Dwyer Instruments MTL5041 Operating Manual

Instruction Manual
INM5000
MTL5000 Series isolating interface units
ii
INM5000-6 Jul 2010
iii
3.1 Installing unenclosed isolators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
4.1 MTL5000 power bus - Installation and use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4.2 Earth rail and tagging accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
5 DX ENCLOSURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5.1 Environmental conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5.2 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.3 Accessories in enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.4 IS warning label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
6 UNIT DESCRIPTIONS, SETTING-UP, CONNECTIONS AND TESTING . . . . . . . . . . . . . . . . . . . . . . . 11
6.1 MTL5011 single-pole relay single-channel switch/proximity detector with phase reversal (Discontinued use MTL5011B) . . . . . . . . . . . . . . . 11
6.2 MTL5011B single-pole changeover relay single-channel switch/proximity detector with line fault detection and phase reversal . . . . . . . . . . . 12
6.3 MTL5012 solid-state single-channel switch/proximity detector with line fault detection and phase reversal . . . . . . . . . . . . . . . . . . . . . . . . 12
6.4 MTL5014 single-pole changeover relay single-channel dual-output switch/proximity detector with line fault detection and phase reversal . . . . 13
6.5 MTL5015 solid-state two-channel switch/proximity detector with line fault detection and phase reversal . . . . . . . . . . . . . . . . . . . . . . . . . . 14
6.6 MTL5016 single-pole relay two-channel switch/proximity detector with phase reversal (Discontinued, use MTL5018) . . . . . . . . . . . . . . . . . 15
6.7 MTL5017 single-pole relay two-channel switch/proximity detector with line fault detection and phase reversal . . . . . . . . . . . . . . . . . . . . . 15
6.8 MTL5018 single-pole, changeover relay, two-channel, switch/proximity detector with line fault detection and phase reversal . . . . . . . . . . . . 16
6.9 MTL5018AC single-pole, changeover relay, two-channel, switch/proximity detector with line fault detection and phase reversal . . . . . . . . . 16
6.10 MTL5021 loop-powered solenoid/alarm driver, IIC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
6.11 MTL5022 loop-powered solenoid/alarm driver, IIB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6.12 MTL5023 solenoid/alarm driver with line fault detection and phase reversal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6.13 MTL5024 solenoid/alarm driver, logic drive with phase reversal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
6.14 MTL5025 low-current loop-powered solenoid/alarm driver, IIC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
6.15 MTL5031 vibration transducer interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
6.16 MTL5032 pulse isolator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6.17 MTL5040 2-channel 4 to 20mA loop isolator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
6.18 MTL5041/42 repeater power supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
6.19 MTL5043 repeater power supply dual output, 4 to 20mA for 2-wire transmitters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
6.20 MTL5044 repeater power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
6.21 MTL5045/46 isolating drivers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
6.22 MTL5048 analogue input/output, loop-powered isolator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
6.23 MTL5049 two-channel isolating driver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
6.24 MTL5051 serial data comms isolator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
6.25 MTL5053 isolator/power supply for 31.25kbit/s fieldbuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
6.26 MTL5061 two-channel loop-powered fire/smoke detector interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
6.27 MTL5074 temperature converters, THC or RTD input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
6.28 MTL5081 millivolt isolator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
6.29 MTL5082 resistance isolator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
6.30 MTL5099 dummy isolator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
6.31 MTL5113P fail-safe switch/proximity detector interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
6.32 MTL5314 trip amplifier for 2– or 3– 2 wire transmitters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
6.33 MTL5344 Repeater power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
6.34 MTL5349 two-channel isolating driver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
6.35 MTL5991 24V dc power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
6.36 MTL5995 fieldbus power supply for 31.25kbit/s fieldbuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
6.37 FBTI-IS fieldbus terminator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
CONTENTS Page
© 2010 MTL Instruments Group plc. All rights reserved.
INM5000-6 Jul 2010
iv
INM5000-6 Jul 2010
7 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
7.1 Routine maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
7.2 Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
8 OTHER USEFUL DOCUMENTATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
9 APPENDIX A - INSTRUCTIONS FOR MTL5500 SERIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
9.1 MTL5521 rotational speed monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
9.2 MTL5531 voltage/current converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
9.3 MTL5536 potentiometer converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
1
INM5000-6 Jul 2010
WARNING
This manual describes the use and installation of safety equipment. This equipment must be installed, operated and maintained only by trained competent personnel and in accordance with all appropriate international, national and local standard codes of practice and site regulations for intrinsically safe apparatus and in accordance with the instructions contained here.
ATEX
If the country of installation is governed by the Essential Health and Safety Requirements (Annex II) of the EU Directive 94/9/EC [the ATEX Directive - safety of apparatus] then MTL document INA5000 must be consulted before installation.
CERTIFICATION DATA
The MTL web site
http://www.mtl-inst.com
contains documentation regarding intrinsic safety certification for many locations around the world. Consult this data for information relevant to your local certifying authority.
REPAIR
These products MUST NOT be repaired. Faulty or damaged products must be replaced with an equivalent certified product.
1 INTRODUCTION
This instruction manual explains how to install, connect, test and maintain MTL5000 Series isolating interface units (isolators).
2 DESCRIPTION
MTL5000 Series isolators provide intrinsically safe (IS) communication and signal conditioning for a wide range of hazardous-area devices. Total ac and dc isolation exists between input, output and power supply on separately powered units, and between input and output on loop­powered units. No IS earth is required. DIN-rail mounting and plug-in signal and power connectors simplify installation and maintenance. Units are powered from a 20 to 35V dc supply, or, in some cases, from the signal itself.
3 INSTALLATION
Mount all MTL5000 Series isolators on low-profile (7mm) or high-profile (15mm) type T35 (top-hat) DIN-rail to EN50022, BS5584, DIN46277. This is available from MTL, in 1 metre lengths (THR2 DIN rail). Install isolators within the safe area unless they are enclosed in approved flameproof, pressurised or purged enclosures and ensure that the local environment is clean and free of dirt and dust. Note the ambient temperature considerations of section 3.1.7.
It is recommended that, in normal practice, the DIN rail is earthed to ensure personnel safety in the event of mains being put accidentally on the rail.
3.1 Installing unenclosed isolators
On new installations, if isolators are mounted in several rows orcolumns, mount alternate rows or columns so that units face in opposite directions. This allows safe- and hazardous-area wiring looms to be shared.
See figure 3.1 for isolator dimensions.
INM5000-6
July 2010
Note: All MTL products are tested for electrical safety to EN 61010 to
comply with the EC Low Voltage Directive
MTL5000 Series Interface units
Figure 1.1: MTL5000 Series isolators
2
INM5000-6 Jul 2010
3.1.1 Mounting isolators on DIN rail
Clip isolators onto type T35 DIN rail as shown in figure 3.2, with the blue signal plugs facing towards the hazardous-area wiring.To remove an isolator from the rail, insert a screwdriver blade into the clip as shown and lever the clip gently outwards; pivot the isolator off the rail. Allow a maximum mounting pitch of 16.2mm for each unit.
3.1.2 Wiring up isolators
Each unit is supplied with the appropriate number and type of safe- and hazardous-area connectors (see figure 3.3), as dicatated by the terminals used and the type of power supply. Loop-powered devices do not require power connectors. Depending on the installation, it may be easier to wire up isolators with power and signal plugs either in place or removed. Either way, allow sufficient free cable to permit plugs to be removed easily for future maintenance and/or replacement purposes. See section 6 for individual unit wiring instructions.
Note: Units for use with 31.25kbit/s fieldbuses may require additional terminators to be fitted. See section 6.33 for details of MTL's FBT1 fieldbus terminator.
Signal and power conductors
Removable signal and power plugs are fitted with screw clamp terminals. Note that the conductors should be between 14 and 24 AWG (1.6 and 0.5mm dia) in size. Signal plugs, located on top of the modules, are mechanically keyed to fit in only one position. They are
coloured grey, for safe-area connections, and blue, for hazardous-area connections.
For externally powered units, a power plug slots into the socket at terminals 13 and 14 on the safe-area side of each module. The socket is coloured blue if the unit is dc powered. Power plugs are coloured grey, for plugging into the blue sockets of dc powered units.
Making connections
a) Trim back the insulation of conductors by 12mm. b) Check the terminal assignments shown in section 6 or on the
side label of the unit.
c) Insert conductors according to the terminal assignments and
tighten screws. If the wires are to be fitted with crimp ferrules, the following is a list of those recommended with required trim lengths for each:
*2- to 3-week lead time
† These ferrules have 18mm length metal tubes which should be cut to 12mm after crimping
Note: Smaller section wire than that stated can often be successfully used if the crimping is good.
Crimp tool: Phoenix Contact Crimpfox UD6 part number 1204436
Finishing
Wire up individual isolators in accordance with wiring schedules. Daisy­chain power supply connections between individual power plugs or use the power bus (see section 4.1).
Segregate hazardous- and safe-area wiring into separate trunking or looms wherever possible to avoid errors and maintain a tidy installation.
Use an MTL5099 dummy isolator to provide termination and earthing for unused cores from the hazardous area.
Hazardous-area connections
Non-hazardous (safe) area connections
Power connectors
104
115
110
16
16.2 pitch
Plug Entry Wire Metal tube Trim Recommended ferrules type size length length
(mm2) (mm) (mm)
Signal Twin 2x1.5 12 14 Cembre PKET 1512 Signal Single 0.75 12 14 Weidmuller 902591 Signal Single 1.0 12 14 Cembre PKC112 Signal Single 1.0 12 14 Phoenix Contact AI 1-12 RD
(3200674)* Signal Single 1.5 12 14 Cembre PKE1518† Signal Single 2.5 12 14 Cembre PKE2518† Power Twin 2x0.75 10 12 Cembre PKET7510 Power Twin 2x0.75 10 12 AMP (non-preferred) 966144-5 Power Twin 2x1.0 10 12 Phoenix Contact AI-TWIN 2X 1-10 RD Power Single 0.75 10 12 AMP 966067-0 Power Single 1.0 10 12 Phoenix Contact AI 1-10 RD
Figure 3.1: Dimensions of MTL5000 Series isolators
Figure 3.2: DIN rail – mounting and removing isolators
12mm
14mm
Power Plugs
Grey: dc supplies (PWR5000)
Signal Plugs
Grey: safe-area side Blue: hazardous-area side
Figure 3.3: Removable power and signal plugs
Consult table below for
additional details.
