Dwyer Instruments MTL7706 Operating Manual

Instruction Manual
INM7700
MTL7700 Series Shunt-diode safety barriers
ii
INM7700-6 Jan 2010
1 OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2.2 MTL7700 Series – barrier ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2.3 MTL7700 Series – accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
3 SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3.1 General requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3.2 Safety checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
4 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
4.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
4.2 Mounting/removing barriers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
4.3 Installing accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
5 WIRING CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5.2 Barrier connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5.3 Connections to plant earth . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5.4 Connections to dummy barriers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
6 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
6.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
6.2 Routine inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
7.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
7.2 Power supply check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
7.3 Barrier resistance test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
8 EQUIPMENT AND BARRIER TESTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
8.1 Thermocouple and RTD tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
8.2 Barrier tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
8.3 Tests for Active Barriers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
8.4 Test tables for passive barriers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
APPENDIX A: TYPICAL WIRING CONNECTIONS FOR SPECIFIC APPLICATIONS. . . . . . . . . . . . . . . . . . . 17
CONTENTS PAGE
© 2010 MTL Instruments Group plc. All rights reserved.
INM7700-6 Jan 2010
iii
INM7700-6 Jan 2010
iv
1
INM7700-6 Jan 2010
MTL7700 Series Shunt-diode safety barriers
INM7700-6
Jan 2010
Figure 1: MTL7700 Series shunt-diode safety barriers
1 OVERVIEW
This instruction manual contains all information needed to install, maintain, fault-find and test MTL7700 Series shunt-diode safety barriers.
Section 3 includes a checklist of essential safety factors that must be considered when using MTL7700 Series barriers as intrinsically safe (IS) interfaces between safe and hazardous areas.
Read section
3 before beginning installation
. Users within the European
Community should also refer to the supplied MTL publication:
INA7700 MTL7700 Series
Instructions for Safe Use
It is assumed that all necessary system design, specification and engineering factors have been taken into account BEFORE installation work begins. To assist pre-planning, the following MTL publications covering the theory, design, application, specifications and certification of shunt-diode safety barriers are available:
AN9003 Application Note:
A user’s guide to
intrinsic safety
AN9007 Application Note:
A user’s guide to MTL700 Series shunt-diode safety barriers
MTL IS catalogue The MTL IS catalogue includes detailed
specifications of all MTL7700 Series barriers and accessories
IS certificates Copies of Baseefa, FM and CSA IS
apparatus and system certificates for MTL7700 Series barriers
If not supplied with the product, these publications are available either from the company website (
www.mtl-inst.com
) or on request
from your local MTL office.
2 DESCRIPTION
2.1 Introduction
MTL7700 Series ‘fourth-generation’ intrinsically safe shunt-diode safety barriers are innovative successors to the MTL700 Series.
MTL7700 Series barriers are 1-, 2- or 3-channel devices that use intrinsically safe explosion-protection techniques to pass electrical signals between safe and hazardous areas, whilst limiting transferred energy to a level that cannot ignite flammable atmospheres.
Connected in series with wiring entering any hazardous area on process plant, MTL7700 Series barriers prevent explosions in all normally occurring explosive atmospheres – including mixtures of air with flammable gases, vapours, dusts and fibres – if a fault or faults develop in the safe area.
2.2 MTL7700 Series – barrier ranges
The range is based on a choice of models which, between them, cover virtually all applications – including the protection of installations incorporating uncertified devices known as ‘simple apparatus’ (eg, switches, thermocouples, resistive sensors, photocells and LEDs) or separately certified ‘energy-storing’ or ‘voltage­producing apparatus’ (eg, ac sensors, proximity detectors, transmitters and current-to pneumatic (I/P) converters. Being intrinsically safe, shunt-diode barriers enable maintenance work or calibration to be carried out ‘live’ without additional precautions. To simplify selection, several ‘key’ barriers (see table 1) are highlighted as meeting the majority of process control requirements.
2
INM7700-6 Jan 2010
2.3 MTL7700 Series – accessories
MTL7700 Series barriers mount directly onto DIN-rail. A comprehensive selection of mounting, tagging, power and earthing accessories is available. Installation details are given in section 4.3.
Essential accessories
The following are usually considered essential for mounting and earthing MTL7700 Series barriers:
DIN-rail (eg, THR2 or THR7000) Insulating spacers (eg, ISP7000) Earth terminal (eg, ETL7000)
The tagging systems for individual modules and columns of barriers are described here. They are shown below under Tagging accessories for columns of barriers.
Mounting accessories (figure 2)
THR2 Standard DIN-rail, 35 x 7.5mm, (in 1m lengths) THR7000 Nickel-plated DIN-rail, 35 x 7.5mm, for use in
potentially corrosive atmospheres (in 1m lengths)
ISP7000 Insulating spacer: attaches to the base of a DIN-
rail to isolate the IS earth from a structural earth
Tagging accessories for individual barriers (figure 2)
TH7700 Tag holder for mounting on the top of an
individual barrier
Tagging accessories for columns of barriers (figure 2)
TAG57 Tagging strips for mounting over a column of
barriers, for marking barrier locations. Supplied (with labels) in 1m lengths for cutting to size.
TGL7700 Spare labels for use with TAG57 tagging strips:
0.5m strips, supplied in sets of 10.
IMB57 Tagging strip supports. Two needed for each
tagging strip. It can also be used as centre support by breaking off the top end tab.
Power accessories (figure 3)
BPL7700 Power link for feeding 24V dc to a maximum of
40 barriers in a single column from an MTL7798 power feed module or MTL7799 Dummy module.
Earthing accessories (figure 3)
ETL7000 Earth terminal providing connections for
routeing the IS earth from the DIN-rail to an appropriate plant earth. Two recommended for each length of DIN-rail.
TAG57
TGL7700
ERB57O
IMB57
ETL7000
ISP7000
TH7700
Figure 2: MTL7700 Series mounting and tagging accessories
Table 1: MTL7700 Series Key barriers
Type Application Key barriers
MTL
Analogue Resistance temperature detectors 7755ac
input Thermocouples, ac sensors 7756ac
(low-level) 7760ac
Analogue Controller outputs, one line earthed 7728+
output Controller outputs, neither line earthed 7787+
dc power supply
26V 20-35V
Analogue Transmitters, 2-wire, 4–20mA 7787+ 7706
input
(high-level)
Digital Switches 7787+ 7707+
(on/off) 7741-44
input
Digital Solenoids, alarms, LEDs 7728+ 7707+
(on/off)
output
3
INM7700-6 Jan 2010
ERB57O
IMB57
ETL7000
ERL7
ETM7
ISP7000
THR2/THR7000
Figure 3: MTL7700 Series earthing accessories
Note: Module earth terminals may be used for cable
screen earth connections. See Figure 17
ERB57S Nickel-plated straight earth-rail bracket,
supplied with two push fasteners, one 14mm earth-rail clamp and one 9mm earth clamp < 16mm2.
ERB57O Nickel-plated offset earth-rail bracket, supplied
with two push fasteners, one 14mm earth-rail clamp and one 9mm earth clamp < 16mm
2
.
ERL7 Nickel-plated 3 x 10mm earth rail supplied in
1m lengths. Provides earthing facilities for cable screens and 0V earth returns, additional to those provided on the module earth foot.
ETM7 Earth terminal (5mm wide) for attachment to an
ERL7 earth rail, for terminating cable screens and spare cable cores.
