Dwyer Instruments Series DH3 Digihelic, Series DH3, DH3 DIGIHELIC Operating And Installation Instruction

Bulletin B-30
Series DH3 Digihelic®Differential Pressure Controller
Specifications - Installation and Operating Instructions
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
1.800.868.7495
QualityInstruments-Direct.ca
2
SPECIFICATIONS Service: Air and non-combustible, compat-
ible gases.
Wetted Materials: Consult factory. Housing Material: Die cast aluminum
case and bezel. Accuracy: ±1.5% for 0.25˝ and ±0.25˝ w.c. ranges. Ranges 0.5˝ to 5˝ w.c. and corre­sponding bi-directional (except ±2.5˝ w.c.): ±1%; All other ranges: ±0.5% @ 77°F (25°C) including hysteresis and repeatabili­ty (after 1 hour warm-up).
Stability: < ±1% per year. Pressure Limits: Ranges
≤ 2.5˝ w.c.: 25 psi; ±2.5˝, 5˝ w.c.: 5 psi; 10˝: w.c. 5 psi; 25˝ w.c.: 5 psi; 50˝ w.c.: 5 psi; 100˝ w.c.: 9 psi. Temperature Limits: 32 to 140°F (0 to 60°C). Compensated Temperature Limits: 32 to 140°F (0 to 60°C). Thermal Effects: 0.020%/°F (0.036/°C) from 77°F (25°C). For 0.25˝ and ±0.25˝ w.c. ranges: ±0.03%/°F (±0.054%/°C).
Power Requirements: 12-24 VAC/VDC. Power Consumption: 3 VA max.
Output Signal: 4-20 mA DC into 900
ohms max. Zero & Span Adjustments: Accessible via menus. Response Time: 250 ms (dampening set to 1). Display: Backlit 4 digit LCD 0.4˝ height LED indicators for set point and alarm sta­tus. Electrical Connections: 15 pin male high density D-Sub connection. 18˝ (46 cm) cable with 10 conductors included. Process Connections: 1/8˝ female NPT. Side or back connections. Mounting Orientation: Mount unit in verti­cal plane. Size: 5˝ (127 mm) O.D. x 3-1/8˝ (79.38 mm).
Weight: 1.75 lbs. (794 g). Agency Approvals: CE.
SWITCH SPECIFICATIONS Switch Type: 2 SPDT relays. Electrical Rating: 1 amp @ 30 VAC/VDC. Set Point Adjustment: Adjustable via key-
pad on face.
DIMENSIONS
(4) 6-32 HOLES
EQUALLY SPACED ON A
5-1/8 (130.18) B.C. PANEL MOUNTING
1/8 FEMALE NPT LOW
PRESSURE CONNECTION
1/8 FEMALE NPT HIGH
PRESSURE CONNECTION
2-1/16
(52.39)
2
(50.80)
1-1/4
(31.75)
ø4-47/64
(120.25)
Ø5
(127.00)
Ø4 (101.60)
FACE
5-1/2 (139.70) O.D.
MOUNTING RING
5/8 (15.88)
PANEL MAX
2-1/2
(63.50)
3/16
(4.76)
1/8 FEMALE NPT HIGH PRESSURE CONNECTION
1/2
(
12.70)
1-9/32
(32.54)
1
1/16
(17.46)
30°
1-3/4
(44.45)
1/2 (12.70)
11/16
(17.46)
1/8 FEMALE NPT LOW
PRESSURE CONNECTION
(3) Ø3/16 (4.77) HOLES EQUALLY SPACED ON A 4-1/8 (104.78) B.C. SURFACE MOUNTING
1.800.868.7495
QualityInstruments-Direct.ca
INSTALLATION LOCATION: Select a clean, dry location free from shock and vibration where temperature
limits will not be exceeded. Distance from the transmitter to the receiver is limited only by total loop resistance. See ELECTRICAL CONNECTIONS. Tubing feeding pressure to the instrument can be practically any length required, but long lengths will increase response time slightly.
