SERIES AVLV | LOW AIR VELOCITY TRANSMITTER
FEATURES/BENEFITS
• Sensing elements have been coated with an engineered conformal coating to ensure durability and longevity
•
Fieldselectablerangescanbequicklyconguredwithoutpowertotheunit
DESCRIPTIONAPPLICATIONS
• VAV systems
• Building ducts
• Clean room systems
The Series AVLV Low Air Velocity Transmitter quickly and accurately measures air velocity or
volumetric ow in imperial or metric units. Simultaneous current and voltage outputs on all models
provide universal inputs to monitoring equipment while the output range, units, and 0-5/10 VDC
output can be congured via local DIP switches. The optional integral display, or the portable remote
tool, provide a convenient way to local monitor process values and congure the unit.
Models are available in 1% and 2% accuracy models and low velocity ranges to suit a variety of
needs, and the optional BACnet MS/TP or Modbus® RTU/ASCII communication protocol allows
units to be daisy-chained while providing access to all of the velocity and ow data, as well as
additional information such as air temperature. The lower ranges in these high accuracy units allow
for applications in quality intensive environments, such as the pharmaceutical industry.
SPECIFICATIONS
Service Clean air and non-combustible, compatible gases.
Wetted Materials Consult factory.
Range 100, 200, 300, 400 FPM (0.5, 1, 1.5, 2 m/s); eld selectable.
Accuracy See chart.
TemperatureLimits 32 to 122°F (0 to 50°C).
Power Requirements 24 VDC ±20% or 24 VAC ±20%.
Humidity Limits 5 to 95% RH, non-condensing.
OutputSignals 4-20 mA, 0-5 VDC, 0-10 VDC.
ResponseTime(90%) 4 s, typical; 1 s at constant temperature.
ZeroandSpanAdjustments Digital push buttons.
OutputLoadResistance Current output: 0 to 1100 Ω max.; Voltage output: Minimum load resistance 1 kΩ.
CurrentConsumption 60 mA max.
Display 5 digit LCD (optional).
Electrical Connections Analog: Power and output: four wire removable European style terminal block for 16 to 26 A
Connections: BACnet MS/TP or Modbus® RTU/ASCII: three wire removable European style terminal block for 16 to 26
AWG.
SupportedCommunication
Baud Rates
Device Load 1/8 unit load.
Electrical Entry 1/2˝ NPS thread. Accessory: Cable gland for 5 to 10 mm diameter cable, A-151.
Enclosure Rating NEMA 4X (IP66).
Mounting Orientation Flow direction must be parallel to the sensor tip.
Weight 6.0 oz (160 g).
AgencyApprovals BTL, CE.
9600, 19200, 38400, 57600, 76800, 115200. (optional).
WG; Communication:
DIMENSIONS WIRING DIAGRAM
3-49/64
[95.71]
3-33/64
[89.13]
1/2 NPS
2-43/64
[67.92]
7-41/64
[194.07]
7-17/64
[184.60]
39/64
[15.32]
Ø15/32
[80.81]
1-19/32
[40.59]
2-5/32
[54.82]
HOW TO ORDER
Use the bold characters from the chart below to construct a product code.
AVLV -2 D A1 -LCD
SERIES
AVLV: Low air velocity transmitter
ACCURACY
-2: ± (2% of reading + 0.06 m/s)
-1: ± (1% of reading + 0.06 m/s)
MOUNTING
D: Duct mount
OUTPUT
A1: Analog universal (0-5 VDC, 0-10 VDC, 4-20 mA)
B1: Analog + BACnet MS/TP
M1: Analog + Modbus
®
RTU/ASCII
POWER
POWER
1234
ZERO
Current output
1234
ZERO
Voltage output
PWR
PWR
GND
GND
IOUT
IOUT
SW1
SW1
SW1
VOUT
VOUT
D1(+)
D1(+)
D0(-)
COM
CURRENT
RECEIVER
D0(-)
COM
VOLTAGE
RECEIVER
SPAN
SPAN
OPTIONS
-LCD: LCD display
-FC: Factory calibration certicate
ZERO
1234
SPAN
-NIST: NIST certicate
-GLD: Electrical cable gland
IOUT
VOUT
D1(+)
D0(-)
COM
VOLTAGE
RECEIVER
ACCESSORIES
Model Description
A-AVLV-LCD
A-AVUL-MTG
Field upgradeable display
Replacement duct mount plate assembly
POWER
CURRENT
RECEIVER
PWR
GND
Simultaneous current and voltage output
Modbus® is a registered trademark of Schneider Automation, Inc.
DWYER INSTRUMENTS, INC.
©Copyright 2019 Dwyer Instruments, Inc.
Printed in U.S.A. 7/19 DS-AVLV Rev. 1
Important Notice: Dwyer Instruments, Inc. reserves the right to make changes to or discontinue any product or service identied in this publication without notice. Dwyer advises its customers to obtain the
latest version of the relevant information to verify, before placing any orders, that the information being relied upon is current.