Note: the open circuit window (between 350µA and 50µA) is not hysteresis, all MTL5000 Series modules with inputs conforming to NAMUR/DIN 19234 will switch between open and complete circuit conditions within these limits.
Note: the short circuit window (between 100
Ω
and 360Ω) is not hysteresis, all MTL5000 Series modules with inputs conforming to NAMUR/DIN 19234 will switch between open and complete circuit conditions within these limits.
Modules with LFD and inputs conforming to NAMUR/DIN 19234:
MTL5011B, 5014* and 5018: LFD enable switch on top label
* The MTL5014 has a Slave/LFD output relay arrangement (see module description in section 6).
MTL5012 and 5015: LFD enable switch on top label
MTL5017: LFD permanently enabled
Other modules with LFD facility
MTL5023 solenoid/alarm driver: LFD automatic
MTL5046 isolating driver: LFD automatic
Note: The safe-area circuit impedance will increase with hazardous­area load and will rise >150kΩ for the 'open circuit' line fault.
MTL5113x: LFD automatic
Hazardous-area load Safe-area input
<50Ω High impedance (>150kΩ) >90Ω Normal operation
Hazardous-area input (either channel) Line-fault-detect relay
<50µA De-energised
>350µA Energised
>360Ω Energised <100Ω De-energised
LFD switch setting Hazardous-area input(s) Solid-state output(s)
On <50µA Non-conducting On >350µA Conducting On >360Ω Conducting On <100Ω Non-conducting
LFD switch setting Hazardous-area input(s) Output relay(s)
On <50µA De-energised On >350µA Energised On >360Ω Energised On <100Ω De-energised
3.1.3 Phase reversal
Switch(es) to change the phase of the output(s) relative to the input(s) are provided on the top labels of some of the MTL5000 Series modules and on the base of others. The following applies:
MTL5011B, 5014 and 5018: Phase reversal switch on top label
MTL5017: Phase reversal switch on base of module
MTL5012 and 5015: Phase reversal switch on top label
MTL5023 and 5024: Phase reversal switch on base of module
Positions for base-located switches are set as shown in figure 3.4.
3.1.4 Line fault detection (LFD)
Line fault detection on hazardous-area sensor lines (open circuit or short circuit) is provided on some MTL5000 Series modules.
Note: resistors must be fitted when using the LFD facility with a contact input: 500Ωto 1kΩin series with switch and 20kΩto 25kΩin parallel with switch.
For hazardous-area inputs conforming to NAMUR/DIN 19234, a line fault condition is indicated as follows:
Open circuit condition if hazardous-area current <50µA Line integrity (no open circuit) if hazardous-area current >350µA Short circuit condition if hazardous-area load <100Ω Line integrity (no short circuit) if hazardous-area load >360Ω
A
B2
1
Normal Reverse
CH1
CH2
Label face
Base of unit
3
INM5000-6 Jul 2010
PR switch setting Hazardous-area input(s) Output relay(s)
Off <1.2mA De-energised Off >2.1mA Energised On <1.2mA Energised On >2.1mA De-energised
PR switch setting Hazardous-area input(s) Solid-state output(s)
Off <1.2mA Non-conducting Off >2.1mA Conducting On <1.2mA Conducting On >2.1mA Non-conducting
Hazardous-area
PR switch setting Safe-area control output
o (off) CTRL+Ve >4.5V above CTRL-Ve Enabled o (off) CTRL+Ve <1.4V above CTRL-Ve Disabled
+ (on) CTRL+Ve >4.5V above CTRL-Ve Disabled+ (on) CTRL+Ve <1.4V above CTRL-Ve Enabled
Hazardous-area load Solid-state LFD output
<50Ω Non-conducting >7kΩ Non-conducting
Hazardous-area input LFD output
< 50µA (open-circuit) de-energised
> 6.6mA (short-circuit) de-energised
Figure 3.4: Phase reversal switch on base of units
PR switch setting Hazardous-area input(s) Output relay(s)
o (off) <1.2mA De-energised o (off) >2.1mA Energised
+ (on) <1.2mA Energised+ (on) >2.1mA De-energised
4
INM5000-6 Jul 2010
3.1.5. Relay outputs
Reactive loads on all units with relays should be adequately suppressed.Changeover relay outputs are provided on the following units: MTL5011B, MTL5014, MTL5018 and MTL5314. In order to achieve maximum contact life, a minimum switching current of 10mA at 5V is recommended.
3.1.6 Earth leakage detection
An MTL4220 earth leakage detector can be used with a number of MTL5000 Series units to detect hazardous-area earth faults which can then be rectified without needing to shut down the loop ('no-fail' operation). On units with a single-channel input, the MTL4220 is connected to terminal 3 and on units with two-channel inputs, to terminals 3 and 6. Units which can be used with an MTL4220 are:
MTL5011B MTL5012 MTL5014 MTL5015 MTL5017 MTL5018 MTL5021 MTL5022 MTL5023 MTL5024 MTL5025 MTL5061
N.B. HAZ1-3 or HAZ4-6 connectors are required.
3.1.7 Ambient temperature considerations
Ambient temperature limits for unenclosed MTL5000 Series isolators are from -20°C to +60°C with units close-packed.
4 ACCESSORIES
4.1 MTL5000 power bus - Installation and use
4.1.1 MTL5000 Series power bus
Power bus kits provide facilities for linking the power supply terminals (13 and 14) of up to 32 installed MTL5000 Series units to a standard 24V power supply. Buses consist of chains of power plugs and are available in different lengths to suit various numbers of modules as follows:
4.1.2. Installation
4.1.2.1 Check to make sure the bus length is correct for the
number of modules involved.
4.1.2.2 If the number of modules is less than the maximum number the chain will support, cut off the surplus power plugs at the tail end of the chain - leaving a 'new' tail end.
4.1.2.3 Insert power plugs into the power terminals on the safe­area side of each module in sequence.
4.1.2.4 Connect the power supply source to the tail end of the chain (using the insulation displacement connectors (Scotchloks) provided if required).
Notes:
1. To reduce the risk of excessive voltage drop or over­current, DO NOT connect power buses in series.
2. Surplus sections can be used (and, if required) connected together provided the cut ends are safely terminated and/or connected together. Use single ferrules with a crimp tool or insulation displacement connectors (Scotchloks). Suitable ferrules and connectors are provided with the kits.
4.2 Earth rail and tagging accessories
This section explains how to specify and assemble earth rail and tagging strip accessories for the MTL5000 Series.
The accessories consist of mounting brackets, earth rails, tagging strips and associated parts. They provide facilities for earthing, terminating cable screens and tagging (identifying) the positions of individual units.
4.2.1 Parts list IMB57 Insulating mounting block (figure 4.5)
One required at each end of a tagging strip/earth rail. Suitable for low­profile (7.5mm) and high-profile (15mm) symmetrical DIN rail.
ERB57S Earth-rail bracket, straight (figure 4.6)
Nickel-plated; supplied with two push fasteners, one earth-rail clamp (14mm, 35mm
2
) and one earth cable clamp (10mm, 16mm2).
Note: ERB57S is the preferred choice of earth-rail bracket. It is usually fitted in the upper slot on insulating mounting block IMB57
.
Number of modules Kit ID code
(contains grey power plugs for 24V dc supply)
1 to 8 PB-8T
9 to 16 PB-16T 17 to 24 PB-24T 25 to 32 PB-32T
 +
Optional insulation
displacement
connectors
x2
OR
Figure 4.1: Installing a chain of power plugs into MTL5000 Series modules
Figure 4.2: Using crimp ferrules or insulation displacement connectors (Scotchloks) to terminate cut ends
133.5mm
16mm
2
35mm
2
16mm235mm
2
10mm
3mm
14mm
10mm
14mm
10mm
5
INM5000-6 Jul 2010
Where the earth rail is required to be positioned at a lower height and to allow access to the IMB57 mounting screws, the straight earth-rail bracket ERB57S can be inserted in the lower slot, but only after insulating mounting blocks IMB57 are clamped to the DIN rail. This may not be possible if, for example, trunking is fitted. In this case, fit offset earth-rail bracket ERB57O (see figure 4.7) in the upper slot: the mounting blocks can then be fitted in a restricted space with this bracket already fitted.
ERB57O Earth-rail bracket, offset (figure 4.7)
Nickel-plated; supplied with two push fasteners, one earth-rail clamp (14mm, 35mm2) and one earth cable clamp (10mm, 16mm2).
ERL7 Earth rail, 1m length (figure 4.8)
Nickel-plated; may be cut to length.
TAG57 Tagging strip, 1m length (figure 4.9)
Cut to size. Supplied with tagging strip label.
TGL57 Tagging strip labels, set of 10 x 0.5m
Spares replacement, for use with TAG57 tagging strip.
MS010 DIN rail module spacer, 10mm, pack of 5 (figure 4.10)
Grey spacer, one required between each MTL5995 and any adjacent module on a DIN rail, to provide 10mm air-circulation space between modules.