POSITION: All standard models are calibrated for use in a vertical mounting position. Higher range models will perform properly at other angles but should be spanned and zeroed in the position in which they will be used. Because of their sensitivity to gravitation­al forces, models with ranges under 1˝ w.c. (25.4 mm w.c.) must always be mounted ver­tically.
PRESSURE CONNECTIONS: For installation convenience two sets of 1/8˝ female NPT pressure ports are supplied. Be sure to seal the unused ports with pipe plugs included.
Positive Pressure - Connect tubing to HIGH PRESSURE port and vent LOW PRESSURE port to atmosphere.
Negative (Vacuum) Pressure - Connect tubing to LOW PRESSURE port and vent HIGH PRESSURE port to atmosphere. (When operating this device in a dusty environment, install an optional A-331 Filter Vent Plug in the vented port to keep interior clean.)
Differential Pressure - Connect tubing from the higher source to HIGH PRESSURE port and from the lower source to LOW PRESSURE port.
3
1-1/2
[38.1]
5/16
[7.94]
11/16
[17.46]
3/4
[19.05]
1-3/32
[27.78]
1-3/4
[44.45]
1/2 [12.70]
(3) Ø3/16 [4.77] HOLES EQUALLY SPACED ON A 4-1/8 [104.78] B.C.
Ø1/2 [12.70] HOLE FOR LOW PRESSURE CONNECTION
Ø1/2 [12.70] HOLE FOR HIGH PRESSURE CONNECTION
Fig. A
1.800.868.7495
QualityInstruments-Direct.ca
4
MOUNTING: The DH 3 may be either panel (flush) mounted or surface mounted.
Panel Mounting - Cut a 4-13/16˝ or 122 mm diameter hole in the panel and insert the unit
from the front. Slip on the mounting ring with the stepped side facing rear. Next, fit the snap ring into the narrow groove at back edge of bezel. Thread four (6) 32 x 1-1/4˝ mounting screws into tapped holes in mounting ring and set it against snap ring. Tighten screws against rear of panel. See Fig. B.
Surface Mounting - Drill (3) 3/16˝ (4.76 mm) diameter holes for mounting and cut a 9/16˝ x 1-1/2˝ (14.3 x 38.1 mm) opening for access to terminal block as indicated in Fig. B. If rear pressure connections are to be used, also provide 1/2˝ diameter holes as shown in Figs. A and C. Insert 6-32 machine screws from rear of mounting surface, thread into tapped holes on back of transmitter and tighten.
Fig. B
Fig. C
Ø4-3/4 [120.65] HOLE
PNEUMATIC PRESSURE TAP S
SNAP RING
GROOVE
1.800.868.7495
QualityInstruments-Direct.ca
WIRING
The DH 3 uses a standard 15 pin male high density D-Sub connector available from most electronic distributors. A pre-wired 18˝ cable is included with each unit. See below table for cable color wiring information.
NOTES:
1. If 12-24 VDC power is used, the polairty is unimportant.
2. Wire in accordance with an equivalent national standard or code. Use copper conduc­tors only rated for 60°C.
3. All terminals are rated CLASS 2.
4. ISOLATION: All inputs and outputs to each other: 500 VAC.
5. 4-20 mA Transmitter – Check the specifications for the device receiving this signal for input resistance. Typical 250 to 600 OHMS, 600 OHMS maximum.