3 SAFETY CONSIDERATIONS
3.1 General requirements
All installers of shunt-diode barriers should be familiar with the installation instructions provided by nationally accepted codes of practice, eg, BS EN 60079-14 for the UK, or a recommended practice, eg, ANSI/ISA-RP 12.6 for the USA.
Users within the European Community should also refer to the supplied MTL publication:
INA7700 MTL7700 Series
Instructions for Safe Use
3.2 Safety checks
Table 2 itemises the essential checks that should be carried out to ensure the safety of a barrier installation. Use the checklist to prevent important safety considerations being overlooked when installing, commissioning, modifying or servicing an installation of MTL7700 Series barriers. Check the list both before and after a barrier system has been installed, the final check being made by someone other than the person(s) who carried out the installation work. Each item in the list is cross-referenced to the appropriate section of the manual.
For Factory Mutual (FM) based installations see also Appendix B for FM certification information.
4 INSTALLATION
4.1 General
MTL7700 Series barriers clamp directly onto standard T-section DIN­rail (DIN EN 50 022). The simple mounting procedure for barriers is described in section 4.2 and for accessories in section 4.3.
4.1.1 DIN-rail length
BEFORE mounting the barriers, make sure the rail length is sufficient for the proposed number of barriers and for other mounting accessories. As a guide, on a given length of DIN-rail, allow space (length) for:
a) Barrier packing pitch: 12.6mm b) ETL7000 earth terminals: 10mm each (minimum
of two)
c) IMB57 tagging strip support 16.0mm (minimum of
(if specified) two)
d) ISP7000 insulating spacer 14.7mm (minimum of
(if specified) two)*
e) ERB57S or O earth-rail 8 mm (minimum of two)
mounting bracket (if specified)
* See Note in section 4.3.2
Make sure that there is sufficient clearance between the DIN-rail and any possible obstruction (eg, other columns of barriers) to remove barriers and install accessories such as ERB57S/O earth rails.
Provide sufficient height for IMB57 tagging strip supports and ISP7000 insulating spacers when fitted.
As a guide, refer to figure 4 (dimensions of an individual barrier) and figure 5 (clearances needed for accessories).
4.2 Mounting/removing barriers
MTL7700 Series barriers clamp directly onto T-section DIN-rail, earthing the barrier through the rail.
a) Hook the hazardous-area end of the mounting/earthing clamp
over the hazardous-area flange of the DIN-rail (figure 6).
b) Push the safe-area end of the barrier firmly down by hand until
it clicks into place.
c) Check that the barrier is securely clamped into place (see notes
below).
d) To remove a barrier (figure 7), use the tip of a screwdriver (with
a blade width of 4 to 5mm, minimum shaft length 60mm) to ease the metal clip at the base on the safe-area end outwards until the barrier is freed and can be removed easily by unhooking the hazardous-area end.
Notes
1: Make sure the barrier is properly clamped onto the rail to ensure the essential earth connection. In a row of barriers, one end of an improperly mounted barrier will stick up slightly.
2: Once an MTL7700 Series barrier is fitted, its mounting/earthing foot grips the DIN-rail strongly in order to maintain positional stability and create a high-integrity earth bond. The unit should not be forced along the rail. If it is necessary to reposition a barrier, detach it from the DIN-rail and re-attach it in the correct location. Where minor repositioning is needed, relieve the pressure on the spring of the mounting foot with a screwdriver and ease the unit into place.
4.3 Installing accessories
See section 2.3, figure 2 and figure 3 for brief details of the accessories available for use with MTL7700 Series barriers. More information and installation details (where relevant) for the various accessories are detailed in the following sections:
4
INM7700-6 Jan 2010
90
Hazardous­area terminals
Safe-area terminals
12.6
105
Installation and approval side label
Product top label
Colour-coded top label
Top label background colour codes
Red = positive barrier Black = negative barrier Grey = ac barrier White = dummy barrier Orange = power feed module
Figure 4: Dimensions (mm) of an MTL7700 Series barrier
Mounting accessories Section 4.3.1 to 4.3.
Earthing accessories Section 4.3.3, 4.3.4
Tagging accessories Section 4.3.5, 4.3.6
Power links Section 4.3.7, 4.3.8
4.3.1 DIN-rail (THR2 and THR7000)
MTL can supply both standard (THR2) and plated (THR7000) low­profile T-section DIN-rail. Although standard DIN-rail maintains a high-integrity earth in normal conditions, for aggressive environments MTL provides THR7000 nickel-plated DIN-rail. Both types are supplied in 1m lengths for cutting to size as necessary. Although there is no strict requirement for the DIN-rail to be isolated from earthed surfaces, it is advisable, in order to minimise the possibility of the earth circuit being invaded by fault currents which might interact adversely with other systems. ISP7000 insulating spacers are a convenient method of insulating the DIN-rail. It is much easier to install insulating spacers during the initial build, than to discover later that an equipped and running installation must be modified.
4.3.2 Insulating spacers (ISP7000)
When used, ISP7000 insulating spacers are attached to each end of the DIN-rail and at intervals depending upon the length of the rail. It is recommended that spacers be mounted at 300mm intervals on low­profile (7.5mm) DIN-rail and at 500mm intervals on high-profile (15mm) rails – see figure 8. The spacers are provided with suitable screws for attaching to both the DIN-rail and the mounting surface, which will need to be suitably drilled and tapped for the purpose. Install each spacer as follows (figure 9):
a) On the mounting surface, drill and tap two holes for M4 screws. b) Attach the spacer to the surface with the two M4 x 16 screws
provided.
c) Drill an M6 clearance hole (6.5mm) in the centre of the base of
the DIN-rail (if not already suitably slotted)
d) Attach the DIN-rail to the spacer with the M6 x 16 screw
provided.
Table 2: Safety checklist
Item Refer to no. section: Action
1 3.1 Before beginning installation, check that the
safety documentation confirms that the proposed system is fully certified (if applicable) and complies with the recommendations contained in the relevant sections of IEC 60079-14 for the gas group, temperature classification and area classification required.
2 4.1/6.2 Make sure the barriers are of the correct type
and polarity as specified in the safety documentation.
3 4.1 Make sure all barriers are mounted the right
way round and are properly attached so that the essential earth contact is made securely in accordance with the safety documentation and in compliance with the recommendations of IEC 60079-14.
4 5.3/6.2 Measure the resistance between the barrier
earth DIN-rail and the main power system earth and make sure it does not exceed the maximum permitted resistance specified in the safety documentation.
5 4.1/6.2 Inspect carefully all cables connected between
the barriers and the hazardous-area equipment, making sure the cables are the type specified by the safety documentation and that they are connected to the correct terminals.
6 5/6.2 Make sure all hazardous-area cables are well
secured and are segregated from all other cables.
7 5 Make sure the permitted cable parameters for
hazardous-area circuits are not exceeded (see relevant certificate or INA7700).
8 5 Make sure all hazardous-area apparatus and
cables are either earth-free or correctly bonded with an equipotential conductor.
9 5.3/6.2 Make sure all hazardous-area cables and cable
screens are terminated correctly, the latter preferably via earth foot on the hazardous side of each barrier or via ERL7.
10 5.4 Make sure all unused hazardous-area cables
are terminated by a dummy barrier (MTL7799), earth rail (ERL7) or otherwise safely connected to earth.
11 Make sure all hazardous-area energy-storing
devices are independently and appropriately certified.
12 4.1/ Inspect all tagging or identification labels and
4.3.5/ make sure they relate to the correct barrier
4.3.6 types, polarities and circuit loop numbers.