TGL57
TAG57
ERB57
ERB570
ETM7
Snap off extension when using IMB57 as central support
10mm Earth clamp
ERB57S in upper position
ERB57S in lower position
IMB57
Push fastener
14mm Earth-rail clamp
ERL7
82mm
135mm
28mm
66mm
15mm
150mm
10mm
3mm
16mm
2
35mm
2
16mm235mm
2
10mm
14mm
10mm
14mm
3mm
10mm
THR2
IMB57
ERL7
HAZ1-3
HAZ4-6
TH5000
TAG57
TGL57
SAF7-9
SAF10-12
ERB57S
PWR5000
ETM7
Figure 4.3: Assembly drawing showing part numbers
Figure 4.4: Mounting details
Figure 4.5: IMB57 Insulating mounting block
Figure 4.6: ERB57S Earth-rail bracket, straight (end-on view), and clamps
Figure 4.7: ERB57O Earth-rail bracket, offset (end-on view), and clamps
Figure 4.8: ERL7 Earth-rail, 1m length
31mm
Figure 4.9: TAG57 Tagging strip,1m length
x 5
Figure 4.10: MS010 DIN rail module spacers
Type A
Type B
6
INM5000-6 Jul 2010
ETM7 Earth terminal, bag of 50 (figure 4.11)
For terminating cable screens and 0V returns on the ERL7 earth rail. For cables ≤ 4mm
2
.
TH5000 Tag holder
Spares replacement.
Connectors
Spares replacement: HAZ1-3, HAZ4-6, HAZ-CJC, PWR5000, SAF7-9, SAF10-12 (SAF1-3 and SAF4-6 grey connectors, also available for use in safe-area applications).
4.2.2 Assembly
4.2.2.1 Fitting earth rails a)
In upper position
Before fitting insulating mounting blocks IMB57, check that the swing nuts in the base of each unit are turned back into the moulding. Locate the mounting blocks on the DIN rail in the chosen position and tighten the screws (see figure 4.12). Check that the swing nuts rotate correctly to locate underneath the flanges of the DIN rail.
Slide a straight earth-rail bracket ERB57S into the upper slot in each mounting block. Push two plastic push fasteners into each bracket to locate the brackets in the mounting blocks.
Cut earth rail ERL7 to the length needed. Slide the required number of ETM7 earth terminals (5mm or 7mm wide) onto the rail. Clamp each end of the earth rail to earth-rail brackets ERB57S using the terminal clamps (14mm, 35mm
2
) supplied. Fit an earth clamp (10mm, 16mm2) to the free end of each earth-rail bracket.
Note: For lengths of earth-rail greater than 500mm, provide additional support by installing a third IMB57 mounting
block and earth-rail bracket, mid-way between the end mounting blocks. Snap out the perforated extension between the lugs on this mounting block if a continuous tagging strip is to be fitted (see figure 4.3).
b)
In lower position
, where at least 150mm clearance exists
on one side, measured from the edge of the mounting block. As for a), but slide earth-rail brackets ERB57S into the
lower slots in each mounting block.
c)
In lower position, where there is insufficient clearance to fit earth-rail brackets ERB57S.
As for a), but slide offset earth-rail brackets ERB57O into the upper slot in each mounting block before assembling the mounting blocks to the DIN rail. ERB57S brackets cannot be used because they obscure the mounting blocks' fixing screws.
4.2.2.2 Fitting tagging strips
Assemble mounting blocks IMB57 to the DIN rail as above. Cut TAG57 tagging strip and label to the length needed, and insert label so that the appropriate side is visible. Clip the strip onto the lugs on the mounting blocks. Hinge up the strip to provide access to the tops of the isolators.
Note: If necessary, provide additional support for long lengths of tagging strip by installing an extra IMB57 mounting block mid-way between the end mounting blocks. Snap out the perforated extension between the lugs on this mounting block.
4.2.3 Completed assemblies
Figure 4.13(below) illustrates a complete assembly of MTL5000 isolators using the accessories mentioned above.
The broken-line boxes either side of the assembly represent cable trunking, and the accompanying dimensions represent the minimum spacing between trunking and assemblies.
For further information on the use of the accessories please refer to the relevant MTL customer drawings listed in section 8.
5.5 mm
7mm
Type A Type B
110mm110mm
Figure 4.11: ETM7 Earth terminal
Figure 4.12: Fitting IMB57
Figure 4.13: MTL5000 Series - complete assembly
7
INM5000-6 Jul 2010
5 DX ENCLOSURES
Enclosures are usually selected on the basis of the number of units they will accommodate and table 5.1 shows the capacity of each of the enclosures. Figures 5.2 to 5.4 show each type of enclosure containing MTL5000 modules.
Table 5.1: DX range of enclosures - module capacities
* Use these figures when two IMB57 mounting brackets for tagging/earth-rail accessories are included
Note: The user should be aware that some workshop preparation may be required for the cable gland plates before the enclosure is ready for on-site installation.
131 (inside)
150
184
147 (inside)
Top of DIN rail
270
540
430
184
147 (inside)
Top of DIN rail
170
102 102
360
270
DX430
DX070
125
70
175
DX170
8080
Enclosure MTL5000 isolators
16.2 mm mounting pitch
DX070 4 (2*) DX170 10 (8*) DX430 26 (24*)
MTL5000 Series Isolators
Figure 5.1: MTL’s DX range of enclosures
Figure 5.2: DX070 enclosure showing MTL5000 modules
mounted
8
INM5000-6 Jul 2010
5.1 Environmental conditions
Environmental conditions that should be taken into account when installing DX enclosures include:-
See section Maximum ambient temperature limits 5.1.1 Storage temperatures 5.1.2 Humidity 5.1.3 Corrosion resistance 5.1.4 Flammability 5.1.5 Impact resistance 5.1.6 Chemical resistance 5.1.7
5.1.1 Maximum outside enclosure
temperature limits
The maximum outside enclosure temperature depends upon the total power dissipated by the installed modules which, in turn, depends upon their number and type. It can also be influenced by the Authority whose standards may need to be applied to the system, e.g. BASEEFA (CENELEC), Factory Mutual Research Corporation, Canadian Standards Association.
Figure 5.5 shows, in graphical form, the maximum outside enclosure temperatures (T
MO
) for given levels of power dissipation.
The graph was derived from the following equation and should be used to calculate accurately the suitability of any particular mix of modules.
T
MO
= 60°C - δT
where δT= k
1
x P P = total power (watts) dissipated by modules in an enclosure k
1
= is a dissipation constant for a given enclosure and
module series. Select the relevant value from table 5.2. (60°C is the temperature inside the enclosure)
Table 5.2: Dissipation constant k
1
for enclosures (°C/watt)
Orientation of the enclosures is also important - the optimum position being on a vertical surface with the internal DIN-rail horizontal as shown in figure 5.6. Any other position can reduce the maximum allowable ambient temperature by up to 5°C.
Examples
Tables 5.3 and 5.4 list likely combinations of MTL5000 Series modules in the three enclosure types and indicate the acceptable maximum permitted outside enclosure temperature for these based on the graph in figure 5.5. See the specifications included in the latest version of MTL's IS catalogue for the power dissipation figures of individual MTL5000 Series modules.
5.1.2 Storage temperatures
Storage temperatures are safe within the range -40°C to +80°C.
5.1.3 Humidity limits
Safe humidity limits are within the range 5 to 95% RH.
MTL5000 Series Isolators
MTL5000 Series Isolators
DX070 DX170 DX430
MTL5000 4.03 1.88 0.82
60
40
20
10
30
50
0
10 20 30 40
Power dissipation (watts)
Max. outside enclosure
temperature (°C)
Enclosures
DX070 DX170 DX430
Figure 5.3: DX170 enclosure showing MTL5000 modules mounted
Figure 5.4: DX430 enclosure showing MTL5000 modules mounted
Figure 5.5: Graph depicting outside enclosure temperature limits for DX enclosures used with MTL5000 Series isolators
Figure 5.6: Optimum orientation for wall-mounted enclosure
9
INM5000-6 Jul 2010
Table 5.3: Typical mix of MTL5000 Series modules
Table 5.4: Power versus maximum outside enclosure temperature
5.1.4 Corrosion resistance
The effect of corrosion on DX enclosures is negligible.
5.1.5 Flammability rating
The flammable properties of the materials used in the construction of the enclosures are well understood by manufacturers and ratings have been established to a number of standards. One of the better known standards is the Underwriter's Laboratory standard UL 94 and the ratings for the enclosure materials are given as:
Materials UL94 rating Polycarbonate (all lids) V2/V0 Polycarbonate with glass reinforcement (DX070 base) V1/V0 Polyester with glass reinforcement (DX170 & DX430 bases) V0 Items made from similar materials are well established as suitable for use
in process I/O marshalling areas.
5.1.6 Impact resistance
The enclosure designs have been tested to an impact resistance of greater than 2 Joules which exceeds the BS EN 61010-1 requirements of 0.5 Joules.
5.1.7 Chemical resistance
The overall chemical resistance of the enclosures is limited by the resistance of the transparent polycarbonate lid. The glass-reinforced polycarbonate/polyester (GRP) bases have a higher resistance than plain polycarbonate. Table 5.5 lists qualitative evaluations of resistance to a variety of chemical agents.
5.2 Mounting
5.2.1 General
These instructions are concerned solely with mounting the DX enclosures. Instructions for wiring and testing individual modules within the enclosures are provided in Section 6.
Sufficient space is provided within the enclosures to accommodate tagging and earth-rail accessories but this is at the expense of a reduction in the number of modules that can be fitted.
5.2.2 Location and orientation
5.2.2.1 Location
The DX enclosures are intended for safe (non-hazardous) area use. In N. America or Canada (because the enclosures are rated NEMA 4X)
they can be used in Class 1, Division 2 (gases) location, but check with local requirements and ensure all cable entries also conform. In this case, an additional warning label will be required on or near the enclosure warning that the MTL5000 interfaces must not be removed unless the area is known to be non-hazardous. The enclosures are NOT suitable for Class II or III, Division 2 hazardous locations.
