Dwyer Instruments SERIES 2500 Catalog Page

Series
2500
Temperature/Controller
1/4 DIN Fully Programmable, Self-TunePID
The Love Series 2500 Temperature Control provides an im-
pressive array of features in an economical 1/4 DIN package.
tures include on-off, time proportioning, proportional, PI, PD, or full
Temperature
PID control, programmable from the front panel, or use Self-Tune
PID. Input types are selectable from a variety of thermocouple types (J,
K, T, E, N or L) or DIN, NIST or Ni RTD’s. Outputs include solid state
isolated 4-20 mA proportional current. Programmable alarm can act as
high or low or high/low guardband alarm.
A water and corrosion resistant front panel (NEMA 4X; IP 65), input
fault timer, digital input filter, Self-Tune ramp to setpoint, four pass-
word protected security levels and °F or °C display selection are all
standard. Entire electronics package is field replaceable without wiring
changes thanks to removable front panel.
MODELS
MODEL NO.
25111 25112 25113 25115 25125
ALARM
Yes Yes Yes Yes Yes
INPUT
Thermocouple Thermocouple Thermocouple Thermocouple
RTD
OUTPUT*
SSR
5 VDC
Relay 4-20 mA 4-20 mA
Fea-
3-25/32
[95.9]
3-19/32
[91.3]
4-9/16 [115.8]
MAXIMUM PANEL THICKNESS
Panel cutout 3.622˝ x 3.622˝ (92 x 92 mm). Depth Behind Mounting Surface: 4˝ (103 mm).
1/4
[6.53]
17/32 [13.5]
3-25/32
[95.9]
SPECIFICATIONS
Inputs: Thermocouple or RTD. Input Impedance: Thermocouple = 3 megohms minimum, RTD current =
200 µA maximum. Display: Two-4 digit, 7 segment, 0.56" high LED. Resolution: 1 degree or
0.1 degree.
Accuracy: ±0.25% of span, ±1 degree. Supply Voltage: 100-240 VAC nominal, ±10%, 50-400 Hz, single phase;
132-240 VDC nominal, ±10%.
Power Consumption: 5 VA maximum. Operating Temperature: 14 to 131°F (-10 to 55°C). Memory Backup: Non-volatile memory. No batteries required. Control Output Ratings:
SSR: 2.5A @ 240 VAC resistive at 77°F (25°C). De-rates to 1.25A
@ 130°F (55°C).
Relay: SPDT, 10 A @ 240 VAC resistive. Switched Voltage (non-isolated): 5 VDC @ 20 mA. Proportional Isolated Current: 0-20 mA, selectable, into 600
Ohms maximum.
Control Action: Selectable for reverse (usually heating) or direct (usually
cooling).
Ramp: One ramp time adjustable from 0-100 hours. Isolation: Relay and SSR outputs; 1500 VAC. 0-20 mA output; 500 VAC.
5 VDC output is not isolated.
Weight: 13 oz (369 g). Front Panel Rating: NEMA 4X (IP65).
*When ordering a control to operate contactor or solenoid loads greater than 100 mA, select the SSR output instead of the Relay. If the Relay is selected, also order P/N A-600 R/C Snubber.