Dwyer Instruments SERIES CDX Catalog Page

4-37/64
[116.33]
1-1/64
[25.65]
3-13/64
[81.28]
Ø5/32 x 4
[Ø3.87]
Ø5/32 x 3
[Ø3.87]
3-13/64
[81.28]
1-1/16
[27.18]
3-13/32
[86.36]
RoHS
Series
CDX
Wall Mount Carbon Dioxide Transmitter
Measures up to 2000 ppm, Adjustable Output
Scan here to watch product video
The Series CDX Carbon Dioxide Transmitter is a low cost and high performing CO2
sensor. This product will provide immediate energy savings by functioning in conjunction with building automation systems and allowing the user to effortlessly and effectively control fresh air into preferred areas. On-Demand ventilation using CO2 sensors prevents energy losses from over ventilation while maintaining indoor air quality. The potential for the greatest energy saving occurs in areas where occupancy alters over the duration of the day. The Series CDX Transmitters utilize the patented Automatic Background Calibration (ABC) Logic self-calibration system. ABC Logic virtually eliminates the need for manual calibration in applications where the indoor CO2 level drops to outside levels during unoccupied periods. If the transmitter is being used in an application where a building is continuously occupied 24 hours per day, then the user will permit that the ABC Logic feature be turned off.
Model CDX-2W10 CDX-2W20 CDX-2E10 CDX-2E20
ACCESSORIES Model 1508, Duct Mount Enclosure Model 1552, Outside Air Measurement Enclosure
Output
Current Voltage Current Voltage
Housing
North America North America Europe Europe
North American European
North American
SPECIFICATIONS Range: 0 to 2000 PPM. Accuracy: ±30 PPM or 3% of reading,
whichever is higher. CO2 accuracy statement excludes standard gas used for calibration that has an accuracy of 2% and there is a potential digital to analog error of up to 1%. Temperature Dependence: 0.2% FS per °C (± 0.11% per °F). Stability: < 2% of FS over life of sensor (15 years). Pressure Dependence: .135% of reading per mm of Hg.
Response Time: 5 s. Warm Up Time: < 2 min (operational),
10 min (max. accuracy).
Temperature Limits:
Operating: 32 to 122°F (0 to 50°C); Storage: -40 to 158°F (-40 to 70°C).
European
Humidity Limits: 0 to 95% relative
humidity, non-condensing. Power Requirements: 18 to 30 VAC RMS, 50/60 Hz, or 18 to 42 VDC, polarity protected. Power Consumption: .7 W @ nominal voltage of 24 VAC RMS. Sensor: Non-dispersive infrared (NDIR) absorption. Output: Analog, 0 to 5 V or 0 to 10 V jumper selectable (100 Ω output impedance), 4 to 20 mA (RL maximum 500 Ω). Housing: Flammability classification UL94 5VA. Weight: European Housing: 5.44 oz (154 g); North American Housing: 6.24 oz (177 g).
Agency Approvals: CE, RoHS.