Dwyer Instruments SERIES CT40, SERIES 50 Catalog Page

Series
Current Transformer
4-20 mA or 0-5 VDC Output, Split Core Case
55/64
[21.85]
33/64
[13.21]
1/8
[3.18]
Series CT40/50 combine current transformer and signal conditioner into a single package. Transformers feature jumper selectable ranges and split core case. Units are designed for applications on linear or sinusoidal AC loads.
Model CT40-100
CT40-102 CT50-100
CT50-102
Range
10/20/50 A
10/20/50 A 100/150/200 A
100/150/200 A
Output
4-20 mA
0-5 VDC 4-20 mA
0-5 VDC
Power Requirements
12-40 VDC, Loop Powered Self Powered 12-40 VDC, Loop Powered Self Powered
55/64
[21.73]
2-13/32
[60.99]
33/64
[13.21]
Split Core-Top Terminals
23/64 [9.15]
23/32
[18.33]
2-1/4
[57.15]
1-3/16
[29.94]
SPECIFICATIONS Output Signal: 0-5 VDC or 4-20 mA, depending on model. Power Requirements: See table. Accuracy: CT40/50-102: 1.0% FS; CT40/50-100: 0.5% FS. Temperature Limits: -4 to 122°F (-20 to 50°C). Response Time: CT40/50-102: 100 ms; CT40/50-100: 300 ms. Isolation Voltage: 1270 VAC. Frequency: CT40/50-102: 50-60 Hz; CT40/50-100: 20-100 Hz
(sinusoidal waveforms only).
Enclosure Rating: UL 94V-0 flammability rated. Agency Approval: CE.
3-17/32
[89.70]
2-13/32
[61.01]
3-3/64
[77.36]
RANGE JUMPER
3/16 I.D. TYP.
2 PLACES
PROCESS CONTROL
Current Transformers/
Switches