13 5/6.2 Inspect carefully all cables connected to the
safe-area equipment and make sure they are connected to the safe-area terminals of the barriers.
14 5.3 Make sure that no safe-area equipment is
supplied from (or includes) a source of potential with respect to earth that exceeds 250V rms or 250V dc under normal or fault conditions unless specifically permitted by the safety documentation.
Note: One phase of a 3-phase supply of up to 440V is permitted as its value is equivalent to 250V rms.
15 Make sure all barriers are protected adequately
against moisture, dust, dirt, vibration, excessive temperatures, physical damage and unauthorised modifications.
5
INM7700-6 Jan 2010
TAG57
TGL7700
ERB57O
IMB57
ETL7000
ISP7000
110mm
110mm
170mm
Figure 5: Clearance for accessories
Note: For high profile (15mm) DIN rail, add 7.5mm to vertical dimension
1
2
3
1
2
Figure 6: Clamping an MTL7700 Series barrier on to a DIN-rail
Figure 7: Removing an MTL7700 Series barrier from a DIN-rail
250mm
Low-profile rail (7.5mm)
High-profile rail (15mm)
250mm
500mm
Figure 8: Maximum DIN-rail spans between ISP7000 spacers
4.3.3 DIN-rail earth terminal (ETL7000)
See figure 10. For those applications (the majority) in which the IS earth is NOT routed through the mounting surface, connections for routing the IS earth from the DIN-rail to an appropriate plant earth are made through earth terminals (ETL7000) clamped onto the DIN­rail. Two terminals are recommended, one at either end of a column of barriers, to provide redundancy and to simplify earth testing procedures.
WARNING: Apart from rare occasions when the mounting surface carries the IS earth, the ONLY method of providing the IS earth connection from any one column of MTL7700 Series barriers is from ETL7000 earth terminals. Never make the plant IS earth connection to the earth screen on any individual barrier: this is MANDATORY. See also section 5.3.
ETL7000 terminals are attached to the rail as follows. Ensure the same security of the earth connection to the rail as for the barriers themselves (see section 4.2):
a) Hook the fixed end-clamp of the terminal over one flange of the
DIN-rail.
b) Press the body of the terminal downwards until the pivoting end-
clamp engages the other flange of the DIN-rail.
c) Clamp the terminal firmly into place by tightening the centre
screw.
d) Important: wire up the earth terminal as given in section 5.3.2.
6
INM7700-6 Jan 2010
High - profile
DIN rail
OR
Low - profile
DIN rail
2 off M4 x 16
M6 X 16
50mm
62mm
14.6mm
20mm
Figure 9: Mounting ISP7000 insulating spacers
ETL7000 earth terminal
Clamping screw
Earth terminal screws
Figure 10: Mounting an ETL7000 DIN-rail earth terminal
TH7700
LABEL
Figure 11: Installing a TH7700 barrier tag holder
4.3.4 Earth rail assembly (ERL7/ETM7/ERB57S/O)
A screw terminals on each barrier is available for terminating cable screens and 0V returns. An alternative is provided by an earth rail assembly (figure 12). This consists of two IMB57’s, ERB57S or O, mounting blocks (one for each end of a column of barriers), a length of ERL7 earth rail (supplied in 1m lengths for cutting to size), and ETM7 terminals for connecting cable screens or 0V returns to the rail.
Install the earth rail assembly as follows:
a) Hook the loose end-clamps of the IMB57 mounting blocks over
the flanges of the DIN-rail at each end of the row of barriers.
b) Making sure the blocks are flush with the end barriers or tagging
strip supports, clamp them firmly into place by tightening the screws at the base of the blocks and fit 2 off ERB57O or S into supports.
c) Slide the number of ETM7 terminals required for connections
onto the length of ERL7 rail needed for the assembly.
d) Important: wire up the earth rail assembly as given in section
5.3.3.
4.3.5 Barrier identifiers (TH7700)
TH7700 tag holders (figure 11) are clipped onto the tops ofindividual barriers to provide transparent holders for identification labels
a) Slide the required label in between the top and lower parts of
the TH7700 b) Push the tag holder downwards until it clips into place. c) To unclip a tag holder, lever up the far end above terminals.
4.3.6 Tagging strip assemblies(IMB57)
The tagging strip assembly (figure 12) identifies the location of individual barriers, ensuring that they are replaced correctly after removal for maintenance or testing. Once installed, the tagging strip pivots upwards to provide access to, and allow removal of, individual barriers.
Each assembly uses two tagging strip supports (IMB57), a tagging strip (TAG57) and tag labels (TGL7700).
The assembly installation procedure is:
a)IMB57 tagging strip support. Making sure that the vertical
slots are on the hazardous-area side, hook the loose end-clamps of each IMB57 tagging strip support over the flanges of the DIN­rail at each end of the group of barriers.
b) Make sure that the tagging strip support is flush with the end
barrier in the row. IMB57 tagging strip support. Clamp firmly in place by
tightening the two screws located at the foot of each support.
c) Remove any clic rivets from the tagging strip and slide out the
label.
d) Measure the distance between the top inside faces of the two
tagging strip supports. e) Cut the tagging strip and label to this length with a hacksaw. f) Annotate the tagging strip label as required and slide it back
into the tagging strip. Divisions on label strips are 12.6mm
wide, the pitch of individual barriers. g) Clip the tagging strip onto the lugs on top of the tagging strip
supports.
4.3.7 Power bus (BPL7700)
For details on using and installing a power bus, see section 5.2.3.
Note: Early versions of TH7700 are hinged on two small locating pins. Later versions are hinged by locating the clips at the hinged end into the rectangular appartures on the barrier body. The later design can be retrofitted on early modules by removing the hinge pins with a knife.
TGL7700
ERB57O
TAG57
ERL7
ETM7
14mm earth-rail clamp
THR2/THR7000
ERB57S
in lower position
ISP7000
ETL7000
10mm earth clamp
IMB57
Snap off extension when using IMB57 as a central support
Figure 12: Mounting earthing and tagging accessories
7
INM7700-6 Jan 2010
5 WIRING CONNECTIONS
5.1 General
This section describes wiring connections as follows:
a) Barrier connections Section 5.2
b) Connections to plant earth Section 5.3
c) Connections to dummy barriers Section 5.4
5.2 Barrier connections
Each barrier has 4 or 8 terminals, 2 or 4 on each side, allocated as follows:
Safe area
Terminals 1,2,5 and 6 Safe-area power Sections
and signal lines 5.2.1 and
5.2.2
Hazardous area
Terminals 3,4,7 and 8 Hazardous-area Section
signal lines 5.2.1
Torque the screw terminals to 0.4Nm.
5.2.1 Signal line connections
Connect signal lines to the screw terminals at both sides of the barrier (1 and 2 and/or 5 and 6 at the safe-area side, 3 and 4 and/or 7 and 8 at the hazardous-area side). The safe-area terminal 1 is also used as a power connection when power is provided from the safe area (see section 5.2.2 for details).
Clearly segregate hazardous-area and safe-area cabling as defined by relevant codes of practice, and route cabling to the barriers through clearly separated and identified conduits or trunking. Deal with spare cable cores or screens as described in section 5.2.3.
Before making any signal connections from the hazardous area, make sure any energy-storing devices (ie, devices NOT classified as ‘simple apparatus’) are certified as being compatible with the barriers to which they will be connected. Check also that the connecting cables conform with the cable types specified by the safety documentation and that the maximum cable parameters specified in MTL’s IS catalogue are not exceeded. In general, cable parameters are unlikely to present problems except in installations where cables longer than 500m are called for in IIC applications.
