Series A6 Durable Pressure Switch
ø1.500
[ø38.1]
ADJUSTMENT
Specications - Installation and Operating Instructions
Bulletin IN-A6
ø1.500
Series A6 Durable Pressure Switches have been specically designed to stand up
to extended duty applications. These switches are constructed with a polyimide lm
diaphragm and are compatible with a variety of uids. For ease of installation, the
switches come with a 1/4˝ male NPT process connection and can be mounted in any
orientation. The Series A6 pressure switches are compact and have great setpoint
integrity, and feature simple, easy set-point eld adjustment.
INSTALLATION/MOUNTING
The switch can be mounted in any position. Do not twist the case when installing.
Note: National Pipe Thread (NPT) when mated may contain slight gaps between
the major and minor diameter of the threads therefor plumbing tape or a compatible
sealing agent must be used on the brass ttings to ensure proper sealing and avoid
leaking.
Model
A6-151221
A6-251221
A6-351221
A6-451221
A6-551221
A6-651221
A6-751221
A6-851221
A6-153221
A6-253221
A6-353221
A6-453221
A6-553221
A6-653221
A6-753221
A6-853221
Set Point Range psi (bar)
0.5 to 1 (0.03 to 0.07)
1.1 to 3 (0.08 to 0.21)
3.1 to 7 (0.21 to 0.48)
8 to 13 (0.55 to 0.90)
14 to 24 (0.97 to 1.66)
25 to 50 (1.73 to 3.45)
51 to 90 (3.52 to 6.21)
91 to 150 (6.28 to 10.35)
0.5 to 1 (0.03 to 0.07)
1.1 to 3 (0.08 to 0.21)
3.1 to 7 (0.21 to 0.48)
8 to 13 (0.55 to 0.90)
14 to 24 (0.97 to 1.66)
25 to 50 (1.73 to 3.45)
51 to 90 (3.52 to 6.21)
91 to 150 (6.28 to 10.35)
1.1 to 3.1 (0.08 to 0.21)
2.27 to 6.05 (0.16 to 0.42)
4.22 to 10.75 (0.29 to 0.74)
12.3 to 17.5 (0.85 to 1.21)
18.6 to 31.8 (1.28 to 2.19)
33.1 to 61 (2.28 to 4.21)
65.6 to 112.3 (4.53 to 7.75)
114.7 to 198.3 (7.94 to 13.68)
1.1 to 3.1 (0.08 to 0.21)
2.27 to 6.05 (0.16 to 0.42)
4.22 to 10.75 (0.29 to 0.74)
12.3 to 17.5 (0.85 to 1.21)
18.6 to 31.8 (1.28 to 2.19)
33.1 to 61 (2.28 to 4.21)
65.6 to 112.3 (4.53 to 7.75)
114.7 to 198.3 (7.94 to 13.68)
Base
MaterialNC NO
Brass
Brass
Brass
Brass
Brass
Brass
Brass
Brass
304 SS
304 SS
304 SS
304 SS
304 SS
304 SS
304 SS
304 SS
3X #8-32
ø1-1/2
[ø38.1]
2
[50.8]
A-439A-439 A-440A-440
SPECIFICATIONS
Service: Air, motor oils, transmission
oils, jet fuels, and similar hydrocarbon
media (not for water use).
Wetted Materials: Base: 304 SS;
Diaphragm: Polyimide lm.
Temperature Limits: -40 to 248°F
(-40 to 120°C).
Pressure Limits: Operating Pressure:
150 psi (10.3 bar) for 0.5-24 psi set point
ranges, 250 psi (17.2 bar) for 25-150 psi
set-point ranges; Proof Pressure: 500 psi
(34.5 bar); Burst Pressure: 750 psi (51.7
bar) for 0.5-24 psi set point ranges, 1250
psi (86.2 bar) for 25-150 psi set-point
ranges.
Enclosure Rating: General purpose or
with cover: IP65 - weatherproof.
SETPOINT ADJUSTMENT
Setpoint is eld adjustable within the range. In order to adjust setpoint remove black
plastic cover to expose the setpoint adjustment screw as indicated in the gure
below. Adjust top screw to change setpoint. Clockwise to increase setpoint and
counterclockwise to decrease setpoint.
SCREW
WIRING
All wiring must conform to the National Electrical Code and local regulations. Do
not install the control to handle loads in excess of the electrical rating shown in the
specications. The terminals are labeled on the switch itself.
Repeatability: ±10% of set-point.
Set Point Tolerance: ±15% of range.
Switch Type: 1 SPST NO, 1 SPST NC.
NO and NC switch independent from
each other.
Electrical Ratings: Resistive: 15 A @
6 VDC, 8 A @ 12 VDC, 4 A @ 24 VDC;
Inductive: 1 A @ 120 VAC, 0.5 A @ 240
VAC.
Electrical Connections: #8-32 screw
terminals.
Process Connection: 1/4˝ NPT male.
Mounting Orientation: Switch can be
installed in any position.
Set-point Adjustment: Screw.
Weight: 0.13 lb (0.06 kg).
Agency Approval: CE.
[ø38.1]
2-5/16
Model Description
A-439
Weatherproof IP65 Cover
A-440
Weatherproof IP65 w/ Fly-wire holes
©Copyright 2018 Dwyer Instruments, Inc. Printed in U.S.A. 7/18 FR# 443563-00 Rev. 6
MERCOID
A DIVISION OF
DWYER INSTRUMENTS, INC.
CAUTION
control only with compatible medias.
MAINTENANCE
Upon nal installation of the Series A6 Durable Pressure Switch, no routine
maintenance is required. A periodic check of the system calibration is recommended.
The Series A6 is not eld serviceable and should be returned if repair is needed (eld
repair should not be attempted and may void warranty). Be sure to include a brief
description of the problem plus any relevant application notes. Contact customer
service to receive a return good authorization number before shipping.
No lubrication or periodic servicing is required. Mount the control
securely. Never exceed the electrical rating for the switch. Use the