5.2.2.2 Orientation
As noted earlier (see section 5.1.1 and figure 5.6), for optimum temperature performance the enclosures should be mounted on a vertical surface with the internal DIN rail horizontal.
5.2.3 Mounting details
See figures 5.7 to 5.9 for the dimensions and mounting hole distances, etc., of the three DX enclosures. The recommended method of mounting­described here-uses the four wall-mounting lugs supplied with each enclosure. An alternative method of mounting is by direct attachment to the mounting surface through the corner holes.
Note: When the wall-mounting lugs are used to attach the enclosures, the overall depth of the enclosure is increased by an additional 3.3 mm (DX070) or 7 mm (DX170 and DX430).
a) At each of the four corner fixing holes, insert one of the
screws provided and use it to attach a fixing lug to the base of the enclosure.
b) Each lug can be used in one of two positions as shown in
figures 5.7 to 5.9.
c) Attach the lugs to the mounting surface with suitable fasteners. d) Diameters of fixing holes in lugs are 5.5mm (DX070) and
7.0mm (DX170 and DX430)
e) Appropriate fixing hole distances are shown in figures 5.7
to 5.9.
Power dissipation Maximum outside
Enclosure Modules installed of modules in watts (P) enclosure temp. (T
MO
)°C
DX070 2xMTL5011B + 2xMTL5044 (2x0.75) + (2x1.5) = 4.5 41.9 DX170 5xMTL5011B + 5xMTL5044 (5x0.75) + (5x1.5) = 11.25 38.9 DX430 13xMTL5011B + 13xMTL5044 (13x0.75) + (13x1.5) = 29.25 36.0
Table 5.5: Qualitative evaluations of resistance to various chemical agents
Qualitative evaluation
Chemical agents of resistance
Salt water; neutral salts; acids (low concentrations); hydraulic oil Excellent Alcohols Very good Acids (high concentrations); alkalis (low concentrations); petrol; cooling fluids Good Alkalis (high concentrations); solvents. Poor
Number of k
1
Power dissipation Maximum outside
Enclosure installed modules °C/watt of modules in watts (P) enclosure temp. (T
MO
) °C
DX070 4 4.03 4.0 43.9
4 4.03 6.0 35.8
DX170 10 1.88 10.0 41.2
10 1.88 15.0 31.8
DX430 26 0.82 21.6 42.3
26 0.82 39.0 28.0
5.2.4 Cable glanding
All cables into the enclosures must be glanded to IP65 standards to maintain this rating for the enclosure as a whole. Cable glands and gland plates are not supplied. Glanding requirements vary for each enclosure as follows:
DX070
On the DX070, 'knockout' holes are provided, in two different sizes (15.5 mm and 21 mm), on the side faces of the base. See table 5.7 for recommended cable glands.
Note: The enclosure may have three or four knockout holes on each side depending on the manufacturer. Consequently, there may be a choice of either six or eight positions for cable glands.
DX170
The DX170 can accommodate one gland plate on each side - see figure
5.10 for details. Table 5.6 lists suppliers of suitable gland plate kits and Table 5.7 lists recommended glands.
DX430
The DX430 can accommodate two gland plates on each side - see figure
5.11 for details. Table 5.6 lists suppliers of suitable gland plate kits and Table 5.7 lists recommended glands.
10
INM5000-6 Jul 2010
107
137
157
187
Ø 5.5
520
576
249
305
Ø 7.0
Gland plate
Typical gland
positions
Gland plate
Typical gland
positions
249
305
339
395
Ø 7.0
Figure 5.7: Dimensions and location of fixing holes - DX070
Figure 5.8: Dimensions and location of fixing holes - DX170
Figure 5.9: Dimensions and location of fixing holes - DX430
Figure 5.10: Cable gland plate locations on a DX170 enclosure
Figure 5.11: Cable gland plate locations on a DX430 enclosure
11
INM5000-6 Jul 2010
Sarel (UK) Tel+44 (0)1793 514774 Bowthorpe Hellermann (UK) Tel +44 (0)1922 458151
Table 5.7: Recommended cable glands for use with DX enclosures.
Weidmuller (UK) Tel +44 (0)1795 580999 Sarel (UK) Tel +44 (0)1793 514774
5.3 Accessories in enclosures
Apart from mounting, there are some other installation details which should be considered before adding the appropriate interface modules and making the necessary cabling connections.
A range of accessories is available to accompany the MTL5000 units (see section 4). Further details of these accessories are provided in product sheet EPS57ACC and instruction manual INM57ACC but the following points should be observed.
5.3.1 Insulating mounting block (IMB57)
A pair of these can be attached to the DIN rail, at either end of the modules, to provide a mounting for earth rails. Use of mounting blocks will reduce the space available for isolator modules.
5.3.2 Earth rails (ERL7)
Earth rail is produced in 1 metre lengths and will require cutting to length before mounting. ERL7 earth rails can be mounted either side of the modules but are typically mounted on the hazardous side of the DIN rail.
5.3.3 Tagging strip (TAG57 and TGL57)
Tagging strip is produced in 1 metre lengths and will require cutting to length before mounting. Similarly, the labels will require cutting to fit the tagging strip.
5.4 IS warning label
A 'Take Care' IS warning label is provided inside each enclosure. This should be attached to the inside of the transparent lid when its orientation has been established.
6 UNIT DESCRIPTIONS, SETTING-UP,
CONNECTIONS AND TESTING
For each MTL5000 Series unit, this section describes the function (briefly), the setting-up procedure, wiring connections and includes a simple functional test. For a fuller functional description and a detailed technical specification, refer to the appropriate entry in MTL's current IS catalogue.
The functional tests can be carried out during commissioning or later, for fault finding. If a fault is suspected, first check that the power LED is lit (not applicable to loop-powered devices). If necessary, check that all signal and power plugs are properly inserted, that no wires are loose and that the unit is mounted correctly. If operation is still suspect, carry out the tests. They establish whether power supplies are connected properly and whether the isolator is operating correctly. Please return units that fail these tests to the supplier.
6.1 MTL5011 single-pole relay single­channel switch/proximity detector with phase reversal (Discontinued use MTL5011B)
The MTL5011 enables a safe-area load to be relay-controlled by a switch or proximity detector located in a hazardous area. Output phase reversal (see 3.1.3) is provided.
6.1.1 Wiring connections
See figure 6.1 for wiring connections.
Note: Reactive loads must be adequately suppressed
Manufacturer/agent Manufacturer’s part number
Enclosure DX170 Enclosure DX430
Bowthorpe Hellermann TL-27/360 TL-27/270 Sarel 21128 21127
Table 5.6: Recommended gland plate kits for DX170 and DX430 enclosures.
Gland Cable Gland plate Weidmuller part nos. Sarel part nos.
thread sizes hole size
size (mm) (mm) Gland Locknut Gland Locknut
PG9 5 to 8 15.2 951891 952216 08871 08881
PG13,5 8 to 13 20.4 951893 952218 08873 08883
WARNING When disconnecting units for testing, take care to segregate hazardous- and safe-area cables. Short circuit hazardous-area cable cores to an IS earth or insulate and secure the ends. Insulate and secure safe-area cables. If testing 'in situ' note that the test equipment used MUST be intrinsically safe.
Terminal Function
1 Input –ve 2 Input +ve
3 Earth leakage detection 11 Output 12 Output 13 Supply –ve 14 Supply +ve
3 2 1
6 5 4
7 8 9
10 11 12
13 14
To earth leakage detector
Vs Vs+
20 to 35V dc
+
Figure 6.1: MTL5011 wiring diagram and connections
Hazardous area Safe area
12
INM5000-6 Jul 2010
6.1.2 Testing
Make the safe- and hazardous-area connections shown in figure 6.2 and check status LEDs and relay contacts as follows:
6.2 MTL5011B single-pole changeover relay single-channel switch/ proximity detector with line fault detection and phase reversal
The MTL5011B is similar to the MTL5011 but with added line fault detection (LFD) facilities.
6.2.1 Wiring connections
See figure 6.3 for wiring connections.
Note: Reactive loads must be adequately suppressed.
6.2.2 Line fault detection
(See section 3.1.4 for definition of a line fault)
Input line faults (open- or short-circuit) are indicated by an LED and the de-energising of the output relay. LFD is enabled/disabled by a switch located on top of the module. Note that if the LFD facility is enabled for switch inputs, the resistors shown in figures 6.3 and 6.4 MUST be fitted.
6.2.3 Testing
Make the safe- and hazardous-area connections shown in figure 6.4 and check the status of the output contacts as shown in table 6.1
Table 6.1
6.3 MTL5012 solid-state single-channel switch/proximity detector with line fault detection and phase reversal
The MTL5012 enables a safe-area load to be controlled, through a solid­state output, by a switch or proximity detector in a hazardous area. Line fault detection (LFD) and output phase reversal (see 3.1.3) facilities are included.
Input Phase Status Relay
switch reverse switch LED contacts
Closed Normal On Closed Closed Reverse Off Open
Open Normal Off Open Open Reverse On Closed
Vs Vs+
20 to 35V dc
+
3 2 1
6 5 4
7 8 9
10 11 12
13 14
Phase Input Output Output Channel Line fault
reverse Line fault switch relay relay LED LED
switch detection (SW) (11-12) (10-11) (yellow) (red)
Normal Off a Closed Open On Off
Reverse Off a Open Closed Off Off
Reverse Off Open Closed Open On Off
Normal On Open Open Closed Off On
Normal On a Open Closed On On
Normal On b Open Closed Off Off
Normal On c Closed Open On Off
Terminal Function
1 Input –ve 2 Input +ve
3 Earth leakage detection 10 Normally-closed contact 11 Common 12 Normally-open contact 13 Supply –ve 14 Supply +ve
6 5 4
3 2 1
7 8 9
10 11 12
13 14
Vs Vs+
20 to 35V dc
Ch1
To earth leakage detector
SW
Ch1
22kW
680W
a
b
c
+
Figure 6.2: Test circuit for MTL5011
Figure 6.4: Test circuit for MTL5011B
6 5 4
3 2 1
7 8 9
10 11 12
13 14
Vs Vs+
20 to 35V dc
Outpu
To earth leakage detector
22kW
680W
+
Resistors required only for line fault detection
Figure 6.3: MTL5011B wiring diagram and connections
Hazardous area Safe area
6.3.3 Testing
Make the safe- and hazardous-area connections shown in figure 6.6 and check as shown in table 6.2
6.4 MTL5014 single-pole changeover relay single-channel dual-output switch/proximity detector with line fault detection and phase reversal
The MTL5014 enables two safe-area loads to be relay-controlled by a single hazardous-area switch or proximity detector. Phase reversal (see
3.1.3 and figure 6.8), line fault detection and slave/line fault monitoring
configurations are possible.