Do not connect barriers to safe-area equipment that is supplied from (or contains) a source of potential with respect to earth that is greater than 250V rms or 250V dc under normal or fault conditions, unless this is specifically permitted by the safety documentation. This limitation does not apply to safe-area equipment fed by a three-phase 440V neutral earth supply.
See Appendix A for examples of wiring connections for specific applications.
5.2.2. Power supply connections general considerations
Take care that if barriers are connected to a safe-area power supply, connections are made correctly. If the internal safety fuse blows, it will destroy MTL7700 barriers. See Appendix A for specific connections for individual barriers and applications.
5.2.3 Bussed Power applications and connections
When a number of barriers use a common power supply, the optional power link (BPL7700) can be used. Typical applications include hazardous-area switches, solenoids and 4–20mA transmitters; and the barriers it can be used with are the MTL7706, MTL7707+, MTL7787+, MTL7787P+ and MTL774x. See figure 14 for a typical power link installation applied to hazardous-area switches.
Up to 40 barriers can be linked using the power links. The link itself is supplied from a power feed module (MTL7798). The MTL7798 power feed module is provided with a trip circuit which protects the barriers by switching off their supply if a fault (such as an overvoltage) occurs in the power source. The state of the module is indicated by one of two LED indicators:
a) Green ON when supply is normal and being passed
to the barriers.
b) Red ON when the trip mechanism is activated
indicating a fault.
After a fault has been indicated, the module can be reset by disconnecting the main power supply.
Install the power links as follows (figure 13):
a) Mount an MTL7798 power feed module on the DIN-rail at one
end of the column of barriers being supplied.
b) Connect a safe-area 20–26V dc supply to terminals 5 and 6 of
the power feed module.
c) select the number of links required.
d) Lift the tag holders to gain access to the power link connectors
and insert the links (figure 13).
e) Close the tag holders.
f) To replace the barrier, lift the identifiers either side of the
appropriate barrier to check which one is linked, remove the
link, replace the barrier and re-insert the link and close the
identifiers.
WARNING
Do not remove bussed power links with power applied if installed in FM Div 2
5.2.4 Spare cores/screens/0V returns: connections
Unused cores should be connected to 0V. Terminals on the earth foot simplify this.
5.3 Connections to plant earth
5.3.1 General considerations
A barrier installation must be earthed properly for correct and safe operation. Care must be taken that individual barriers are correctly mounted so that the earth connection with the DIN-rail is secure.
An installation must, in turn, be connected to a suitable plant high­integrity earth. This should be done by connecting suitable conductors to ETL7000 earth terminals (see section 5.3.2). It is also usually advisable to make sure that the DIN-rail is isolated from any possible enclosure earths by separating it from the mounting surface with ISP7000 isolating spacers (see section 4.3.2).
BPL7700 power link
Figure 13: Power link insallation
8
INM7700-6 Jan 2010
5.3.2 Earthing an installation
See figure 15. Connections from the DIN-rail to a suitable plant earth are made from ETL7000 earth terminals. These clip onto the DIN-rail as described in section 4.3.3 to make the vital earth connection with the rail and the barriers. They are provided with two screw-clamp terminals, to one of which a copper conductor to plant earth should be connected. This should have a resistance no greater than 1Ω though to increase safety and reduce interference, a resistance as close to 0.1Ω as possible is preferable. The cross-sectional area of the conductor should be as least 4mm
2
(12 AWG).
It is advisable to mount one ETL7000 earth terminal at each end of a column of barriers to provide redundancy by connecting both ETL7000 terminals to the plant earth. This makes it possible to introduce a multimeter into one of the loops to measure loop resistance without breaking the earth connection (figure 16) – a test which should be done periodically. In these circumstances, resistance for each cable loop should not exceed 2Ω.
The IS plant earth conductors should be clearly identified to warn against unauthorised interference. Though not mandatory, it is recommended that this should be done by winding blue insulating tape round the conductors at intervals along their length.
WARNING
Do not use earth foot terminal as an IS earth termination. Make IS earth connections using an ETL7000 earth terminal as described in section 5.3.2.
5.3.3 Earthing an earth rail assembly
On installations which include earth rail assemblies (see section
4.3.4) an earth conductor, normally copper wire with a cross­sectional area of at least 4mm
2
(12AWG) must be connected between ETM7 earth terminals located at each end of the rail and the ‘spare’ terminals on the ETL7000 terminals at each end of the column of barriers. See figure 17.
5.3.4 Hazardous-area equipment isolation
Hazardous-area equipment and interconnections should be isolated from earth sufficiently to be capable of withstanding a 500V isolation test. Such tests can, however, only be undertaken when the area is gas free so it is fortunate that most circuits can be tested at low voltages. To do this:
a) Disconnect from the barrier any cable connected directly to earth
or returned through a barrier with a nominal voltage of less than 10V.
b) Check the resistance to earth of the safe-area terminals with a
multimeter; it should be greater than 100kΩ.
Note: some hazardous-area equipment (eg, pH and conductivity instrumentation) is unable to withstand this insulation test. As an alternative, in these circumstances the system can comply with the installation requirements described in IS sketch 121. See also
12.2.4.in BS EN 60079-14.
3
4
1
2
MTL7787+
MTL7787P+
Logic signal
1
5
MTL7798
(MTL7799)
3
4
1
2
MTL7706+ MTL7787+
MTL7787P+
250Ω
3 4
1 2
MTL7741
5
6
7 8
6
0V
0V
1-5V
}
Contact signals
Power Bus
PB7700
Loop power to opposite ends to allow module removal
Power Connections
Hazardous Area
Safe Area
Figure 14: Typical application of the Power Bus
ETL7000 earth terminal
To IS earth
Figure 15: Plant earth connection to ETL7000 earth terminal
ETL7000 earth terminal
Loop resistance <2Ω
Local distribution transformer
Resistance meter or bond integrity monitor
Figure 16: Earthing an installation with two conductors and providing resistance test facilities
9
INM7700-6 Jan 2010
5.3.5 Bonding practice when hazardous-area equipment cannot meet prescribed insulation standards
Where hazardous-area equipment is connected to earth (either directly or indirectly) and/or it will not withstand a 500V insulation test to ground or the alternative described in section 5.3.4, eg, strain­gauge bridges with low-voltage insulation, pH and conductivity sensors, bare and/or earthed thermocouples, and some level detectors, the following considerations apply:
Safety considerations
a) The pipe, vessel, or body of the hazardous-area apparatus
and/or the adjacent metallic structure must be connected to the barrier DIN-rail (see item d) by a bonding conductor of at least 4mm2cross-sectional area for lengths of 100m or less; or at least 8mm2area for lengths between 100m and 200m.
b) Where bonding conductors are used, care must be taken to
avoid invading other intrinsically safe systems (those not using bonding conductors) by elevation arising from currents which may flow in the common earthing systems as a result of the presence of the bonding conductor. Where this possibility cannot be avoided, then barriers associated with bonded systems should be mounted on a separate DIN-rail from those on which other barriers are mounted. Additionally, the DIN-rails themselves should also be earthed separately.
c) The hazardous-area equipment and/or adjacent metallic
structure bond connections must be secured against vibration and corrosion. A terminal of the type used on ‘increased safety’ (‘e’) equipment is the mandatory solution.
d) The barrier DIN-rail connections must provide suitable
termination facilities for the bonding conductor and usual ‘earth return’ by being equipped with separate increased safety (‘e’) terminals.
