0.25 X 0.033 [6.35 X 0.84] QUICK CONNECT
SERIES 781 & 782
ICE CUBE RELAYS
SPDT or DPDT Operation
[40.60]
The Series 781 & 782 Ice Cube Relays are full-featured relays that can be used to
handle loads up to 15 amps for AC or DC circuits. It features a ag status indicator
and a LED status lamp to let the user know when the relay is activated. In order to
differentiate between AC and DC actuated models, the push-to-test button is color
coded and a removable lock-down lever holds the test button in place.
FEATURES/BENEFITS
• Clear plastic housing to easily view the contacts
• Flag and LED status indicators for visual conrmation of relay state
• Socket mounted for quick installation/replacement
APPLICATIONS
• Refrigeration compressor systems
• HVAC motor controls
• Water/wastewater pump control
MODEL CHART
Model Operation Input Voltage Coil Resistance Electrical Rating
781XAXRM4L-24A
781XAXRM4L-120A
781XAXRM4L-240A
781XAXRM4L-24D
782XBXM4L-24A
782XBXM4L-120A
782XBXM4L-240A
782XBXM4L-24D
AC
AC
AC
DC
AC
AC
AC
DC
24 VAC 50/60 Hz
120 VAC 50/60 Hz
240 VAC 50/60 Hz
24 VDC
24 VAC 50/60 Hz
120 VAC 50/60 Hz
240 VAC 50/60 Hz
24 VDC
[14.00]
1-3/32
[27.09]
Pictures shown with socket accessory (sold separately)781
180 Ω
4430 Ω
15720 Ω
750 Ω
180 Ω
4430 Ω
15720 Ω
650 Ω
15 A @ 277 VAC (50/60 Hz) or 28 VDC
15 A @ 277 VAC (50/60 Hz) or 28 VDC
15 A @ 277 VAC (50/60 Hz) or 28 VDC
15 A @ 277 VAC (50/60 Hz) or 28 VDC
15 A @ 120 VAC 50/60 Hz; 12 A @ 277 VAC 50/60 Hz or 28 VDC (UL);
10 A @ 277 VAC 50/60 Hz (CSA)
15 A @ 120 VAC 50/60 Hz; 12 A @ 277 VAC 50/60 Hz or 28 VDC (UL);
10 A @ 277 VAC 50/60 Hz (CSA)
15 A @ 120 VAC 50/60 Hz; 12 A @ 277 VAC 50/60 Hz or 28 VDC (UL);
10 A @ 277 VAC 50/60 Hz (CSA)
15 A @ 120 VAC 50/60 Hz; 12 A @ 277 VAC 50/60 Hz or 28 VDC (UL);
10 A @ 277 VAC 50/60 Hz (CSA)
53/64
[21.00]
782
SPECIFICATIONS
Operating and Load Voltage Range:
24-240 VAC; 24 VDC.
Electrical Connection: Silver alloy plug-
in contacts.
Switching Operation: SPDT or DPDT.
Electrical Rating: Depends on model,
see model chart.
Temperature Limits: Storage: -40 to
185°F (-40 to 85°C); Operation: -40 to
131°F (-40 to 55°C).
ACCESSORIES
Model Description
70-781D5-1A
70-782D8-1A
Socket for 781 series relay
Socket for 782 series relay
DWYER INSTRUMENTS, INC. |
19/64
[7.37]
1-3/32
[27.90]
1-17/32
[39.10]
Power Consumption: 781: 0.9 VA;
0.7W; 782: 1.2 VA; 0.9W.
Cycle Life: 100,000 cycles (electrical);
10,000,000 cycles (mechanical).
Housing: Plastic polycarbonate.
Weight: 781: 1.02 oz (29 g); 782: 1.3
oz (36 g).
Agency Approvals: CE, CSA, cULus,
cURus.
3/16
[4.75]
Relays
355