6.4.1 Wiring connections
See figure 6.7 for wiring connections
Note: Reactive loads must be adequately suppressed.
13
INM5000-6 Jul 2010
6.3.1 Wiring connections
See figure 6.5 for wiring connections.
6.3.2 Line fault detection
(See section 3.1.4 for definition of a line fault)
Input line faults (open- or short-circuit) are indicated by an LED and the non-conducting of the output. LFD is enabled/disabled by a switch located on top of the module. Note that if the LFD facility is enabled for switch inputs, the resistors shown in figures 6.5 and 6.6 MUST be fitted.
Table 6.2
Terminal Function
1 Input –ve 2 Input +ve 3 Earth leakage detection
10 &11 Output –ve
12 Output +ve 13 Supply –ve 14 Supply +ve
+
6 5 4
3 2 1
7 8 9
10 11 12
13 14
Vs Vs+
20 to 35V dc
To earth leakage detector
SW
22kW
680W
a
b
c
+
1kW
V
d
Phase Input Output Channel Line fault
reverse Line fault switch status status LED LED
switch detection (SW) (11-12) (yellow) (red)
Normal Off a Vd < 4V On Off
Reverse Off Isc= 7–9mA Vd = V
S
Off Off
Reverse Off Open Vd < 4V On Off
Normal On V
oc
= 7V5–9V5 Vd = V
S
Off On
Normal On a V
d
= V
S
Off On
Normal On c Vd < 4V On Off
Normal On b Vd = V
S
Off Off
Terminal Function
1 Input –ve 2 Input +ve 3 Earth leakage detection 7 Normally closed (output 2) 8 Common (output 2)
9 Normally open (output 2) 10 Normally closed (output 1) 11 Common (output 1) 12 Normally open (output 1) 13 Supply –ve 14 Supply +ve
Figure 6.6: Test circuit for MTL5012
 +
6 5 4
3 2 1
7 8 9
10 11 12
13 14
Vs Vs+
20 to 35V dc
To earth leakage detector
22kW
680W
+
Resistors required only for line fault detection
Figure 6.5: MTL5012 wiring diagram and connections
Hazardous area
Safe area
6 5 4
3 2 1
7 8 9
10 11 12
13 14
Vs Vs+
20 to 35V dc
To earth leakage detector
22kW
680W
+
Output 2
Output 1
For contact inputs resistors must be fitted
Figure 6.7: MTL5014 wiring diagram and connections
Safe area
Hazardous area
14
INM5000-6 Jul 2010
6.4.2 Outputs
The output 1 relay reflects the status of the input and may be configured to operate in reverse phase (PR) or with line-fault detection (LF). The output 2 relay may be configured either to follow (slave mode) output 1 or as a line-integrity monitor (LFD) (see 6.4.3).
6.4.3 Line fault detection
(See section 3.1.4 for definition of a line fault)
Line-fault detection and the operational mode of output 2 (ie slave to output 1 or LFD) are selected by switches located on the top of the module (see figure 6.8).
When LFD is selected for output 2 and there is a line fault in the sensor circuit the output 2 relay is de-energised (providing an alarm output). When LF is selected for output 1, the output 1 relay is de-energised if there is a line fault in the sensor circuit. Note that resistors must be fitted when using LFD with a contact input; 500Ω to 1kΩ in series, and 20kΩ to 25kΩ in parallel with the switch.
6.4.4 Testing
Make the relevant safe- and hazardous-area connections shown in figure
6.9 for the tests listed in table 6.3. (Figure 6.8 shows the switch positions for configuring output 2 slave/LFD, output 1 line fault (LF) and phase reversal (PR)).
Table 6.3
6.5 MTL5015 solid-state two-channel switch/proximity detector with line fault detection and phase reversal
The MTL5015 enables each of two safe-area loads to be controlled, through a solid-state output, by a switch or proximity detector in a hazardous area. Line fault detection (LFD) and output phase reversal (see 3.1.3) facilities are included.
6.5.1 Wiring connections
See figure 6.10 for wiring connections.
Phase Line fault Output 1 Output 2 Status Fault
reverse detection Slave Input test switch position relay relay LED LED
Test switch (PR) (LF) (LFD) (terminals 1 & 2) (11-12) (9-8) (yellow) (red)
1 Normal Off LFD (a) i.e. short-circuit Closed Open On On
2 Reverse Off LFD (a) short-circuit (Isc=7–9mA) Open Open Off On
3 Normal On Slave (a) short-circuit Open Open Off On
4 Normal Off Slave (a) short-circuit Closed Closed On Off
5 Normal Off Slave open-circuit (Voc=7V5–9V5) Open Open Off Off
6 Normal On Slave open-circuit Open Open Off On
7 Normal Off LFD (b) 22kΩ Open Closed Off Off
8 Normal Off LFD (c) 680Ω Closed Closed On Off
LF PR O/P1
ON
SLAVE LFD
Output 2
MTL5014
PWR
Output 1 follows sensor
Output 2 slaves output 1
Output 1 follows sensor
Output 2 monitors LFD
Output 1 follows sensor & LFD
Output 2 slaves output 1
Output 1 follows sensor & LFD
Output 2 monitors LFD
Output 1 in phase with sensor
Output 1 in anti-phase with sensor
(LFD not affected)
6 5 4
3 2 1
7 8 9
10 11 12
13 14
Vs Vs+
20 to 35V dc
Output 2
relay
Output 1
relay
To earth leakage detector
SW
22kW
680W
a
b
c
+
open
Terminal Function
1 Input –ve (Ch 1) 2 Input +ve (Ch 1) 3 Earth leakage detection 4 Input –ve (Ch 2) 5 Input +ve (Ch 2) 6 Earth leakage detection 8 Output –ve (Ch 2)
9 Output +ve (Ch 2) 11 Output –ve (Ch 1) 12 Output +ve (Ch 1) 13 Supply –ve 14 Supply +ve
6 5 4
3 2 1
7 8 9
10 11 12
13 14
To earth leakage detector
SW
22kW
680W
a
b
c
open
22kW
+
Vs Vs+
20 to 35V dc
} V
d2
1kW
1kW
+
+
} Vd1
Ch1
Ch2
+
Figure 6.8: Top label of MTL5014 with explanation of switch positions
Figure 6.9: Test circuit for MTL:5014
Figure 6.11: Test circuit for MTL5015
6 5 4
3 2 1
7 8 9
10 11 12
13 14
Vs Vs+
20 to 35V dc
To earth leakage detector
22kW
680W
+
Resistors required only for line fault detection
Ch 2
22kW
680W
+
Ch 1
+
+
Figure 6.10: MTL5015 wiring diagram and connections
Hazardous area Safe area
15
INM5000-6 Jul 2010
Table 6.4
6.5.2 Line fault detection
(See section 3.1.4 for definition of a line fault)
On both channels, input line faults (open- or short-circuit) are indicated by an LED and the de-energising of the output. LFD is enabled/disabled by switches located on top of the module. Note that if the LFD facility is enabled for switch inputs, the resistors shown in figures 6.10 and 6.11 MUST be fitted.
6.5.3 Testing
Make the safe- and hazardous-area connections shown in figure 6.11 and check the status of the output contacts for each channel in turn (with a 22kΩ resistor connected to the other channel) as shown in table 6.4.
6.6 MTL5016 single-pole relay two­channel switch/proximity detector with phase reversal (Discontinued, use MTL5018)
The MTL5016 enables two safe-area loads to be relay-controlled by two switches or proximity detectors located in a hazardous area. Output phase reversal (see 3.1.3) is provided.
Table 6.5
6.6.1 Wiring connections
See figure 6.12 for wiring connections.
Note: Reactive loads must be adequately suppressed.
6.6.2 Testing
Make the safe- and hazardous-area connections shown in figure 6.13 and check status LEDs and relay contacts as in table 6.5.
6.7 MTL5017 single-pole relay two­channel switch/proximity detector with line fault detection and phase reversal
The MTL5017 is similar to the MTL5018 but with the addition of line fault detection facilities.
6.7.1 Wiring connections
See figure 6.14 for wiring connections.
Note: Reactive loads must be adequately suppressed.
6.7.2 Line fault detection
(
See section 3.1.4 for definition of a line-fault)
Line faults de-energise a dedicated line fault detect relay (between terminals 7 and 10) to provide an alarm facility and are indicated by an LED. Each channel relay will also de-energise (open) when a line fault exists on that channel. LFD is automatic. Note that for switch inputs the resistors shown in figures 6.14 and 6.15 MUST be fitted for correct LFD operation.
