2X 5/16 [7.94]
4
[101.6]
3-31/64
[88.5]
3
[76.2]
4-9/16
[115.89]
2-3/4
[69.85]
1-31/64
[37.70]
1-27/64
[36.12]
Series
CMT
Carbon Monoxide Transmitter
Current/Voltage Output, 125 PPM Range
3-1/2 [88.90]
6 [152.40]
Wall Duct
The Series CMT Carbon Monoxide Transmitter accurately detects and transmits
low concentrations of carbon monoxide inside a parking garage or loading dock.
Transmitters can be ordered in wall mount or duct mount configurations. Universal current
and voltage outputs are field selectable and match most common building management
controllers. Optional relay and alarm buzzers are available on the wall mount models to
directly connect to a warning light or exhaust fan. The Series CMT can be field calibrated
using internal potentiometers. Software settings such as set points for optional relay
outputs are password protected.
Model
CMT-WN
CMT-WN-WP
CMT-WR-WP
CMT-WN-D
CMT-DN
CMT-DN-D
Configuration
Wall
NEMA 4X Wall
NEMA 4X Wall
Wall
Duct
Duct
External Display
No
No
No
Yes
No
Yes
Alarm/Buzzer
No
No
Yes
No
No
No
146
1-3/32
[27.69]
SPECIFICATIONS
Range: 0 to 125 PPM CO.
Accuracy: ±2.5% of reading.
Repeatability: ±1% of reading.
Response Time: Less than 60 seconds typical for 90% step change.
Ambient Operating Temperature: -4 to 104°F (-20 to 40°C).
Ambient Operating Humidity: 15 to 90% non-condensing.
Power Requirements: 24 VDC/VAC at 100 mA.
Internal Display: Two line 8-digit alphanumeric LCD.
Sensor: Electrochemical (2 to 3 year expected life typical).
Output: Current/voltage: 4 to 20 mA and 2 to 10 VDC; Optional relay: (2) SPDT 1
Amp dry contact; Buzzer: 85 dB @ 1 foot.
Coverage Area: 7500 square feet (max).
Weight: 5.7 oz (161.6 g).
1-19/32
[40.31]