Series MTL5541 Galvanic Barrier
Specications - Installation and Operating Instructions
41/64 [16.27]
Bulletin PC-MTL5541
4-11/32
[110.33]
The Series MTL5541 Galvanic Barrier provides a fully-oating dc supply for energizing
a conventional 2 or 3-wire 4/20mA transmitter, which is located in a hazardous area,
and repeats the current in another oating circuit to drive a safe-area load. For HART
2-wire transmitters, the unit allows bi-directional communication signals superimposed
on the 4/20mA loop current. Separately powered current sources, such as 4-wirw
transmitters, can be connected but will not support HART communication.
FEATURES/BENEFITS
• Designed to mount on most standard DIN rails
• Approved for use in hazardous areas
APPLICATIONS
• Electrically isolates pressure and level transmitters from unregulated circuits for
intrinsically safe applications.
Mounting and Wiring
MTL5541 MTL5541S
4-20 mA
Com
Tx+
Input
I
I
20 TO 35 VDC
4-20 mA
VsVs+
Load
Load
HAZARDOUS
REA TERMINAL
SPECIFICATIONS
Hazardous Area Input: Signal range: 0 to 24 mA (including over-range);
Transmitter voltage: 16.5 V at 20 mA.
Safe Area Output: Signal range: 4 to 20 mA; Under/over-range: 0 to 24 mA; Load
resistance: 0 to 360Ω @ 24 mA, or 0 to 450Ω @ 20 mA; Current sink: 600Ω max.;
Maximum Voltage Source: 24 VDC; Output resistance: > 1 MΩ.
Power Requirement: 20 to 35 VDC.
Response Time: Settles to within 10% of nal value within 50 µs.
Current Consumption (20 mA signal): 51 mA @ 24V.
Maximum Power Dissipation (20 mA signal): 0.7 W @ 24 VDC, 1.0 W @ 24
VDC.
Isolation: 250 V RMS, tested at 1500 V RMS minimum, between safe- and
hazardous-area terminals; 50 V between safe-area circuits and power supply.
Transfer Accuracy at 68°F (20°C): Better than 15 µA.
LED Indicator: Green: Power Indication.
Temperature Limits: Operating: -6 to 140°F (-20 to 60°C); Storage: -40 to 176°F
(-40 to 80°C).
Temperature Drift: < 0.8µA/°C.
Humidity: 5 to 95% RH.
Mounting: T-section 35mm DIN rail (7.5 or 15mm) to EN 50022.
Terminals: Accommodate up to 2.5 mm2 stranded or single-core.
Safety Description: Vo= 28 V, Io= 93 mA, Po= 651mW, Um= 253 RMS or DC.
Weight: 150 g.
Agency Approvals: FM, UL, ATEX, IECEx, CE.
TERMINAL FUNCTION
1
2
3
10
11
12
13
14
Current Input.
Transmitter Supply +ve.
Common.
Output +ve via 220Ω for HART apps.
Output –ve (+ve current sink).
Output +ve (-ve current sink).
Supply –ve.
Supply +ve.
4-3/32 [103.98]
SAFE ARE
TERMINAL
MAINTENANCE/REPAIR
Upon nal installation of the Series MTL5541, no routine maintenance is required. The
Series MTL5541 is not eld serviceable and is not possible to repair the unit. Field
repair should not be attempted and may void warranty.
WARRANTY/RETURN
Refer to “Terms and Conditions of Sale” in our catalog and on our website. Contact
customer service to receive a Return Goods Authorization number before shipping the
product back for repair. Be sure to include a brief description of the problem plus any
additional application notes.
Printed in U.S.A. 3/18 FR# 444431-00©Copyright 2018 Dwyer Instruments, Inc.
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Phone: 219/879-8000
Fax: 219/872-9057
www.dwyer-inst.com
e-mail: info@dwyermail.com