Phase Input Output Channel Line fault
reverse Line fault switch status status LED LED
switch detection (SW) (11-12, 8-9) (yellow) (red)
Normal Off a Vd<4V On Off Reverse Off a V
d
=V
S
Off Off
Reverse Off open V
d
<4V On Off
Normal On open V
d
=V
S
Off On
Normal On a V
d
=V
S
Off On
Normal On c V
d
<4V On Off
Normal On b V
d
=V
S
Off Off
Phase reverse Phase reverse Channel 1 Channel 2 Relay Relay
Input switch Input switch switch switch status LED status LED contacts contacts
(ch 1) (ch 2) (ch 1) (ch 2) (yellow) (yellow) (ch 1) (ch 2)
Closed Open Normal Normal On Off Closed Open Closed Closed Normal Normal On On Closed Closed Closed Closed Reverse Reverse Off Off Open Open
Open Open Reverse Reverse On On Closed Closed
Terminal Function
1 Input –ve (Ch 1) 2 Input +ve (Ch 1) 3 Earth leakage detection 4 Input –ve (Ch 2) 5 Input +ve (Ch 2) 8 Output (Ch 2)
9 Output (Ch 2) 11 Output (Ch 1) 12 Output (Ch 1) 13 Supply –ve 14 Supply +ve
3 2 1
6 5 4
7 8 9
10 11 12
13 14
Vs Vs+
20 to 35V dc
+
SW1
SW2
Ch1
Ch2
+
Figure 6.13: Test circuit for MTL5016
3 2 1
6 5 4
7 8 9
10 11 12
13 14
Vs Vs+
20 to 35V dc
+
To earth leakage detector
Ch1
Ch2
Ch1
Ch2
+
Figure 6.12: MTL5016 wiring diagram and connections
Hazardous area
Safe area
16
INM5000-6 Jul 2010
6.7.3 Testing
Make the safe- and hazardous-area connections shown in figure 6.15 and check the status of the output contacts for each channel in turn (with a 22kΩ resistor connected to the other channel) as shown in table 6.6.
Table 6.6
6.8 MTL5018 single-pole, changeover relay, two-channel, switch/proximity detector with line fault detection and phase reversal
The MTL5018 modules enable each of two safe-area loads to be relay­controlled by switches or proximity detectors in a hazardous area. Line fault detection (LFD) and output phase reversal (see 3.1.3) facilities are included.
6.8.1 Wiring connections
See figure 6.16 for wiring connections.
Note: Reactive loads must be adequately suppressed.
6.8.2 Line fault detection
(See section 3.1.4 for definition of a line fault)
On each channel, input line faults (open- or short-circuit) are indicated by an LED and the de-energising of the output.
LFD is enabled/disabled by switches located on the top of the module. Note that if the LFD facility is enabled for switch inputs, the resistors shown in figures 6.16 and 6.17 MUST be fitted.
6.8.3 Testing
Make the safe- and hazardous-area connections shown in figure 6.17 and check the status of the output contacts for each channel in turn (with a 22kΩ resistor connected to the other channel) as shown in table 6.7.
6.9 MTL5018AC single-pole, changeover relay, two-channel, switch/proximity detector with line fault detection and phase reversal
The MTL5018AC modules enable each of two safe-area loads to be relay-controlled by switches or proximity detectors in a hazardous area. Line fault detection (LFD) and output phase reversal facilities are included (see section 3.1.3 ).
6.9.1 Wiring connections
See figure 6.18 for wiring connections.
Note: Reactive loads must be adequately suppressed.
6.9.2 Line fault detection
(See section 3.1.4 for definition of a line fault)
On each channel, input line faults (open- or short-circuit) are indicated by an LED and the de-energising of the output. LFD is enabled/disabled by switches located on the top of the module.
Note that if the LFD facility is enabled for switch inputs, the resistors shown in figures 6.18 and 6.19 MUST be fitted.
Terminal Function
1 Input –ve (Ch 1) 2 Input +ve (Ch 1) 3 Earth leakage detection 4 Input –ve (Ch 2) 5 Input +ve (Ch 2) 7 Line fault detection 8 Output (Ch 2)
9 Output (Ch 2) 10 Line fault detection 11 Output (Ch 1) 12 Output (Ch 1) 13 Supply –ve 14 Supply +ve
6 5 4
3 2 1
7 8 9
10 11 12
13 14
LFD
Vs Vs+
20 to 35V dc
Ch 2
Ch 1
LFD
LFD
To earth leakage detector
SW
22kW
680W
a
b
c
open
22kW
+
Ch1
Ch2
+
Output Line-fault
Input relay relay
(11-12, 8-9) (7 & 10)
Open-circuit Open Open Short-circuit Closed Open
680Ω Closed Closed
22kΩ Open Closed
Terminal Function
1 Input –ve (Ch 1) 2 Input +ve (Ch 1) 3 Earth leakage detection 4 Input –ve (Ch 2) 5 Input +ve (Ch 2) 6 Earth leakage detection 7 Normally-closed contact (Ch 2) 8 Common (Ch 2)
9 Normally-open contact (Ch 2) 10 Normally-closed contact (Ch 1) 11 Common (Ch 1) 12 Normally-open contact (Ch 1) 13 Supply –ve 14 Supply +ve
6 5 4
3 2 1
7 8 9
10 11 12
13 14
Vs Vs+
20 to 35V dc
Ch 2
Ch 1
To earth leakage detector
SW
22kW
680W
a
b
c
open
22kW
+
Ch1
Ch2
+
Figure 6.15: Test circuit for MTL5017
Figure 6.17: Test circuit for MTL5018
6 5 4
3 2 1
7 8 9
10 11 12
13 14
LFD
Vs Vs+
20 to 35V dc
To earth leakage detector
22kW
680W
+
Ch 2
22kW
680W
+
Ch 1
LFD
LFD
For contact inputs resistors must be fitted
Figure 6.14: MTL5017 wiring diagram and connections
Hazardous area Safe area
6 5 4
3 2 1
7 8 9
10 11 12
13 14
Vs Vs+
20 to 35V dc
To earth leakage detector
22kW
680W
+
22kW
680W
+
Resistors required only for line fault detection
Ch 2
Ch 1
Figure 6.16: MTL5018 wiring diagram and connections
Hazardous area Safe area
17
INM5000-6 Jul 2010
6.9.3 Testing
Make the safe- and hazardous-area connections shown in figure 6.19, and check the status of the output contacts for each channel in turn (with a 22kΩ resistor connected to the other channel) as shown in table 6.7.
6.10 MTL5021 loop-powered solenoid/alarm driver, IIC
The MTL5021 enables a device located in the hazardous area to be controlled by a switch located in the safe area. Suitable for IIC applications.
610.1 Wiring connections
See figure 6.20 for wiring connections.
6.10.2 Testing
Make the safe- and hazardous-area connections shown in figure 6.19, apply 24V to terminals 11 and 12 and, with no load, check voltage and short-circuit current levels at terminals 1 and 2 as follows:
Terminal Function
1 Input –ve (Ch 1) 2 Input +ve (Ch 1) 3 Earth leakage detection 4 Input –ve (Ch 2) 5 Input +ve (Ch 2) 6 Earth leakage detection 7 Normally-closed contact (Ch 2) 8 Common (Ch 2)
9 Normally-open contact (Ch 2) 10 Normally-closed contact (Ch 1) 11 Common (Ch 1) 12 Normally-open contact (Ch 1) 13 Supply N 14 Supply L
6 5 4
3 2 1
7 8 9
10 11 12
13 14
680W
22kW
22kW
To earth leakage detector
SW
a
b
c
open
+
Ch1
Ch2
Vs
Vs
85 to 265V ac
Ch1
Ch 2
+
Phase Input Output Output Channel Line fault reverse Line fault switch relay relay status LED LED switch detection (SW) (11-12, 8-9) (10-11, 7-8) (yellow) (red)
Normal Off a Closed Open On Off
Reverse Off Isc= 7 – 9mA Open Closed Off Off
Reverse Off Open Closed Open Off Off
Normal On Voc= 7.5 – 9.5V Open Closed Off On
Normal On a Open Closed Off On
Normal On b Open Closed Off Off
Normal On c Closed Open On Off
Input Output Short-circuit
voltage Status voltage current
(terminals 11 & 12) LED (terminals 1 & 2) (terminals 1 & 2)
24V dc On 22 to 24V — 24V dc On 45 to 52mA
Figure 6.19: Test circuit for MTL5018AC
6 5 4
3 2 1
7 8 9
10 11 12
13 14
Vs Vs
Ch1
Ch 2
+
22kW
22kW
680W
+
To earth leakage detector
Ch 1
Ch 2
680W
Hazardous area Safe area
Figure 6.18: MTL5018AC wiring diagram and connections
7 8
9 10 11 12
6 5 4 3 2 1
Solenoid, alarm or other IS device
To earth leakage detector
20  35Vdc
 +
+
Hazardous area
Safe area
Figure 6.20: MTL5021 wiring diagram and connections
Table 6.7
7 8
9 10 11 12
6 5
4 3 2 1
24Vdc
 +
+
V
A
Figure 6.21: Test circuit for MTL5021
Terminal Function
1 Output –ve 2 Output +ve
3 Earth leakage detection 11 Supply –ve 12 Supply +ve
6.11 MTL5022 loop-powered solenoid/alarm driver, IIB
The MTL5022 enables a device located in the hazardous area to be controlled by a switch located in the safe area. Suitable for IIA and IIB applications.
6.11.1 Wiring connections
See figure 6.22 for wiring connections.
6.11.2 Testing
Make the safe- and hazardous-area connections shown in figure 6.23, apply 24V to terminals 11 and 12 and, with no load, check voltage and short-circuit current levels at terminals 1 and 2 as follows
18
INM5000-6 Jul 2010
6.12 MTL5023 solenoid/alarm driver with line fault detection and phase reversal
The MTL5023 enables a device located in the hazardous area to be controlled by a volt-free contact or logic signal located in the safe area. Line fault detection (LFD) and output phase reversal (see 3.1.3) facilities are included.
6.12.1 Wiring connections
See figure 6.24 for wiring connections.
6.12.2 Line fault detection
(See section 3.1.4 for definition of a line fault)
Hazardous-area line faults are signalled to the safe area by an LED and a solid-state switch which de-energises when a line is open- or short­circuited.
