Dwyer Instruments SERIES 605 Data Sheet

®
SERIES 605 | MAGNEHELIC® DIFFERENTIAL PRESSURE
INDICATING TRANSMITTER
FEATURES/BENEFITS
Easy to read gage permits viewing from far away
Patented design provides quick response to pressure changes means no
delay in signaling and alerting to critical situations
Durable and rugged housing and high-quality components combined
4 to 20 mA output allows for integration into Building Automation Systems
Optional stainless steel bezel is the same installation diameter as
Magnehelic
APPLICATIONS
Monitor pressures in ducts, rooms, or total building pressures
Filter monitoring
Local indication of clean room pressures with process signal sent to control room
DESCRIPTION
The SERIES 605 Magnehelic® Indicating Transmitter provides for both visual monitoring and electronic control of very low differential pressure. The Series 605 is ideal for control applications in building HVAC systems where local indication is desired during routine maintenance checks or necessary when trouble shooting the system. The easily read dial gage is complimented by the two-wire, 4 to 20 mA control signal utilizing the time-proven Dwyer® Magnehelic® gage mechanical design and Series 600 transmitter technology. The
two-wire design with terminal strip on the rear simplies connection in any 4 to 20 mA control
loop powered by a 10 to 35 VDC supply.
GAGE SPECIFICATIONS
®
gage and simplies eld upgrade to 605 indicating transmitter
Service Air and non-combustible, compatible gases.
Wetted Materials Consult factory.
Accuracy See ordering page.
Stability ±1% FS/yr.
Pressure Limits See ordering page.
Temperature Limits 20 to 120°F (-6.67 to 48.9°C).
Process Connections 1/8˝ female NPT.
4˝ (101.6 mm) dial face, 5˝ (127 mm) OD x 2-11/16˝ (68.3 mm). For -SS Bezel 4-3/4˝ OD (120.7 mm) x
Size
2-21/32˝ (67.5 mm).
Weight 1 lb, 12.6 oz (811 g).
Agency Approvals CE.
Note: Shown with optional -SS bezel.
Backward compatible with Magnehelic®
Gage.
TRANSMITTER SPECIFICATIONS
Accuracy See ordering page (includes linearity, hysteresis, and repeatability).
Temperature Limits 20 to 120°F (-6.67 to 48.9°C).
Compensated Temperature Range 32 to 120°F (0 to 48.9°C).
Thermal Effect ±0.025% FS/°F (0.045% FS/°C).
Power Requirements 10 to 35 VDC (2-wire).
Output Signal 4 to 20 mA.
Zero and Span Adjustments Protected potentiometers.
Loop Resistance DC: 0 to 1250 Ω maximum.
Current Consumption DC: 38 mA maximum.
Electrical Connections Screw terminal block.
Mounting Orientation Diaphragm in vertical position. Consult factory for other position orientations.
DWYER INSTRUMENTS, INC.
®
DIMENSIONS WIRING DIAGRAM
(3) #6-32 x 3/16 [4.76] DP
(4) 6-32 HOLES
RING
TRANSMITTER
EQUALLY SPACED ON
2
[50.80]
2-1/16
A 5-1/8 [130.18] B.C.
[52.39]
FOR FLUSH MOUNTING
Ø4-47/64
[ 120.25]
Ø5
[127.00]
5/8 [15.88]
PANEL MAX
3/16
[4.76]
Ø4 [101.60]
FACE
5-1/2 [139.70]
O.D. MOUNTING
SERIES 605 PRESSURE
NOTE: RECEIVER MAY BE IN
SERIES WITH + OR -
LEG OF CONTROL LOOP
RECEIVER (RL)
SEE FIG. C
[25.40]
HOLES EQUALLY
SPACED ON A
Ø4-1/8 [104.78] B.C.
FOR PANEL MOUNTING
1
30°
1-1/8
[28.58]
11/16
[17.46]
23/32
[18.26]
1/8 FEMALE
NPT HIGH
PRESSURE
CONNECTION
1-3/4
[44.45]
1/2 [12.70]
1/8 FEMALE NPT
LOW PRESSURE
CONNECTION
1-1/4
[31.75]
2-1/2
[63.50]
HOW TO ORDER
Use the bold characters from the chart below to construct a product code.
-X -X605
SERIES
605 - Differential pressure indicating transmitter
POWER SUPPLY
10.0-35 VDC
OPTIONS
VARIANT 1
00N – 0.05 to 0 to 0.20 in w.c. 0 - 0.05 to 0.50 in w.c. 1 - 0.05 to 1.0 in w.c. 2 – 0.05 to 2.0 in w.c. 3 - 0.05 to 3.0 in w.c.
6 - 0.05 to 6.0 in w.c.
10 - 0.05 to 10.0 in w.c. 11 - 0.25 to 0 to 0.25 in w.c. 12 - 0 to ±60 Pa
20 - 0.05 to 20.0 in w.c. 30 - 0.05 to 30.0 in w.c.
50 - 0.05 to 50.0 in w.c. 60PA - 0 to 60 Pa 125PA - 0 to 125 Pa 250PA - 0 to 250 Pa 500PA - 0 to 500 Pa
1KPA - 0 to 1kPa
1.5KPA - 0 to 1.5kPa
AT - Aluminum tag G - Green scale overlay HC - Horizontal calibration (90 deg face up) M - Mirror scale overlay NIST - NIST traceable calibration certicate R - Red scale overlay SS - Brushed 304 stainless steel bezel ST - Stainless steel tag TA - Tilt angle from vertical in degrees (-90 to 90) WP - Weather proof enclosure Y - Yellow scale overlay
ACCESSORIES
Model Description A-298 A-370
Flat aluminum bracket for ush mounting Photohelic Flush mount bracket used with: Photohelic® 3000MR/MRS, Capsuhelic®, 631B transmitter, EDA. Bracket is then surface mounted. Steel with gray hammertone epoxy nish
A-320-B
Enclosure for 3000MR/MRS Photohelic® switch/gage, 605 Magnehelic® DP transmitter, DH3 Digihelic® pressure controller, 2000 Magnehelic® gage with medium and high pressure options, 4-13/16˝ (122.24 mm)
A-489
Important Notice: Dwyer Instruments, Inc. reserves the right to make changes to or discontinue any product or service identied in this publication without notice. Dwyer advises its customers to obtain the
latest version of the relevant information to verify, before placing any orders, that the information being relied upon is current.
4˝ 303 SS straight static pressure tip with ange
®
& Capsuhelic® gages, 603A, 605, and 3000MR
DWYER INSTRUMENTS, INC.
DS-605 rev. 1 | 12/17