Operational requirements
e) Figure 18 shows the 0V rail of the safe-area equipment returned
to the barrier DIN-rail by a separate insulated conductor and the structural earths of any safe-area equipment returned separately to the neutral star-point. This reduces interference problems but is not essential for safety reasons.
f) In general, the use of barriers in all measurement leads reduces
the possibility of earth circulating currents causing measurement problems.
g) Resistance from the neutral star point to ‘terrestrial earth’ – via
the buried earth mat or rods – is determined by other regulations and is not modified or determined by the intrinsic safety requirements, which are concerned with the plant earth only.
5.4 Connections to dummy barriers
See figure 19. The MTL7799 dummy barriers provide safe connection facilities for unused cable cores, cable screens and 0V returns. In addition, safe-area terminals 2 and 1 are connected internally to provide a straight ‘feedthrough’ 24V dc supply connection, enabling the units to be used as feed modules for use with a power bus, useful in applications where the fault trip mechanism of the MTL7798 is not needed.
6 MAINTENANCE
6.1 General
Circuits in all MTL7700 Series barriers are encapsulated and so cannot be repaired. However, provided they are correctly installed and connected (as described in sections 4 and 5 of this manual) and the circuits they protect are not themselves defective, barrier faults are highly unlikely to occur. Therefore, servicing of barrier installations consists mainly of routine inspection and earth testing as described in this section.
More information about the maintenance of barrier installations is given in BS EN 60079 -17.
6.2 Routine inspection
At intervals not exceeding two years (more frequently for harsh environments), make a visual check of the barrier installation. Personnel undertaking these checks should comply with all regulations relating to the safety of plant and personnel. Care must be taken to prevent any inadvertent direct connection between hazardous- and safe-area circuits and, at all times, the safety precautions discussed in section 3 MUST be observed.
TAG57
TGL7700
ERB57O
IMB57
ETL7000
ISP7000
ERL
(optional earth rail)
Cable screens using earth rail
Cable screens using module terminals
ETM7
Figure 17: Earthing and screening using module earth terminals or earth rail alternative
10
INM7700-6 Jan 2010
Check that:
a) Barriers are of the types and polarities specified in the safety
documentation.
b) The barriers are attached securely and correctly to the DIN-rail
to make sure the earth connection is safe.
c) There are no apparent signs of damage or corrosion to the
barriers, the ETL7000 earth terminals, the plant earth connections, and, if fitted, any earth rail assemblies.
d) All hazardous-area and safe-area cable connections are made
correctly and the terminals properly tightened.
e) Interconnecting cables are of the type and rating specified by
the safety documentation and that they are not frayed or otherwise damaged.
f) All earth returns and cable screens from the hazardous area are
connected to earth either through a barrier, a dummy barrier or an earth rail.
g) Visually examine the earth conductors and make sure they are
not damaged in any way and that their terminations are secure and free from corrosion.
h) Using a low-voltage low-current test meter (ie, a meter with an
output not exceeding 3V and 50mA), measure the resistance between the DIN-rail and the neutral star-point of the supply and make sure it does not exceed 1Ω. Record the reading and compare it with readings taken during previous inspections. A consistent reading repeated over a long period of time is a reassuring sign indicating a sound earth return which is likely to remain so. If two earth conductors are used as described in section 5.3.2, the loop resistance should be measured as described in that section and the reading should not be greater than 2Ω.
WARNING: do not try to carry out a high-current earth resistance test unless it is confirmed by the authority in charge of the plant that the plant is gas-free.
7 FAULT-FINDING
7.1 Introduction
Most barrier-protected systems are relatively simple and their operation is easy to check. However, when fault finding is necessary, it must only be undertaken after checking with plant personnel responsible for safety that it is safe to proceed.
The fault-finding procedures described in this section call for the use of a digital multimeter – this being the most common type used. However, other types can be used provided their characteristics when measuring silicon diodes are known.
Many digital multimeters include a diode test function which is useful when diode chains are included in the test. These usually operate by passing 1mA through the diode and measuring the voltage across it. When measuring more than two diode drops in series, note that the full-scale range of some multimeters is only 2V on the diode test range. With three or more diode drops it is therefore possible that the meter may indicate over-range. In the test tables (tables 4 to 10), section 8, any drop of more than 4V is indicated as infinity (∞).
Zener diodes and ordinary silicon diodes have a typical forward voltage drop of approximately 0.6V/diode. Diode return paths with Schottky diodes have a typical voltage drop of <0.3V for each diode in the chain, eg, MTL7787+, 7787P+.
Figure 20 depicts a typical switch-status transfer circuit protected by an MTL7787+ barrier which illustrates some of the fault-finding techniques discussed in this section. To determine the serviceability of MTL7700 Series barriers, follow the steps described in sections
7.2 to 7.3.
Hazardous-area equipment incapable of withstanding insulation test
Safe-area equipment
0V
Local distribution transformer
1Ω maximum
Safe area
Hazardous area (Zone 2) or safe area
Hazardous area Zone 0, 1 or 2
Bonding conductor <100m: 4mm
2
minimum
100 200m (maximum): 8mm
2
minimum
Enclosure
DIN-rail
Barriers
Figure 18: Bonding practice where hazardous-area equipment cannot meet required standards of insulation from earth
1
2
3
4
MTL7799
Unused cable
cores and
screens
24Vdc
Bussed power
Figure 19: MTL7799 dummy barrier connections
11
INM7700-6 Jan 2010
7.2 Power supply check
Check that the power supply to an individual barrier circuit (or to an MTL7798 power feed module or an MTL7799 dummy barrier sourcing the power bus ) is functional and that the voltage across the supply with respect to earth is correct. For example, in Figure 20 the presence of 24V on terminal 1 and 12V on terminal 2 when the switch in the hazardous area is closed confirms the serviceability of almost the complete circuit.
7.3 Barrier resistance test
To test the resistance of a barrier on site, refer to figure 20 and carry out the following procedure:
a) Unplug hazardous-area cables from terminals 3 and 4.
b) Unplug safe-area cables from terminals 1 and 2.
WARNING: Take care when handling safe-area cables; the relay contacts in figure 20 for example could be carrying mains voltage.
c) Measure the end-to-end resistance of the barrier by connecting a
digital multimeter (set to a suitable Ω range) between terminals 1 and 3. The reading should typically be slightly less (eg 1–3% lower) than the maximum end-to-end resistance listed in tables 4 to 10 for the appropriate barrier type or approximately 10–20% higher than the figure specified in the safety description.
d) Check the functioning of the diode-return channel (MTL7787+,
7787P+, only) by selecting the diode test function on the multimeter and connecting it between terminals 4 (+ve) and 2 (–ve). This measures the forward voltage drop of the Schottky diodes in the chain: the reading should be less than 0.9V. Repeat the test with the connections reversed (ie, terminals 4 (–ve) and 2 (+ve) for an expected reading of for the reverse voltage drop.
e) Tests c) and d) confirm the continuity of both barrier channels. If
either channel is open-circuit it is most likely that the fuse has blown. The safe-area circuit should be investigated in an attempt to discover the cause of the fault.
Note: if the barrier is removed, make sure the safe-area and hazardous-area cables disconnected during operations a) and b) are connected to an earth-rail, a dummy barrier or insulated completely.
c) If it is not possible to disconnect wiring to the barrier for steps a)
and b), carry out the tests given in table 4.