6.12.3 Testing
Make the safe- and hazardous-area connections shown in figure 6.25 and carry out the voltage and current checks as shown in table 6.8.
Input Status Output Short-circuit
voltage LED voltage current
(terminals 11 & 12) yellow (terminals 1 & 2) (terminals 1 & 2)
24V dc On 22 to 24V – 24V dc On 61 to 70mA
Terminal Function
1 Output –ve 2 Output +ve
3 Earth leakage detection 11 Supply –ve 12 Supply +ve
7 8
9 10 11 12
6 5
4 3 2 1
24Vdc
 +
+
V
A
Figure 6.23: Test circuit for MTL5022
7 8
9 10 11 12
6 5 4 3 2 1
Solenoid, alarm or other IS device
To earth leakage detector
20  35Vdc
 +
+
Hazardous area Safe area
Figure 6.22: MTL5022 wiring diagrm and connections
Input switch LFD Status Output Output
SW1 Phase reverse LED LED voltage current
(terminals 11 & 12) Load switch (red) (yellow) (terminals 1 & 2) (terminals 1 & 2)
Closed 2kΩ Normal Off On >19.5V
Open 2kΩ Normal Off Off <4.5V
Closed 15kΩ Normal On On >21.0V
Open 15kΩ Normal On Off <7.0V
Closed Short-circuit Normal On On >45mA
Open Short-circuit Normal On Off <6mA
Closed Short-circuit Reverse On Off <6mA
Table 6.8
Vs Vs+
20 to 35V dc
Line fault detection
+
+
Test meter (set initially to volts)
Load
+
6 5 4
3 2 1
7 8 9
10 11 12
13 14
Solenoid, alarm or other IS device
To earth leakage detector
+
Vs Vs+
20 to 35V dc
Line fault detection
+
+
6 5 4
3 2 1
7 8 9
10 11 12
13 14
Figure 6.24: MTL5023 wiring diagram and connections
Figure 6.25: Test circuit for MTL5023
Hazardous area Safe area
Terminal Function
1 Output –ve 2 Output +ve 3 Earth leakage detection
7 Line fault signal -ve 10 Line fault signal +ve 11 Control –ve 12 Control +ve 13 Supply –ve 14 Supply +ve
6.13 MTL5024 solenoid/alarm driver, logic drive with phase reversal
The MTL5024 enables an on/off device located in a hazardous area to be controlled by a volt-free contact or logic signal located in t he safe area. Output phase reversal (see 3.1.3) facilities are included.
6.13.1 Wiring connections
See figure 6.26 for wiring connections.
6.13.2 Testing
Make the safe- and hazardous-area connections shown in figure 6.27 and carry out the following output voltage and short-circuit current checks:
6.14 MTL5025 low-current loop-powered solenoid/alarm driver, IIC
The MTL5025 enables an on/off device located in a hazardous area to be controlled by a switch or voltage change in a safe area.
6.14.1 Wiring connections
See figure 6.28 for wiring connections.
19
INM5000-6 Jul 2010
6.14 .2 Testing
Make the safe- and hazardous-area connections shown in figure 6.29 and carry out the following output voltage and short-circuit current checks:
6.15 MTL5031 vibration transducer interface
The MTL5031 repeats the signal from a vibration sensor in a hazardous area to a monitoring system in a safe area.
6.15.1 Wiring connections
See figure 6.30 for wiring connections.
Terminal Function
1 Output –ve 2 Output +ve
3 Earth leakage detection 11 Control –ve 12 Control +ve 13 Supply –ve 14 Supply +ve
Solenoid, alarm or other IS device
To earth leakage detector
+
Vs Vs+
20 to 35V dc
+
Control
6 5 4
3 2 1
7 8 9
10 11 12
13 14
Figure 6.26: MTL5024 wiring diagram and connections
SW1 Output Output
(terminals Phase Status voltage current
11 & 12) setting LED (terminals1 & 2) (terminals 1 & 2)
Closed Normal On 22 to 24V
Closed Normal On 45 to 52mA
Closed Reverse On <6mA
Vs Vs+
20 to 35V dc
+
+
SW1
V
A
6 5 4
3 2 1
7 8 9
10 11 12
13 14
Figure 6.27: Test circuit for MTL5024
Safe areaHazardous area
Terminal Function
1 Output –ve 2 Output +ve
3 Earth leakage detection 11 Supply –ve 12 Supply +ve
Solenoid, alarm or other IS device
To earth leakage detector
+
20 to 35V dc
+
6 5 4
3 2 1
7 8 9
10 11 12
Figure 6.28: MTL5025 wiring diagram and connections
Input voltage Status Output voltage Output current
(terminals 11 & 12) LED (terminals 1 & 2) (terminals 1 & 2)
24V On 22 to 24V – 24V On 45 to 52mA
+
20 to 35V dc
+
V
A
6 5 4
3 2 1
7 8 9
10 11 12
Figure 6.29: Test circuit for MTL5025
Hazardous area
Safe area
Vs Vs+
20 to 35V dc
Vibration transducer
Common
Signal
Transducer power V
T
Signal ve
Signal 0V
Monitor
6 5 4
3 2 1
7 8 9
10 11 12
13 14
Figure 6.30: MTL5031 wiring diagram and connections
Hazardous area
Safe area
Terminal Function
1 Common 2 Signal 3 Transducer power V
T
11 Signal –ve 12 Signal 0V 13 Supply –ve 14 Supply +ve
20
INM5000-6 Jul 2010
6.15.2 Testing
Make the safe- and hazardous-area connection shown in figure 6.31.
Measure the voltage on terminal 3 with respect to terminal 1; this should be >19V. Vary the potentiometer setting and check that the reading on voltmeter V varies by no more than ±100mV.
6.16 MTL5032 pulse isolator
The MTL5032 isolates pulses from a switch, proximity detector, current pulse transmitter or voltage pulse transmitter located in the hazardous area.
6.16.1. Wiring connections
See figure 6.32 for wiring connections.
*Note: When connected to a circuit which requires an external voltage or current input, the output may be connected in parallel with that input in conjunction with a pull-up resistor wired to terminal 12 and connected to an appropriate voltage source. The zero volt of the same voltage source should be referenced back to terminal 11. (Maximum current is 50mA; e.g. resistor value of 510Ωat 24V.)
6.16.2 Voltage pulse settings
The threshold voltage for the voltage pulse input is set by two switches located on the base of the unit. Referring to figure 6.33, these are set as follows:
6.16.3 Testing
Make the safe- and hazardous-area connections shown in figure 6.34 and carry out the following checks:
O N
2
1
OFF
ON
SW1
SW2
Label face
Base of unit
Figure 6.33: Pulse voltage selection switches
Threshold SW1 SW2
3V On On 6V On Off
12V Off Off
Vs Vs+
20 to 35V dc
V
100W
1kW
V
T
Sig 0V
6 5 4
3 2 1
7 8 9
10 11 12
13 14
Figure 6.31: Test circuit for MTL5031
V
Vs Vs+
20 to 35V dc
Voltage pulse
Current pulse
2-wire current pulse
3-wire current pulse
3-wire voltage pulse
+
4/20 mA
4/20 mA
4/20 mA
6 5 4
3 2 1
7 8 9
10 11 12
13 14
+
+
+ +
Figure 6.32: MTL5032 wiring diagram and connections
Hazardous Area
Safe Area
Vs Vs+
20 to 35V dc
+
SW1
2.2kW
2.2kW
SW2
4.7kW
TEST
6 5 4
3 2 1
7 8 9
10 11 12
13 14
+ +
Figure 6.34: Test circuit for MTL5032
Status Test LED
SW1 SW2 LED (terminal 14)
Closed Open On On
Open Closed On On
Terminal Function
1 Common -ve 2 Proximity detector +ve 3 Current +ve 4 Transmitter +ve
5 Voltage +ve 11 Output –ve 12 Output +ve 13 Supply –ve 14 Supply +ve
21
INM5000-6 Jul 2010
6.17 MTL5040 2-channel 4 to 20mA loop isolator
The MTL5040 provides a fully floating dc supply for energising a conventional 2-wire 4 to 20mA transmitter located in a hazardous area. It also passes on a 4 to 20 mA or 0 to 20mA signal from a controller located in the safe area to a load in the hazardous area.
6.17.1 Wiring connections
See figure 6.35 for wiring connections.
6.17.2 Testing
Make the safe and hazardous-area connections shown in figure 6.36 and, using RV1 to vary the output current on channel 1, and using the current source to vary the output current on channel 2, carry out the checks shown in table 6.9
Table 6.9
6.18 MTL5041/42 repeater power supplies
The MTL5041/42 provide fully-floating dc supplies for energising conventional 2-wire 4 to 20mA transmitters located in a hazardous area. They repeat the current in another floating circuit to drive safe-area loads. The MTL5042 also provides similar facilities for 3-wire transmitters
and permits bi-directional transmission of 'smart' digital communication signals superimposed on the 4 to 20mA signal.
Note: MTL5042 terminals 1 and 3 only support HART® communi­cations in one direction from field device to safe-area connections 11 and 12.
6.18.1 Wiring connections
See figures 6.37 and 6.38 for wiring connections (MTL5041 and MTL5042 respectively).
6.18.2 Testing
Make the safe- and hazardous-area connections shown in figure 6.39 and, using RV1 to vary the output current, carry out the checks shown in table 6.10.