5
Function
12-24 VAC/VDC Power 12-24 VAC/VDC Power 4-20mA XMTR Output ­4-20mA XMTR Output + SP1 Relay N/O SP1 Relay Com SP1 RELAY N/C SP2 or ALarm Relay N/O SP2 or ALarm Relay Com SP2 or ALarm Relay N/C
15 PIN Connector Terminal
1 6 2 11 12 13 14 15 10 5
Cable Color
Brown Yellow Black Red Vilolet Grey White Blue Green Orange
1.800.868.7495
QualityInstruments-Direct.ca
6
SP/ALSP/AL
M
ENUMENU
EE
RSTRST
Home Position Function
Sequences the display through SET POINT and ALARM settings Allows access to the menus
Displays full scale range of unit
Clears or resets an Alarm (alarm set for manual reset)
Main Menu Function
Return to home position
Return to home position
Sequences through menus
Sequences through menus
Enter into SUB MENU
Sub Menu Function
Return to home position
Return to previous menu
Increments a value
Decrements a value
Changes a value or setting. Press ENTER and display will blink. Adjust with UP or DOWN arrows. Press ENTER to store. Display will stop blinking.
Peak/Valley SUB  MENU resets display to present value.
SP/AL
MENU
UP
ARROW
DOWN
ARROW
ENTER
RESET
KEY FUNCTIONS
INWCINWC
1.0001.000
SP1SP1
SP2SP2
ALHIALHI
ALLOALLO
SP/ALSP/AL
RSTRST
MENUMENU
EE
X1KX1K
FRONT PANEL
ALARM DESCRIPTOR
UNITS
I
NPUT VALU E
MULTIPLIER
DESCRIPTOR
VISABLE WITH
SOME VELOCITY
A
ND FLOW
RANGES
SP2 DESCRIPTOR
SP1 DESCRIPTOR
1.800.868.7495
QualityInstruments-Direct.ca
7
SETTING SET POINTS AND ALARMS
The hot key provides direct access to the Set Point and Alarm MENU. The Set Point and Alarm MENUS that are displayed are based upon the Control (CtrL) SUB MENU.
S
P/ALSP/AL
S
P/ALSP/AL
S
P/ALSP/AL
SP/ALSP/AL SP/ALSP/AL
S
P/ALSP/AL
S
P/ALSP/AL
SP/ALSP/AL
SP/ALSP/AL SP/ALSP/AL
SP/ALSP/AL
S
P/ALSP/AL
S
P/ALSP/AL
Visible whenVisible when
Visible whenVisible when
Visible whenVisible when
mode =mode =
mode =mode =
mode =mode =
CONTROL MODECONTROL MODE
CONTROL MODECONTROL MODE
CONTROL MODECONTROL MODE
SET POINT ADJUSTMENT
Adjusting the DH
®
3 Set Points is quick and simple. Instead of setting a set point and dead-
band, simply adjust
SP1H
or
SP2H
for the desired relay turn on point, and then adjust
SP1L
or
SP2L
for the desired relay turn off point.
PRES
SURE
PRESSURE
00
00
TIMETIME
0.20.2
0.40.4
0.60.6
0.80.8
1.0
(in. w.c.)
In the above graph, an instrument with a 1.0˝ range would have the SP1 relay turn on at
0.8˝ and off at 0.4˝.
SP1H
sets the relay turn on point, and
SP1L
sets the relay turn off point. The relays outputs normally function in the direct acting mode, which means the relays turn on with an increase in pressure. SP1 may be configured to act as a reverse acting relay (refer to the 1SP SUB MENU setting, page 15). When set for reverse acting,
SP1H
sets the
relay turn OFF point, and
SP1L
sets the relay turn ON point. SP2 is always direct acting.
SP/ALSP/AL
1.800.868.7495
QualityInstruments-Direct.ca
8
MENU MAPMENU MAP
CONTINUED
CONTINUED
SETTINGSSETTINGS
MAIN MENUS SUB MENUS
MENUS
UNAVAILABLE
FOR
BI-DIRECTIONAL
RANGES AND
RANGES ABOVE
25 IN. W.C.
EE
MENUMENU
1.800.868.7495
QualityInstruments-Direct.ca
9
CONTINUEDCONTINUED
SETTINGSSETTINGS
MAIN MENUS SUB MENUS
0PEn
EE
MENUMENU
1.800.868.7495
QualityInstruments-Direct.ca
10
MAIN MENUS SUB MENUS
SETTINGS
Menus present only
in pressure operation
EE
MENUMENU
1.800.868.7495
QualityInstruments-Direct.ca
11
M
ain Menu Selections (Upper Right Display Reads
M
ENU
)
SECr
Security - Lock out access to Set Point and Alarm settings, or lock out access to
all settings.