8 EQUIPMENT AND BARRIER TESTS
8.1 Thermocouple and RTD tests
8.1.1 Thermocouple circuit testing
Thermocouple test and calibration equipment is rarely certified intrinsically safe and therefore requires special authorisation before it can be used for testing or calibrating thermocouple circuits in hazardous areas. To overcome this problem, the thermocouple circuits can be protected by using an MTL7760ac barrier as shown in figure 21. This permits the thermocouple output to be measured without needing special authorisation to use uncertified thermocouple test equipment.
As it is seldom possible to measure accurately the temperatures of thermocouples located in hazardous areas, a safe way of adjusting calibration tables to compensate for plant temperatures is needed. This can be done by disconnecting the compensating cables from the thermocouple, shorting them together, and measuring the temperature of the shorting point.
8.1.2 Resistance temperature detector (RTD) circuit testing
Resistance temperature detector (RTD) circuits can be tested by disconnecting the measuring leads from the RTD head in the hazardous area and connecting them to a resistance box. Sometimes it is more convenient to connect the resistance box in the safe area, for instance at point ‘xx’ in figure 22. For the latter method, however, the RTD must be shorted out or an allowance made for its temperature. The effect of a negative temperature change can be simulated by connecting the resistance box into the measurement lead at point ‘yy’. The advantage of connecting the resistance box at the RTD head is that any leakage can also be determined by connecting the resistance box at point ‘yy’.
8.2 Barrier tests
8.2.1 General
MTL7700 Series barriers do not need to be subjected to routine testing if they are in normal use. Generally, the inspection tests described in section 6 are more than adequate. However, if the performance of barriers is in any way suspect, then carry out the detailed tests described in this section. Barriers which pass these tests satisfactorily are highly unlikely to represent an unacceptable level of risk or cause a circuit malfunction.
There are two types of test (as shown by tables 4 to 10); a simple test using a digital multimeter to test barriers on site and a more comprehensive bench test using a constant current source to establish the breakdown characteristics.
Although certification requirements concentrate on pulse-current tests, in many ways the leakage current tests described in this section are a more satisfactory method of testing suspect diodes. If a complete functional check of a barrier is needed, then the multimeter and constant current tests described in sections 8.2.2 and 8.2.3 should be made although, for most purposes, the multimeter tests should suffice.
1
2
3
4
370Ω
+24Vdc
12V
0V
400Ω 12V relay
Plant earth via DIN-rail
30mA
MTL7787+
Figure 20: Switch-status transfer circuit using an MTL7787 barrier
1
2
3
4
1
2
3
4
Compensating cables
Safe-area equipment
Calibration equipment
MTL7760ac
Figure 21: Calibrating a thermocouple barrier circuit
12
INM7700-6 Jan 2010
8.2.2 Multimeter tests
See tables 4 to 10. The use of a digital multimeter for testing barriers is described in section 7. The tables assume that the multimeter is set to a suitable Ω range for the end-to-end resistance tests (except for diode return channels) and for the continuity tests; and that the multimeter diode test function is used for the diode tests, channel isolation tests and for the end-to-end resistance tests for diode return channels.
8.2.3 Constant-current tests
For these tests (last column of tables 4 to 10) a constant-current generator capable of supplying 10µA, 20mA and 40mA currents from a 30V source is needed. Ideally, a purpose-built current generator should be used but, alternatively, a set-up based on a laboratory power supply and two multimeters (figure 23) will serve. The current is measured by one multimeter and trimmed by adjusting the output voltage of the power supply indicated on the second multimeter.
When using a constant-current generator for testing MTL7700 Series barriers, note the following points:
a) The current must be limited to 50mA to avoid damaging the
barriers. b) The accuracy of the current is not critical and can vary by ±5%. c) Test leads must be connected securely to the barrier terminals;
however, the changeover switch and current selector reduce the
need for connection changes. d) Using a high resistance in series with the barrier gives more
stable results and makes it easier to set the required current.
8.3 Tests for Active Barriers
8.3.1 Tests for the MTL7706+
Comprehensive testing requires specialised equipment, beyond the scope of on-site tests. However, an effective test which will confirm that the unit is operating correctly is shown in figure 24. Ammeter 1 measures the transmitter simulator current of between 4 and 20mA flowing from terminal 4 and the safe-area load current flowing to terminal 4 simultaneously. Since these two currents are equal and opposite, the resulting reading on the ammeter should be virtually zero. Ammeter 2 verifies the presence of the 4–20mA transmitter signal.
1
2
3
4
5
7
Bridge supply
Measurement
Safe-area
equipment
MTL7756ac
Variable
resistance
Measurement
Variable
resistance
yy x
x
Figure 22: Calibrating an RTD barrier circuit
To barrier on test
Digital multimter (current)
Digital multimter (voltage)
current selector
current limited
to 30mA
2-channel laboratory power supply
0 - 30V variable
0 - 30V variable
+ -
+ -
Changeover
switch
40mA
20mA
10mA
3MW
1.5kW
750W
Figure 23: Constant-current test circuit using a power supply and digital multimeters
1
2
3
4
A1
A2
Transmitter simulator
4-20mA
250W
+20 to 35Vdc
MTL7706+
+
+
_
_
Figure 24: MTL7706+ test circuit
8.3.2 Tests for the MTL7707+
Since this unit incorporates a built-in protection circuit, it has to be tested in a different manner to an ordinary shunt-diode barrier. Referring to figure 25, set the transmitter simulator to 4mA and to 20mA, and check that the ammeter reads approximately the same value. Then, having set the simulator to 20mA, check that the voltage between terminals 1 and 3 is less than 8.5V and between terminals 2 and 4 is less than 1.6V.
Figure 25: MTL7707+ test circuit
1
2
3
4
A
MTL7707+
Transmitter simulator
4-20mA
+20 to 35Vdc
250W
+
_
13
INM7700-6 Jan 2010
Input Output Line Fault
Open circuit Open Closed Short circuit Closed Closed 620Ω Closed Open 10KΩ Open Open
8.3.3.2 Testing MTL7742 Barriers
The MTL7742 is a single channel switch/prox input barrier with an open collector solid state interface to the safe area equipment. To verify correct operation proceed as follows:
a) Connect the barrier as shown in figure 27. b) Check that the LED is on when the input switch is closed, and off
when the input switch is open.
8.3.3.3 Testing MTL7743 Barriers
The MTL7743 is a dual channel switch/prox input barrier, each channel with a relay interface to the safe area equipment. To verify correct operation proceed as follows:
a) Connect the barrier as shown in figure 28. b) With an ohmeter, check that the output contacts (terminal 1 & 2)
close when the input switch for channel 1 is closed.
c) Repeat the procedure for channel 2.
8.3.3.4 Testing MTL7744 Barriers
A dual channel version of the MTL7742, this module provides two solid state interfaces for prox/switch inputs. To verify correct operation proceed as follows:
a) Connect the barrier as shown in figure 29. b) Connect power via the power bus c) Check that the LED is on when the input switch is closed for
channel 1, and off when the input switch is open for channel 1.
d) Repeat the procedure for channel 2.
