SERIES 1900
COMPACT LOW DIFFERENTIAL PRESSURE SWITCHES
Set Points from 0.07 to 20 in w.c. Repetitive Accuracy within 3%
PRESSURE
41/64
[16.27]
Series 1910 switch with conduit enclosure off.
Shows electric switch and set point adjustment screw located
E
O
D
I
V
O
N
L
Our most popular Series 1900 Compact Low Differential Pressure Switches
combine advanced design and precision construction to make these switches able
to perform many of the tasks of larger, costlier units. Designed for air conditioning
service, they also serve many uidics, refrigeration, oven and dryer applications.
Series 1900 switches have set points from 0.07 to 20 in w.c. (1.8 to 508 mm). Set point
adjustment is easy with range screw located inside conduit enclosure. Internal location
helps prevent tampering. UL, CE and CSA listed, and FM approved. For use with air
or compatible gages.
FEATURES/BENEFITS
• Compact size and repeatability, provides a high-value switch for many industrial and
OEM applications
• Wide range of models from 0.07 in w.c. to 20 in w.c. can meet exacting OEM
specications for a low pressure switch
• Range screw protected inside enclosure provides simplies making adjustments but
prevents tampering
APPLICATIONS
• Air conditioning refrigeration coil icing detection; defrost cycle initiation
• Clogged lter detection
• Variable air volume controller
MODEL CHART
Model
1910-00
1910-0
1910-1
1910-5
1910-10
1910-20
ACCESSORIES
Model Description
A-399
A-329
A-302F-A
A-489
on same side for easy installation.
I
N
Operating Range
in w.c.
0.07 to 0.15
0.15 to 0.5
0.40 to 1.6
1.40 to 5.5
3.0 to 11.75
4.0 to 20.0
Duct pressure monitor kit; for use with standard or manual reset
model switches; includes mounting ange, tubing and adapters
Street ell; brass adapter for applications requiring right angle
connections; two required for differential pressures
303 SS static pressure tip with mounting ange; for 3/16˝ ID
rubber or plastic tubing; 4˝ insertion depth; includes mounting
screws
4˝ straight static pressure tip with ange
Approximate Deadband
At Min.
Set Point
0.04
0.10
0.15
0.30
0.40
0.40
At Max.
Set Point
0.04
0.10
0.16
0.30
0.40
0.50
1-19/32
[40.48]
diaphragm movement and results in a switch with excellent sensitivity and repeatability.
HIGH PRESS. CONNECTION
2-11/32
[59.53]
The Dwyer-engineered force-motion amplier increases the leverage of
1-3/4 [44.45]
CLEARANCE
FOR COVER REMOVAL
SPECIFICATIONS
Service: Air and non-combustible,
compatible gases.
Wetted Materials: Consult factory.
Temperature Limits: -30 to 180°F (-34
to 82.2°C).
Pressure Limits: 45 in w.c. (11.2 kPa)
continuous, 10 psig (68.95 kPa) surge.
Switch Type: Single-pole double-throw
(SPDT).
Repeatability: ±3%.
Electrical Rating: 15 A @ 120-480 VAC,
60 Hz. Resistive 1/8 HP @125 VAC, 1/4
HP @ 250 VAC, 60 Hz. Derate to 10 A
for operation at high cycle rates.
OPTIONS
Weatherproof Housing
16 ga. steel enclosure with gasketed cover (NEMA 4, IP66) for wet or oily
conditions. Withstands 200 hour salt spray test. Wt. 5-1/2 Ib (2.5 kg). Switch must
be factory installed.
Note: To order, change 1910 base number to 1911, add -WP sufx.
Example: 1911-1-WP
Explosion-Proof Housing
Cast iron base with brass cover. Rated Class I, Groups D; Class II, Div. 2, Groups
E, F, G; Class III and NEMA 7, 9 NEMA 3. (7 lb). Switch must be factory installed.
Note: To order, change 1910 base number to 1911, add -EXPL sufx.
Example: 1911-1-EXPL
Manual Reset Option (Model 1900 MR)
Includes special snap switch which latches on pressure increase above the
setpoint. Switch must be manually reset after pressure drops below the setpoint.
Available on -1, -5,-10 or -20 ranges only. Option is not UL, CSA or FM listed. For
use only in single positive pressure applications.
Note: To order, change 1910 base number to 1900, add -MR sufx.
Example: 1900-10-MR
Manual reset option
USA: California Proposition 65
WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
1/8 FEMALE NPT
3
[76.20]
1-5/16
[33.32]
TYP
Ø3-1/2
[88.90]
Ø7/8 [22.23]
CONDUIT
CONNECTION
51/64
[20.24]
Electrical Connections: 3 screw type,
common, normally open and normally
closed.
Process Connections: 1/8˝ female NPT.
Mounting Orientation: Diaphragm in
vertical position. Consult factory for other
position orientations.
Set Point Adjustment: Screw type
inside conduit enclosure.
Weight: 1 lb 4.5 oz (581 g).
Agency Approvals: CE, CSA, FM,
and UL. Optional-EXPL explosion-proof
enclosure does not possess any agency
approvals.
Process Tubing Options: See page 455 (Gage Tubing Accessories)
1-7/8
[47.63]
2-9/32
[57.94]
2-7/16
[61.90]
60° TYP
(2) Ø3/16 [4.76]
MOUNTING HOLES
ON A 4-3/16 [106.36] B.C.
1/8 FEMALE NPT
LOW PRESSURE
CONNECTION
DWYER INSTRUMENTS, INC. |
Differential Pressure Switches
49