OPEr
Operation - Selection of Pressure, Velocity or Flow and corresponding engineering
units.
OUt
Output - Select a Single Set Point, 2 Set Points, or a Set Point and an Alarm
mode of operation.
d.S
Display - Monitor and adjust display related settings: Peak, Valley, display reso-
lution, % output and dampening.
AdU
Advanced functions - Modify advanced function parameters, transmitter output
scaling, Maintenance Set Point settings and calibration.
1.800.868.7495
QualityInstruments-Direct.ca
12
MAIN MENUS and SUB MENUS
SECr
(Security) MAIN MENU
SECr
is the only SUB MENU in the security MENU. When the security SUB MENU is selected, the present security level is displayed in the upper right hand display. To change the security level, adjust the number displayed to the number shown in the following table for the desired security level.
The password values shown in the table cannot be altered, so retain a copy of these pages for future reference.
OPEr
(Operation) MAIN MENU
The
OPEr
MENU selects the measurement type of the instrument.
The SUB MENUS are:
PrES
- Pressure
KFAC
- K Factor
XDIM
- X Dimension
UEL
- Velocity
ArEA
- Area
YDIM
- Y Dimension
FLO
- Flow
DIA
- Diameter
If the instrument is set for Velocity, the
OPEr
MENU will have an additional
KFAC
SUB
MENU. If the instrument is set for Flow, the
OPEr
MENU will have additional
KFAC
and
ArEA
SUB MENUS. These will be discussed under Velocity and Flow. When scrolling
through the
OPEr
SUB MENUS, the measurement type the unit is currently set for will show the units in the upper right display. The other measurement types will have a blank upper right display.
Security Level Displayed
1 2
3
4
Access
All menus access
Menu Access SP/AL Locked SP/AL Access Menus Locked All settings locked
Password Value to Enter
10
70
90
111
Units visible, so unit is presently set to measure pressure
is presently set to measure pressure
Units not visibleUnits not visible Units not visibleUnits not visible
1.800.868.7495
QualityInstruments-Direct.ca
13
PrES
(Pressure) SUB MENU
For pressure measurement, the following units are available:
Table 1 Pressure Range vs. Available Units
INWC
.1000 .2500 .5000
1.000
2.500
5.000
10.00
25.00
50.00
100.0
FTWC
.2083 .4167 .8333
2.083
4.167
8.333
MMWC
2.540
6.350
12.70
25.40
63.50
127.0
254.0
635.0 1270 2540
CMWC
.2540 .6350
1.270
2.540
6.350
12.70
25.40
63.50
127.0
254.0
PSI
.1806 .3613 .9032
1.806
3.613
INHG
.1839 .3678 .7356
1.839
3.678
7.356
MMHG
.1868 .4671 .9342
1.868
4.671
9.342
18.68
46.71
93.42
186.8
MBAR
.2491 .6227
1.245
2.491
6.227
12.45
24.91
62.27
124.5
249.1
PA
24.91
62.27
124.5
249.1
622.7 1245 2491 6227
KPA
.1245 .2491 .6227
1.245
2.491
6.227
12.45
24.91
HPA
.2491 .6227
1.245
2.491
6.227
12.45
24.91
62.27
124.5
249.1
OZIN
.1445 .2890 .5780
1.445
2.890
5.780
14.45
28.90
57.80
UEL
(Velocity) SUB MENU
For velocity measurement, the following units are available:
SFPM
- Standard feet per minute
M/S
- Meters per second
Table 2 Available Velocity Ranges
NOTE: Air velocity and flow readings are based upon standard dry air conditions with an
ambient temperature of 70°F and a barometric pressure of 29.92 INHG.
