psi on power loss. Mounting congurations include a metal bracket mount in the EPTA-B models and a snap-track mount in the EPTA-S models. The A-400 accessory kit will allow the EPTA-S models to be mounted on a standard DIN rail.
FEATURES/BENEFITS
• Adjustable span and offset
• Manual override
• Field selectable output ranges
• Not position sensitive
MODEL CHART Model Description EPTA-S0
EPTA-B0 EPTA-S1 EPTA-B1
Standard snap-track mount transducer Standard metal bracket mount transducer Snap-track mount transducer with fail-safe Metal bracket mount transducer with fail-safe
APPLICATIONS
• Pneumatic dampers and valve actuators
23/32
[18.26]
Shown with snap-track mounting Shown with metal bracket mounting
3-1/4
[82.55]
1-23/64
[34.53]
3 [76.20]
SPECIFICATIONS Service: Clean dry air or any inert gas.
Input Signal: DC current (4-20 mA) or
DC voltage (0-5/0-10/0-15). Input Impedance: Current: 250 Ω; Voltage: Innite. Output Signal: Jumper selectable 0 to 10 psig (0 to 69 kPa), 0 to 15 psig (0 to 103 kPa), or 0 to 20 psig (0 to 138 kPa).
Feedback Output: 0-5 VDC. Air Supply: 25 psig (172 kPa) max. Air Flow: 750 scim. Air Consumption: 0 scim normal
operation, fail-safe model vents to 0 psi
on power loss.
Accuracy: ±1.0% FS @ room temperature; ±2.0% FS @ 32 to 120°F (0 to 48.8°C).
ACCESSORIES Model Description A-400
A-403
USA: California Proposition 65 WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
3-1/4 [82.55]
DIN mounting kit Replacement integral barb lter
3-23/64
Supply Voltage: 24 VDC (+10%/-5%) or 24 VAC (±10%) 50/60 Hz. Supply Current: 180 mA max, 200 mA max on fail-safe model. Temperature Limits: Operating: 32 to 120°F (0 to 48.8°C); Storage: -20 to 150°F (-6.7 to 65.6°C). Operating Humidity Range: 5 to 95%,
non-condensing.
Pressure Connections: 1/4˝ OD (polyethylene tubing optimum). Electrical Connections: Plug-in block terminal type with 5 mm pin spacing. Wire Size: Up to one 14 AWG per
terminal.
Weight: EPTA-S0: 6.9 oz. (196 g); EPTA-S1: 9.2 oz. (261 g); EPTA-B: 14.5 oz. (411 g).
3-25/64 [86.12]
4X ø13/64
[ø5.16]
4-1/16
[103.19]
VALVES
[113.5]
Current to Pressure
Loading...