8.3.3.5 Testing MTL7745 Barriers
This module is a single channel interface for prox/switch inputs with line fault detection. To verify correct operation proceed as follows:
a) Connect the barrier as shown in figure 30. b) With an ohmeter, check the status of the output contacts
according to Table 3
3 4
1
2
MTL7742
5 6
7 8
Bussed Power
24V
Vs+
Vs-
}
2KΩ
Figure 27: Test circuit for MTL7742
3
4
1 2
MTL7745
5 6
620W10kW
24V
Bussed Power
Line Fault
Output
Vs+
Vs
Figure 30: Test circuit for MTL7745
Table 3 Test conditions for MTL7745
3 4
1 2
MTL7743
5 6
7
8
Bussed Power
24V
Vs+
Vs
Channel 1
Channel 2
Channel 1
Channel 2
Figure 28: Test circuit for MTL7743
3 4
1 2
MTL7744
5 6
7 8
Bussed Power
24V
Vs+
Vs-
2KW
2KW
Channel 1
Channel 2
Channel
1
Channel
2
Figure 29: Test circuit for MTL7744
8.3.3 Tests for MTL774x
The MTL774x range are switch/prox input barriers with a choice of changeover relay contacts or a solid state switch acting as the safe area interface. Relay contacts provide a universal interface capable of switching a wide range of signals including ac, low level and high level voltages. Phase reversal is achieved by connecting the normally open or normally closed contacts as required. The solid state switch variants can be configured to switch from a power rail or down to ground and makes these barriers ideal for high switching frequency applications.
When testing bus powered barriers use either an MTL7798 Power Feed module or an MTL7799 dummy barrier for direct ‘feed-through’ connection of a 24V dc supply.
8.3.3.1 Testing MTL7741 Barriers
The MTL7741 is a single channel switch/prox input barrier with changeover relay contacts acting as the safe area interface. To verify correct operation proceed as follows:
a) Connect the barrier as shown in figure 26. b) With an ohmeter, check that the output contacts (terminal 5 & 6)
close when the input switch is closed.
3
4
1 2
MTL7741
5 6
7 8
Bussed Power
24V
Vs+
Vs
Output
Figure 26: Test circuit for MTL7741
14
INM7700-6 Jan 2010
BARRIER DATA MULTIMETER TESTS CONSTANT-CURRENT TESTS
MTL Safety End-to-end Diode Diode Terminal Terminal
model Description Resistance Test Test Voltage Voltage
No.
ΩΩ
+ve -ve @ 10μμA @ 20mA
V
ΩΩ
mA Min Max Min Max Min Max
7710+ 10 50 200 62 75 Vf
z
x 1 6 9.5 6.6 9.7
7715+ 15 100 150 110 119 Vf
z
x 1 12 13.6 12.4 13.7
7715P+ 15 50 291 59 64 Vf
z
x 1 12.6 13.3 13 13.4
7722+ 22 150 147 159 174 Vf
z
x 2 19.6 20.9 19.7 21.1
7728+ 28 300 93 311 333 Vf
z
x 2 25.9 26.5 26 26.7
7728- 28 300 93 311 333 Vf
z
x 2 25.9 26.5 26 26.7
7728P+ 28 237 119 241 252 Vf
z
x 3 24.9 25.5 25 25.6
7729P+ 28 164 170 171 184 Vf
z
x 3 24.9 25.5 25 25.6
8.4 Test tables for passive barriers
Tables 4 to 10 detail the tests for all MTL7700 Series ‘passive’ barriers. In the ‘diode test’ columns, the figures adjacent to the diode description indicate the number of forward-biased diodes used in the barrier chain. Using the multimeter diode test function and knowing the diode voltage drop figures (approximately 0.6V for each Zener diode and 0.3V for each Schottky diode), the expected reading across the diode chain can be determined.
BARRIER DATA MULTIMETER TESTS CONSTANT-CURRENT TESTS
MTL Safety End-to-end Diode Diode Terminal Terminal
model Description Resistance Test Test Voltage Voltage
No.
ΩΩ
+ve -ve @ 10μμA @ 20mA
V
ΩΩ
mA Min Max Min Max Min Max
7758+ 7.5 10 750 14 17 Vf
z
x 1 6 6.9 6.6 7
7758- 7.5 10 750 14 17 Vf
z
x 1 6 6.9 6.6 7
7764+ 12 1k 12 1010 1050 Vf
z
x 1 10 11.4 10.5 11.6
7767+ 15 100 150 110 119 Vf
z
x 1 12 13.6 12.4 13.7
7779+ 28 300 93 311 333 Vf
z
x 2 25.9 26.3 26 26.5
7796+ 26 300 87 311 333 Vf
z
x 2 23.9 24.4 24 24.6
7796+ (ch2) 20 390 51 401 428 Vf
z
x 2 18.3 18.8 18.4 19
7796- 26 300 87 311 333 Vf
z
x 2 23.9 24.4 24 24.6
7796- (ch2) 20 390 51 401 428 Vf
z
x 2 18.3 18.8 18.4 19
7788+ 28 300 93 311 333 Vf
z
x 2 25.9 26.4 26 26.6
7788+ (ch2) 10 50 200 62 75 Vf
z
x 1 6 9.5 6.6 9.7
7788R+ 28 300 93 311 333 Vf
z
x 2 25.9 26.4 26 26.6
7788R+ (ch2) 10 50 200 62 75 V
r
V
r
0 0 6.2 6.8
Table 4: Single channel polarised barriers
Table 5: Dual channel polarised barriers
Note: Vfzis the voltage dropped by a forward biased zener diode - 0.6V typically
V
r
is the voltage dropped by the sense and current limit resistors - 3.2V for a typical 1mA test current
15
INM7700-6 Jan 2010
Table 6: Single channel
BARRIER DATA MULTIMETER TESTS CONSTANT-CURRENT TESTS
MTL Safety End-to-end Diode Diode Terminal Terminal
model Description Resistance Test Test Voltage Voltage
No.
ΩΩ
+ve -ve @ 10μμA @ 20mA
V
ΩΩ
mA Min Max Min Max Min Max
7728ac 28 300 93 311 333 ∞∞25 26.7 25.6 27.2
BARRIER DATA MULTIMETER TESTS CONSTANT-CURRENT TESTS
MTL Safety End-to-end Diode Diode Terminal Terminal
model Description Resistance Test Test Voltage Voltage
No.
ΩΩ
+ve -ve @ 10μμA @ 20mA
V
ΩΩ
mA Min Max Min Max Min Max
7761ac 9 90 100 98 107 ∞∞6 8.6 6.9 8.9 7761Pac 9 350 26 361 378 ∞∞6.8 8.6 7.7 8.9 7764ac 12 1k 12 1010 1050 ∞∞10 11.6 10.8 11.9 7766ac 12 150 80 159 174 ∞∞10 11.6 10.8 11.9 7766Pac 12 75 157 84 92 ∞∞9.6 10.9 10.4 11.2
Table 7: Dual-channel ac barriers
BARRIER DATA MULTIMETER TESTS CONSTANT-CURRENT TESTS
MTL Safety End-to-end Diode Diode Terminal Terminal
model Description Resistance Test Test Voltage Voltage
No.
ΩΩ
+ve -ve @ 10μμA @ 20mA
V
ΩΩ
mA Min Max Min Max Min Max
7760ac 10 50 200 62 75 ∞∞6 9.5 6.9 9.8 7765ac 15 100 150 112 124 ∞∞12 14.1 12.7 14.4 7778ac 28 600 47 614 651 ∞∞24.0 24.4 25.4 26.0
Table 9: Dual-channel star-connected ac barriers
BARRIER DATA MULTIMETER TESTS CONSTANT-CURRENT TESTS
MTL Safety End-to-end Diode Diode Terminal Terminal
model Description Resistance Test Test Voltage Voltage
No.