INPUT RANGE INWC
0 - 0.1 0 - 0.25 0 - 0.5 0 - 1 0 - 2.5 0 - 5 0 - 10 0 - 25
SFPM RANGE
0 - 1266 0 - 2002 0 - 2832 0 - 4004 0 - 6332 0 - 8954 0 - 12.66 x IK 0 - 20.02 x IK
M/S RANGE
0 - 6.431 0 - 10.17 0 - 14.39 0 - 20.35 0 - 32.17 0 - 45.48 0 - 64.33 0 - 101.7
INWC
- Inches of water column
FTWC
- Feet of water column
MMWC
- Millimeters of water column
CMWC
- Centimeters of water column
PSI
- Pounds per square inch
INHG
- Inches of mercury
MMHG
- Millimeters of mercury
MBAR
- Millibar
PA
- Pascal
KPA
- Kilopascals
HPA
- Hectopascals
OZIN
- Ounce inches
NOTE:
OVFL
(over flow) or
UnFL
(under flow) will appear when the ranges have been
exceeded above or below full scale by 2%.
1.800.868.7495
QualityInstruments-Direct.ca
14
F
LO
(
Flow) SUB MENU
For flow measurements the following units are available:
SCFM
- Standard cubic feet per minute
M^3H
- Cubic meters per hour
FLO r
(Flow Range) SUB MENU
LO
- 99.99 x 1K flow range
HI
- 999.9 x 1K flow range
Tables 3-6 show the flow ranges available, and the maximum duct size that can be set for each input range.
Table 3
FLOr = LO
Maximum Duct Size (English)
RANGE IN WC
0.1
0.25
0.5 1
2.5 5 10 25
SCFM RANGE
99.99 x 1K
99.99 x 1K
99.99 x 1K
99.99 x 1K
99.99 x 1K
99.99 x 1K
99.99 x 1K
99.99 x 1K
MAX. DUCT SIZE, SQ. FT.
78.9
49.9
35.3
24.9
15.7
11.1
7.8
4.9
KFAC
SUB MENU
KFAC
K Factor - becomes accessible if the instrument is set for Velocity or Flow.
When the DH3
®
is used with a Pitot tube, the manufacturer may specify a K
Factor. The adjustment range is 0.01 to 2.00. The factory setting is 1.
Table 4
FLOr = HI
Maximum Duct Size (English)
RANGE IN WC
0.1
0.25
0.5 1
2.5 5 10 25
SCFM RANGE
999.9 x 1K
999.9 x 1K
999.9 x 1K
999.9 x 1K
999.9 x 1K
999.9 x 1K
999.9 x 1K
999.9 x 1K
MAX. DUCT SIZE, SQ. FT.
789.8
499.5
353.1
249.7
157.9
111.7
78.9
49.9
Table 5
FLOr = LO
Maximum Duct Size (Metric)
RANGE IN WC
0.1
0.25
0.5 1
2.5 5 10 25
Mˆ3/Hr RANGE
99.99 x 1K
99.99 x 1K
99.99 x 1K
99.99 x 1K
99.99 x 1K
99.99 x 1K
99.99 x 1K
99.99 x 1K
MAX. DUCT SIZE Mˆ2
4.32
2.73
1.93
1.37
0.86
0.61
0.43
0.27
Table 6
FLOr = HI
Maximum Duct Size (Metric)
RANGE IN WC
0.1
0.25
0.5 1
2.5 5 10 25
M
3
/Hr
Range
999.9 x 1K
999.9 x 1K
999.9 x 1K
999.9 x 1K
999.9 x 1K
999.9 x 1K
999.9 x 1K
999.9 x 1K
MAX. DUCT SIZE, M
2
43.19
27.31
19.3
13.64
8.63
6.10
4.31
2.73
1.800.868.7495
QualityInstruments-Direct.ca
15
A
rEA
,
D
IA
,
X
DIM
a
nd
Y
DIM
S
UB MENUS
These SUB MENUS become accessible if the instrument is set for flow. When measuring flow, the area of the duct must be specified. Tables 3 and 4 show the input range vs max­imum flow and duct size. For a rectangular duct the maximum size is specified in square feet or meters. For a circular duct the maximum size is specified as the diameter. X, Y and circular dimensions are entered in feet with 0.01 foot resolution for
FLOr = LO
and 0.1 foot
resolution for
FLOr = HI
, or entered in millimeters with 1 millimeter resolution.
