Dwyer Instruments SERIES 782H Catalog Page

Series
29/32
[23.10]
1-5/32
[29.36]
1-9/32
[32.54]
1/4
[6.35]
1/64
[0.51]
WARNING: DO NOT DISCONNECT WHEN CIRCUIT IS LIVE UNLESS AREA IS KNOWN TO BE NON-HAZARDOUS
QUALIFIED FOR CLASS 1 DIVISION 2. GROUPS A, B, C, D HAZARDOUS LOCATIONS WHEN USED WITH APPROVED SOCKETS. USE HOLD DOWN CLIP WHEN SOCKET MOUNTED
T-CODE T4A
BOTTOM VIEW
CONTACTS
5 AMP 120/240 VAC, 30 VDC
IND. CONT. EQ.
FOR USE IN
HAZARDOUS LOCATIONS
31BN
CHINA
D932ADL
782XDXH21­XXX VXC
RoHS
782H
PROCESS CONTROL
Hermetically Sealed Ice Cube Relays
5 Amp, 4PDT Operation, Class 1 Div II Rated
Relays
Picture shown with socket accessory
(sold separately)
The Series 782H Hermetically Sealed Ice Cube Relay is suitable for switching up to four circuits in a hazardous environment. It features a hermetically sealed housing and a safety seal to withstand a wash-down. The plug-in socket is easy to mount and remove from crowded DIN rails.
AC Operated Model 782XDXH21-120A DC Operated Model 782XDXH21-24D
ACCESSORY 70-782D14-1, Socket for 782H Series Relay
Input Voltage
120 VAC 50/60 Hz
Input Voltage
24 VDC
Coil Resistance
4430 Ω
Coil Resistance
650 Ω
SPECIFICATIONS Operating and Load Voltage Range: 120 VAC, 24 VDC. Electrical Connection: Silver alloy plug-in contacts. Switching Operation: 4PDT. Electrical Rating: 5 A @ 120/240 VAC 50/60 Hz or 30 VDC. Temperature Limits:
Storage: -40 to 185°F (-40 to 85°C); Operation: -40 to 158°F (-40 to 70°C).
Power Consumption: 1.2 VA; 0.9 W. Cycle Life: 100,000 cycles (electrical); 10,000,000 cycles (mechanical). Housing: Metal. Weight: 1.6 oz (45 g). Agency Approvals: CE, CSA, RoHS, cUL, UL, cUR, UR.