SERIES 607
PRESSURE
LOW RANGE DIFFERENTIAL PRESSURE TRANSMITTER
±0.25% or ± 0.5% Full Scale Accuracy, Ranges from 0 to 25 in w.c.
[42.06]
3-5/16 [84.12]
3-59/64 [99.62]
The Series 607 Low Range Differential Pressure Transmitter combines very low
ranges with exceptional stability, reliability and either ±0.25% or ±0.5% accuracy
for the most demanding applications. Ranges from 0-0.1˝ to 0-25 in w.c. Ultra-thin
glass clad silicon diaphragm design resists shock and vibration, practically eliminates
drift. Certication to NIST standards is included with each unit. Tough stainless steel
housing is NEMA 2 rated to protect against moisture and dirt. Use with air and other
compatible gases.
FEATURES/BENEFITS
• High stability at low pressure ranges provides exceptional accuracy for ensuring
tight-control and minimizing costly out of specication conditions
• Provides sensitivity to pressure changes but resists vibration preventing drift and
less accurate readings
• Stainless steel housing meets standards for lab and clean room applications
APPLICATIONS
• Leak detection • Clean room control • Lab and fume hood pressure control
MODEL CHART
Model Range (in w.c.) Model Range (in w.c.)
607-0
0 to .10
607-01*
0 to .10
607-1
0 to .25
607-11*
0 to .25
607-2
0 to .50
607-21*
0 to .50
607-3
0 to 1.0
607-4
0 to 2.0
607-7
0 to 5.0
*Models have a ±0.25% FS accuracy.
607-71*
607-8
607-0B
607-1B
607-2B
607-9
607-3B
607-4B
607-7B
0 to 5.0
0 to 10
0 to ±.10
0 to ±.25
0 to ±.50
0 to 25
0 to ±1.0
0 to ±2.0
0 to ±5.0
SPECIFICATIONS
Service: Air and non-conductive, non-
corrosive gases.
Wetted Materials: Contact factory.
Accuracy: ±0.5% or ±0.25% FS.
Stability: ±0.5% FS/yr.
Temperature Limits: -20 to 160°F
(-29 to 71°C), 10 to 95% RH.
Pressure Limits: 10 psig (0.69 bar).
Compensated Temp. Range: 35 to
135°F (2 to 57°C).
Thermal Effects: ±0.015% FS/°F (zero
and span).
Power Requirements: 12 to 36 VDC.
Output Signal: 4 to 20 mA DC, 2-wire.
ACCESSORY
Model Description
A-302F-A 303 SS static pressure tip with mounting ange; for 3/16˝ ID
OPTIONS
Use order code: Description
NISTCAL-PT1 NIST traceable calibration certicate
rubber or plastic tubing; 4˝ insertion depth; includes mounting
screws
7/32 [5.556]
3-13/32
[86.52]
3-7/8
[98.43]
4-3/8
[111.1]
Zero & Span Adjustments: Externally
accessible potentiometers, noninteractive, ±10% FS adjustment.
Response Time: 250 ms max.
Loop Resistance: 0 to 1045 Ω
Vmin=12V+[(.22A)(RL)].
Current Consumption: 3.6 mA (min).
Electrical Connection: Screw
terminals.
Process Connection: Barbed stainless
steel for 3/16˝ ID tubing.
Housing: 300 Series SS (NEMA 2,
IP11).
Weight: 1.04 lb (472 g).
Agency Approvals: CE.