ArEA
- Area, select
CIR
for a circular duct or
RECT
for a rectangular duct. If a
circular duct is selected, the
DIA
SUB MENU will be activated. If a rectangular duct
is selected, the
XDIM
and
YDIM
SUB MENUS will be activated.
DIA
- Diameter, enter the diameter of a duct
XDIM
- Enter the “X” dimension of a duct
YDIM
- Enter the “Y” dimension of a duct
OUt
(Output) MAIN MENU
The
OUt
MENU selects the output type of the instrument. The SUB
MENUS are:
CtrL
- Control type
ALrE
- Alarm reset, manual or auto
ISP
- SP1 reverse or direct acting
AL.H
- Alarm inhibit
AL
- Alarm type
ALDL
- Alarm delay
Y
X
1.800.868.7495
QualityInstruments-Direct.ca
16
0
100
Process
Rever
se A
ct
i
ng
Tim
e
SPH
SPL
Relay Inactive
Relay Active
C
trL(Control) SUB MENU
1SP
- Single set point
2SP
- Two fully independent set points
SPAL
- Single set point and alarm
1SP
(SP1 Reverse or Direct Acting) SUB MENU
DIR
- Direct. Relay turns on with increasing pressure
REV
- Reverse. Relay turns on with decreasing pressure
0
100
Process
D
i
re
ct
Act
i
n
g
T
im
e
SPH
SPL
Relay Inactive
Relay Active
1.800.868.7495
QualityInstruments-Direct.ca
17
T
he following alarm function SUB MENUS are activated when
C
trL
i
s set to
S
PAL
:
AL
(Alarm Type) SUB MENU
HI
- High alarm
LO
- Low alarm
HILO
- For a high/low guardband type alarm
ALARM ADJUSTMENT
Alarm settings are dependent upon the selected alarm mode. The DH3
®
differential pres­sure controller alarm may be configured as a High Alarm, Low Alarm, or High/Low Alarm. Alarm settings are all absolute and may be set to anywhere within the range of the instru­ment. The dead bands of the alarms are fixed at 1% of full scale.
MIN. PRESSURE
MAX. PRESSURE
ALHI
Relay OFF Relay ON
HIGH ALARM FUNCTION
MIN. PRESSURE
MAX. PRESSURE
ALLO
Relay ON Relay OFF
LOW ALARM FUNCTION
MIN. PRESSURE
MAX. PRESSURE
ALLO
Relay ON Relay OFF Relay ON
HIGH/LOW ALARM
FUNCTION
ALHI
1.800.868.7495
QualityInstruments-Direct.ca
18
A
L0S
(
Alarm Output State) SUB MENU
CL0S
- Alarm relay contacts close upon alarm condition
0PEN
- Alarm relay contacts open upon alarm condition
ALrE
(Alarm Reset) SUB MENU
ONOF
- Automatic reset
HOLD
- Manual reset. An alarm is reset by the RESET key on the front
panel, or an external reset switch.
AL.H
(Low Alarm Inhibit) SUB MENU
ON
- Alarm inhibit is on
OFF
- Alarm inhibit is off
If
AL.H
is selected ON, a low alarm condition is suspended upon power up until the
process value passes through the alarm set point once.