ΩΩ
+ve -ve @ 10μμA @ 20mA
V
ΩΩ
mA Min Max Min Max Min Max
7755ac 3 10 300 15 19 Vf
d
x 3 Vfdx 3 1 2.1 1.8 2.4
7756ac 3 10 300 15 19 Vf
d
x 2 Vfdx 2 0.7 1.4 1.2 1.6
Table 8: 2/3 channel low voltage ac barriers
Note: Vfdis the voltage dropped by a forward biased rectifier diode - 0.6V typically
16
INM7700-6 Jan 2010
BARRIER DATA MULTIMETER TESTS CONSTANT-CURRENT TESTS
MTL Safety End-to-end Diode Diode Terminal Terminal
model Description Resistance Test Test Voltage Voltage
No.
ΩΩ
+ve -ve @ 10μμA @ 20mA
V
ΩΩ
mA Min Max Min Max Min Max
7787+ 28 300 93 311 333 Vf
z
x 2 26.6 27.4 26.7 27.6
7787+ (ch2) 28 (+)
0.9V + 26 Vf
z
x 2 26.6 27.4 26.7 27.6
7787P+ 28 237 119 241 253 Vf
z
x 3 26.4 27.4 26.5 27.6
7787P+ (ch2) 28 (+)
0.9V + 26 Vf
z
x 2 26.6 27.4 26.7 27.6
7789+ 38 300 93 614 651 Vf
z
x 2 26.6 27.4 26.7 27.6
7789+ (ch2) 28 — — (+)
0.9V + 26 Vf
z
x 2 26.6 27.4 26.7 27.6
Table 10: Diode return barriers
Note: Vfzis the voltage dropped by a forward biased zener diode - 0.6V typically
17
INM7700-6 Jan 2010
APPENDIX A: TYPICAL WIRING CONNECTIONS
FOR SPECIFIC APPLICATIONS.
Hazardous Area
Safe Area
3
4
1
2
250W4 -20mA
Power +26V
Signal
Power Bus
1-5V
MTL7706+ MTL7787+ MTL7787P+ MTL7788+
Hazardous Area
Safe Area
3
4
1
2
MTL7788R+
250Ω
1-5V
Power +26V
Power Bus
Figure A1: 2-wire transmitters
Hazardous Area
Safe Area
3 4
1
2
MTL7789+
7 8
5
6
Power +26.6V
Power +26.6V Logic signal
Logic signal
Power Bus
Figure A5: 2-channel switch inputs
Hazardous Area
Safe Area
3
4
1
2
MTL7756ac
Receiver
7
5
3
4
1
2
MTL7755ac
Receiver
Figure A6: Low-level analogue inputs (RTD’s)
Figure A2: 2-wire transmitters with 250Ω conditioning
Hazardous Area
Safe Area
3
4
1
2
MTL7760ac MTL7765ac MTL7778ac
Recorder Controller Data logger Computer
Compensating cable
Figure A3: Thermocouple/mV input
Hazardous Area
Safe Area
3 4
1 2
MTL7743 MTL7744
7 8
5 6
Logic signal
Logic signal
Power
Figure A7: 2-channel switch/proximity input
Hazardous Area
Safe Area
3 4
1
2
MTL7742
5
6
Logic signal
Logic signal
Power Bus
+20V - 35V
0V
Figure A8: Single channel switch/proximity input
Hazardous Area
Safe Area
3
4
1
2
MTL7787+
MTL7787P+
Power +26.6V
Signal
Power Bus
Figure A4: 2-wire transmitter/switch input
18
INM7700-6 Jan 2010
Hazardous Area
Safe Area
3
4
1
2
MTL7728+
0V
+26V
P
I
Figure A9: Analogue output
Hazardous Area
Safe Area
3
4
1
2
+7V
3
4
1
2
MTL7761ac
MTL7764ac
3
4
1
2
MTL7761ac
--7V
0V
Output (mV)
Sense
+
Figure A13: Strain-gauge bridges
Hazardous Area
Safe Area
3 4
1
2
MTL7745
5 6
620Ω
10kΩ
+22.9 - 30V
LFD
COM
CH 1
Power Bus
Figure A10: Single channel switch/proximity input with Line
Fault Detect
Hazardous Area
Safe Area
3 4
1
2
MTL7789+
7 8
5
6
Power +26V
Power +26V
Power Bus
Figure A11: Low power digital outputs
Hazardous Area
Safe Area
3 4
1
2
MTL7741
5
6
7 8
NO
COM
Power Bus
22.9V - 30V
NC
Figure A12: Single channel switch/proximity input with cutout
relay
MTL Instruments Pty Limited
9 /12 Billabong Street Stafford Queensland 4053 Australia Tel: + 61 1300 308 374 Fax: + 61 1300 308 463 E-mail: enquiries@mtlaus.com.au
MTL Canada Safety Instrumentation
#102, 4249 97 Street Edmonton, Alberta Canada T6E 5Y7 Tel: +1 780 485 3132 Fax: +1 780 485 3122 E-mail: cinfo@mtlnh.com
MTL Instruments China Co. Ltd.
Room 1002A, The Gateway No 10 Yabao Road, Chaoyang District Beijing 100020 China Tel: +86 010 8562 5718/5720/5721 Fax: +86 010 8562 5725 E-mail: bjsales@mtl-inst.cn
MTL Instruments sarl
Les Carrés du Parc 10 rue des Rosiéristes 69410 Champagne au Mont d’Or France Tel: +33 (0)4 78 64 98 32 Fax: +33 (0)4 78 35 79 41 E-mail: info@mtl-inst.fr
MTL Instruments GmbH
An der Gümpgesbrücke 17 D-41564 Kaarst Germany Tel: +49 (0)2131 718930 Fax: +49 (0)2131 7189333 E-mail: info@mtl.de
MTL India
No. 36, Nehru Street Off Old Mahabalipuram Road Sholinganallur Chennai - 600 119 India Tel: + 91 (0)44 24501660/24501857 Fax: + 91 (0)44 24501463 E-mail: sales@mtlindia.com
MTL Italia srl
Via Cantù 11 I - 20092 Cinisello Balsamo MI Italy Tel: +39 (0)2 61802011 Fax: +39 (0)2 61294560 E-mail: info@mtl-inst.it
MTL Instruments KK
MT Building 3F 2-7-5 Shiba Daimon Minato-ku Tokyo Japan 105-0012 Tel: +81 (0)3 6430 3128 Fax: +81 (0)3 6430 3129 E-mail: sales@mtlkk.co.jp
MTL Instruments BV
MTL Instruments BV Terheijdenseweg 465 4825BK Breda The Netherlands Tel: +31(0)76 7505360 Fax: +31(0)76 7505370 E-mail: info@mtlbenelux.com
Cooper Crouse-Hinds Pte Ltd
No.2 Serangoon North Avenue 5 #06-01 Fu Yu Building Singapore 554911 Tel: +65 6 487 7887 Fax: +65 6 487 7997 E-mail: sales@mtlsing.com.sg
MTL Instruments
Villa No. 4, Sector 2-17, Street 6 PO Box 53234, Abu Dhabi, UAE Tel: +971 2 446 6840 Fax: +971 2 446 6841 E-mail: mtlgulf@mtl-inst.com
Measurement Technology Limited
Great Marlings, Butterfield, Luton, Beds England LU2 8DL Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283 E-mail: enquiry@mtl-inst.com
MTL Incorporated
3413 N. Sam Houston Parkway W. Suite 210 Houston TX 77086 USA Tel: +1 281 571 8065 Fax: +1 281 571 8069 E-mail: csinfo@mtl-inst.com
Group Internet home page http://www.mtl-inst.com/
Members of The MTL Instruments Group
Loading...