Dwyer Instruments SERIES 861H Catalog Page

29/32
[23.10]
1-5/32
[29.36]
1-9/32
[32.54]
1/4
[6.35]
1/64
[0.51]
WARNING: DO NOT DISCONNECT WHEN CIRCUIT IS LIVE UNLESS AREA IS KNOWN TO BE NON-HAZARDOUS
QUALIFIED FOR CLASS 1 DIVISION 2. GROUPS A, B, C, D HAZARDOUS LOCATIONS WHEN USED WITH APPROVED SOCKETS. USE HOLD DOWN CLIP WHEN SOCKET MOUNTED
T-CODE T4A
BOTTOM VIEW
CONTACTS
5 AMP 120/240 VAC, 30 VDC
IND. CONT. EQ.
FOR USE IN
HAZARDOUS LOCATIONS
31BN
CHINA
D932ADL
782XDXH21- XXX VXC
RoHS
11/16
[17.60]
3-41/64
[92.40]
9/16
[14.30]
1-13/32
[35.60]
9/64
[3.40]
1-23/64
[34.60]
5/8
[16.00]
3-35/64
[90.00]
2-5/8
[66.80]
1-25/32
[45.30]
2-9/16 [65.00]
Caution!
High Temperature
861HSSRXXX-XX-X
INPUT: (VOLTAGE)
INPUT
24-280 VAC
OUTPUT
10A
(VOLTAGE)
861HSSRXXX-XX-X
CERTIFIED FOR
CLASS 1
DIVISION 2
HAZARDOUS
LOCATIONS
GROUPS 1, B, C, & D
Patent Pending
#14 AWG COPPER WIRE MAXIMUM
RATED AT 75°C
7.1 lb-in TORQUE MAXIMUM
DIN RAIL
Derating
Derating
RoHS
Series
861H
Hazardous Rated Solid State Relays
15 Amp Rating, SPST-NO, Internal Heat Sink
The Series 861H Hazardous Rated Solid State Relay provides reliable switching and long life operation in some of the most demanding applications, such as medical equipment, mining, oil and gas. It integrates an internal heat sink and internal snubber into a compact housing to save space in the panel. In order to reduce installation time, integral tabs can be used to snap the relay onto a DIN rail or surface mount to a wall inside the panel. LED indicator lights give the user quick visual indication of the switch status. The 861H is intrinsically safe rated for Class 1, Division 2 Groups A, B, C and D.
Model 861HSSR210-AC-1 861HSSR210-DC-1 861HSSR115-DD
Input Voltage
90 to 280 VAC 3 to 32 VDC
3.5 to 32 VDC
Load Voltage
24 to 280 VAC 24 to 280 VAC 3 to 50 VDC
Rated Current
10 amp 10 amp 15 amp
SPECIFICATIONS Electrical Connection: Screw terminals. Switching Operation: SPST normally open. Switching Type: AC/DC: Zero cross; DD: DC switching. Temperature Limits:
Storage: -40 to 212°F (-40 to 100°C); Operation: -22 to 176°F (-30 to 80°C).
Voltage Loss: AC/DC: 1.6 VAC max; DD: 0.5 VDC max. Output Leakage Current: AC/DC: 10 mA max; DD: 0.25 mA max. Housing: Polycarbonate. Hazardous Classification: Class 1 Division 2; Hazardous Locations: Groups A, B,
C and D.
Weight: 4.1 oz (127.1 g). Agency Approvals: RoHS, cUR, UR.
359