Series
19/64
[7.54]
3
[76.20]
1-3/4
[44.45]
2-3/8
[60.32]
DLD
Dual Channel Leak Detection Relay
Shaft Seal Leak Protection
Series DLD Dual Channel Leak Detection Relay is used to monitor the shaft seals
of two submersible pumps to detect a leak before pump failure. A leak is detected by
sensing the status of a float or conductivity switch installed in the seal cavity. When this
LEVEL
resistance drops below the set sensitivity, the output relay energizes and the corresponding
LED indicator illuminates. The DLD offers normally open relay contacts to energize an
alarm or de-energize the pump in the event of a leak. When the seal failure condition clears,
the relay automatically resets.
Model
DLD-ACY
DLD-ACZ
Pump Leak Detectors
334
Sensitivity
10 K to 25 K Ω adjustable
4.7 K to 100 K Ω adjustable
DWYER INSTRUMENTS, INC.
SPECIFICATIONS
Power Requirement: 120 VAC, 50/60 Hz.
Power Consumption: 2 VA (approximate).
Isolation Voltage: 2500 V.
Temperature Limits:
Operating: -4 to 131°F (-20 to 55°C);
Storage: -40 to 185°F (-40 to 85°C).
Switch Type: (2) N.O. SPST.
Switch Voltage 9 VDC.
Electrical Rating: 5 A @ 120 VAC resistive, 345 VA inductive.
Response Times:
Energize: 6 ms (approximate);
Release: 2.5 ms (approximate).
Indicators: Respective red LED illuminates when leak is detected.
Enclosure: Polycarbonate dust cover.
Mounting: 8-pin octal.
Weight: 8 oz (227 g).
Agency Approvals: cUR, UR.