Dwyer Instruments MTL5541 Operating Manual

Series MTL5541 Galvanic Barrier
A
A
SAFE AREAHAZARDOUS AREA
®
Specications - Installation and Operating Instructions
41/64 [16.27]
Bulletin PC-MTL5541
4-11/32 [110.33]
The Series MTL5541 Galvanic Barrier provides a fully-oating dc supply for energizing a conventional 2 or 3-wire 4/20mA transmitter, which is located in a hazardous area, and repeats the current in another oating circuit to drive a safe-area load. For HART 2-wire transmitters, the unit allows bi-directional communication signals superimposed on the 4/20mA loop current. Separately powered current sources, such as 4-wirw transmitters, can be connected but will not support HART communication.
FEATURES/BENEFITS
• Designed to mount on most standard DIN rails
• Approved for use in hazardous areas
APPLICATIONS
• Electrically isolates pressure and level transmitters from unregulated circuits for intrinsically safe applications.
Mounting and Wiring
MTL5541 MTL5541S
4-20 mA
Com Tx+ Input
I
I
20 TO 35 VDC
4-20 mA
Vs­Vs+
Load
Load
HAZARDOUS
REA TERMINAL
SPECIFICATIONS Hazardous Area Input: Signal range: 0 to 24 mA (including over-range);
Transmitter voltage: 16.5 V at 20 mA. Safe Area Output: Signal range: 4 to 20 mA; Under/over-range: 0 to 24 mA; Load resistance: 0 to 360Ω @ 24 mA, or 0 to 450Ω @ 20 mA; Current sink: 600Ω max.; Maximum Voltage Source: 24 VDC; Output resistance: > 1 MΩ.
Power Requirement: 20 to 35 VDC. Response Time: Settles to within 10% of nal value within 50 µs. Current Consumption (20 mA signal): 51 mA @ 24V. Maximum Power Dissipation (20 mA signal): 0.7 W @ 24 VDC, 1.0 W @ 24
VDC. Isolation: 250 V RMS, tested at 1500 V RMS minimum, between safe- and hazardous-area terminals; 50 V between safe-area circuits and power supply.
Transfer Accuracy at 68°F (20°C): Better than 15 µA. LED Indicator: Green: Power Indication. Temperature Limits: Operating: -6 to 140°F (-20 to 60°C); Storage: -40 to 176°F
(-40 to 80°C).
Temperature Drift: < 0.8µA/°C. Humidity: 5 to 95% RH. Mounting: T-section 35mm DIN rail (7.5 or 15mm) to EN 50022. Terminals: Accommodate up to 2.5 mm2 stranded or single-core. Safety Description: Vo= 28 V, Io= 93 mA, Po= 651mW, Um= 253 RMS or DC. Weight: 150 g. Agency Approvals: FM, UL, ATEX, IECEx, CE.
TERMINAL FUNCTION
1 2 3 10 11 12 13 14
Current Input. Transmitter Supply +ve. Common. Output +ve via 220Ω for HART apps. Output –ve (+ve current sink). Output +ve (-ve current sink). Supply –ve. Supply +ve.
4-3/32 [103.98]
SAFE ARE TERMINAL
MAINTENANCE/REPAIR
Upon nal installation of the Series MTL5541, no routine maintenance is required. The Series MTL5541 is not eld serviceable and is not possible to repair the unit. Field repair should not be attempted and may void warranty.
WARRANTY/RETURN
Refer to “Terms and Conditions of Sale” in our catalog and on our website. Contact customer service to receive a Return Goods Authorization number before shipping the product back for repair. Be sure to include a brief description of the problem plus any additional application notes.
Printed in U.S.A. 3/18 FR# 444431-00©Copyright 2018 Dwyer Instruments, Inc.