ALDL
(Alarm Delay) SUB MENU
Sets the amount of time an alarm condition must be continuously met before the alarm condition is recognized. The alarm delay is adjustable from 0-3600 seconds.
d.S
(Display) MAIN MENU
PEAK
- Peak value
rESO
- Resolution
VALy
- Valley value
Pd.S
- Process display
ZERO
- Zero
DAMP
- Dampening level
PEAK
(Peak) SUB MENU
The Peak feature stores the highest pressure reading the instrument has measured since the last reset or power up. At power up
PEAK
is reset to the present pressure
reading. To manually reset the
PEAK
value, press the RESET key while in the
PEAK
SUB MENU.
VALy
(Valley) SUB MENU
The valley feature stores the lowest pressure reading the instrument has measured since the last reset or power up. At power up
VALy
is reset to the present pressure
reading. To manually reset the
VALy
value, press the RESET key while in the
VALy
SUB MENU.
1.800.868.7495
QualityInstruments-Direct.ca
19
r
ESO
(
Resolution) SUB MENU
The DH 3 is capable of displaying four digits of resolution. However, at very low pressures the instability of the pressure may cause fluctuations in the least significant digit causing the least significant digit to be of little value. Three digit resolution (
3DIG
) can only be active when there is at least one digit to the
right of a decimal.
3DIG
- Set display for 3 digit resolution
4DIG
- Set display for 4 digit resolution
Pd.S
(Process Display) SUB MENU
STD
- Display reads pressure, velocity, or flow values
PCT
- Display reads % of full scale value
When the display is reading percent,
PCT
is displayed in the upper right of the
display. The percent display is only available in pressure operation.
DAMP
(Dampening) SUB MENU
Adjust from 1-16
Dampening stabilizes the display from instabilities due to things such as vibration and excessive pressure fluctuations. The dampening setting adjusts the amount of readings that are averaged for each display update. Adjust the dampening value until the display reads a stable value for the application.
AdU
(Advanced) MAIN MENU
POL
- Process output low
ZERO
- Zero calibration
POH
- Process output high
SPAN
- Span calibration
MSP1
- Maintenance set point 1
MSP2
- Maintenance set point 2
POL
and
POH
(Process Output Low and High) SUB MENUS
This feature is used in pressure operation only.
Process output low and high are used to scale the 4-20 mA output. Set
POL
to the
desired display reading for 4mA output, and set
POH
to the desired display reading
for 20 mA output.
POH
must be higher than
POL. POL
may be adjusted 2% BELOW
minimum scale up to
POH. POH
may be adjusted from
POL
to 2% ABOVE maximum
scale.
1.800.868.7495
QualityInstruments-Direct.ca
M
SP1
a
nd
M
SP2
(
Maintenance Set Point 1 & 2) SUB MENUS
Adjust for the desired maintenance set points when the unit is placed in the maintenance mode. The deadband is fixed at 2% of full scale. To enter or leave the maintenance mode, press and hold the for 8 seconds.
ZERO
and
SPAN
(Calibration of Zero and Span) SUB MENUS
The lower display reads
CAL
in this mode.
ZERO
Calibration
NOTE: For accurate calibration, DO NOT apply any pressure when
performing this function.
With the display reading
ZERO
, press the ENTER key. The upper display will blink. Press ENTER again to complete the zeroing of the instrument or press the
MENU
key to cancel.
SPAN
Calibration
With the display set to
SPAN
, apply full scale pressure to the unit. Press the ENTER key. The upper display will blink. Press ENTER again to complete the calibration or press the
MENU
key to cancel.
SP/ALSP/AL
©Copyright 2012 Dwyer Instruments, Inc.
Printed in U.S.A. 2/12
FR# 443555-00 Rev.3
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
1.800.868.7495
QualityInstruments-Direct.ca