7 8 9
6 5 4 3 2 1
13 14
10 11 12
I
I
I
I
4/20mA
4/20mA
P
I
Vs Vs+
20 to 35V dc
+
+
4/20mA
Figure 6.35: MTL5040 wiring diagram and connections
Terminal Function
1 Input –ve (transmitter), ch 1 2 Input +ve (transmitter), ch 1 4 Output –ve (driver), ch 2 5 Output +ve (driver), ch 2 8 Input -ve (driver), ch 2
9 Input +ve (driver), ch 2 11 Output –ve (transmitter), ch 1 12 Output +ve (transmitter) ch 1 13 Supply –ve 14 Supply +ve
7 8 9
6 5 4 3 2 1
13 14
10 11 12
I
I
I
I
Vs Vs+
20 to 35V dc
+
+
+
+
+
470
W
Ch 2
Current Source
Ch 1
RV1
10kW lin
A3
A1
A4
A2
Figure 6.36: Test circuit for MTL5040
Output current Current reading Channel 1 Voltage
(A2 for Ch 1 and (A1 for Ch 1 and (terminal 2 with
A4 for Ch 2) A3 for Ch 2) respect to terminal 1)
4 to 20mA <±20μA
20mA >16.5V
Safe areaHazardous area
6 5 4 3 2 1
7 8
9 10 11 12
13 14
Vs Vs+
20 to 35V dc
+
4/20mA
HHC*
Load
+
4/20mA
HHC*
* Hand-held communicator
I
I
Figure 6.38: MTL5042 wiring diagram and connections
Hazardous area Safe area
+
4/20mA
Vs Vs+
20 to 35V dc
4/20mA
I
I
Load
+
6 5 4
3 2 1
7 8 9
10 11 12
13 14
Safe areaHazardous area
Figure 6.37: MTL5041 wiring diagram and connections
6 5 4
3 2 1
7 8 9
10 11 12
13 14
I
I
Vs Vs+
20 to 35V dc
10kW lin
RV1
A1
A2
+
+
Terminal Function
1 Input –ve
2 Input +ve 11 Output –ve 12 Output +ve 13 Supply –ve 14 Supply +ve
Figure 6.39: Test circuit for MTL5041/2
Terminal Function
1 Current Input
2 Transmitter supply +ve
3 Common
4 Optional HHC -ve
5 Optional HHC +ve
8 Optional HHC -ve
9 Optional HHC +ve 11 Output –ve 12 Output +ve 13 Supply –ve 14 Supply +ve
Table 6.10
6.19 MTL5043 repeater power supply dual output, 4 to 20mA for 2-wire transmitters
The MTL5043 provides fully-floating dc supplies for a single conventional 2-wire 4 to 20mA transmitter located in a hazardous area and driving two safe-area loads. The MTL5043 design changed to add HART functionality at the end of 2003.
6.19.1 Wiring connections (earlier non-HART version)
See figure 6.40 for wiring connections.
6.19.2 Wiring connections (HART version)
See figure 6.41 for wiring connections.
22
INM5000-6 Jul 2010
Current Current Voltage Voltage
Output reading reading (terminal 2 with respect (terminal 2 with respect current (A1) (A1) to terminal 1) to terminal 1)
(A2) (MTL5041) (MTL5042) (MTL5041) (MTL5042)
4 to 20mA <±20µA <±10µA
20mA >16.5V >16.5V
6.19.3 Testing
Make the safe- and hazardous-area connections shown in figure 6.42 and, using RVI to vary the output current, carry out the following checks:
6.20 MTL5044 repeater power supply
The MTL5044 provides fully-floating dc supplies for two conventional 2­wire 4 to 20mA transmitters located in a hazardous area and repeating the current in two floating circuits to drive two safe-area loads.
6.20.1 Wiring connections
See figure 6.43 for wiring connections.
Safe area
Figure 6.40: MTL5043 wiring diagram and connections
Hazardous area
Safe area
Hazardous area
7 8 9
6 5 4 3 2 1
13 14
10 11 12
I
I
I
Vs Vs+
20 to 35V dc
+
4/20mA
4/20mA
Load
+
4/20mA
Load
+
HHC
HHC
7 8 9
6 5 4 3 2 1
13 14
10 11 12
I
I
I
V
Vs Vs+
20 to 35V dc
+
4/20mA
4/20mA
Load 2
+
4/20mA
Load 1
+
+
4/20mA
current
source mode
current
sink mode
Figure 6.41: MTL5043 wiring diagram and connections
Terminal Function
1 Input –ve 2 Input +ve 7 Output –ve (Ch 2 passive current sink) 8 Output –ve (Ch 2 active/+ve current sink)
9 Output +ve (Ch 2 active) 10 Output +ve (Ch 1 via 220Ω for HART apps.) 11 Output –ve (Ch 1) 12 Output +ve (Ch 1) 13 Supply –ve 14 Supply +ve
6 5 4
3 2 1
7 8
9 10 11 12
13 14
I
I
I
I
Ch 2
Ch 1
Vs Vs+
20 to 35V dc
4/20mA
Load
+
4/20mA
Load
+
+
4/20mA
+
4/20mA
Ch 2
Ch 1
Figure 6.43: MTL5044 wiring diagram and connections
Hazardous area Safe area
Output Current Voltage current reading terminal 2 with
(A2) (A1) respect to terminal 1)
4 to 20mA <±20µA
20mA >16.5V
6 5 4
3 2 1
7 8 9
10 11 12
13 14
I
I
I
Vs Vs+
20 to 35V dc
10kW lin
RV1
A1
A2
+
+
Output 1
Output 2
+
Figure 6.42: Test circuit for MTL5043
Terminal Function
1 Input –ve (Ch 1) 2 Input +ve (Ch 1) 4 Input –ve (Ch 2) 5 Input +ve (Ch 2) 8 Output –ve (Ch 2)
9 Output +ve (Ch 2) 11 Output –ve (Ch 1) 12 Output +ve (Ch 1) 13 Supply -ve 14 Supply +ve
Terminal Function
1 Input –ve 2 Input +ve 8 Output –ve (Ch 2)
9 Output +ve (Ch 2) 11 Output –ve (Ch 1) 12 Output +ve (Ch 1) 13 Supply –ve 14 Supply +ve
6.20.2 Testing
Make the safe- and hazardous-area connections shown in figure 6.44 and, using RV1 to vary the output current, carry out the following checks, first on channel 1 and then on channel 2:
6.21 MTL5045/46 isolating drivers
The MTL5045/46 isolate and pass on a 4 to 20mA signal from a controller located in a safe area to a load in a hazardous area. The MTL5046 also permits bi-directional transmission of 'smart' digital communication signals superimposed on the 4 to 20mA signal, and is provided with line fault detection (LFD).
6.21.1 Wiring connections
See figures 6.45 and 6.46 for wiring connections (MTL5045 and MTL5046 respectively).
6.21.2 Line fault detection (LFD) (MTL5046 only)
(See section 3.1.4 for definition of a line fault)
Line fault detection is signalled by an impedance change in the safe-area loop. When a line fault occurs, the impedance between terminals 11 and 12 is >100kΩ.
6.22.1 Testing
Make the safe and hazardous-area connections shown in figure 6.47 and, using the current source to vary the output current, carry out the checks shown in the table above figure 6.47.
6.22 MTL5048 analogue input/output, loop­powered isolator
The MTL5048 is a dual channel analogue input/output loop-powered isolator being powered from the safe area side. The same current flows in both hazardous and safe-area circuits and can be controlled
23
INM5000-6 Jul 2010
7 8 9
6 5 4
3 2 1
13 14
10 11 12
I
I
I
I
+
+
Ch 1
10kW lin
RV1
A1
A2
Ch 1
Ch 2
Ch 2
Vs Vs+
20 to 35V dc
+
+
Figure 6.44: Test circuit for MTL5044
6 5 4 3 2 1
7 8
9 10 11 12
13 14
Vs Vs+
20 to 35V dc
+
4/20mA
P
I
4/20mA
+
I
I
Hazardous area
Safe area
Figure 6.45: MTL5045 wiring diagram and connections
Hazardous area
Safe area
6 5 4 3 2 1
7
8
9 10 11 12
13 14
Vs Vs+
20 to 35V dc
+
4/20mA
HHC*
HHC*
* Hand-held communicator
P
I
4/20mA
+
I
I
Hazardous area
Safe area
Figure 6.46: MTL5046 wiring diagram and connections
Output Current Voltage channel 1 Voltage channel 2 current reading (terminal 2 with (terminal 5 with
(A2) (A1) respect to terminal 1) respect to terminal 4)
4 to 20mA <±20µA
20ma >16.5V
20ma >16.5V
Output Current reading Current reading current (A1) (A1)
(A2) (MTL5045) (MTL5046)
4 to 20mA <±20µA <±10µA
6 5 4 3 2 1
7 8
9 10 11 12
13 14
I
I
Vs Vs+
20 to 35V dc
+
A1
A2
+
Current source
680W
+
Figure 6.47: Test circuit for MTL5045/46
Terminal Function
1 Output –ve 2 Output +ve 4 Optional HHC -ve 5 Optional HHC +ve 8 Optional HHC -ve
9 Optional HHC +ve 11 Input –ve 12 Input +ve 13 Supply –ve 14 Supply +ve
6 5 4
3 2 1
7 8 9
10 11 12
I
I
I
I
Ch 2
+
Ch 1
+
22 35V dc
Ch 2
Ch 1
+
4/20mA
4/20mA
HHC
HHC
4/20
+
HHC
HHC
P
I
P
I
4/20
22 35V dc
Figure 6.48: MTL5048 wiring diagram and connections
Terminal Function
1 Tx– or input connection –ve (Ch 1) 2 Tx+ or input connection +ve (Ch 1) 4 Tx– or input connection –ve (Ch 2) 5 Tx+ or input connection +ve (Ch 2) 8 Output –ve or input +ve (Ch 2)
9 Output +ve or Tx supply +ve (Ch 2) 11 Output –ve or input +ve (Ch 1) 12 Output +ve or Tx supply +ve (Ch 1)
Terminal Function
1 Output –ve
2 Output +ve 11 Input –ve 12 Input +ve 13 Supply –ve 14 Supply +ve
6.24 MTL5051 serial data comms isolator
The MTL5051provides either bi-directional serial data communications from a computer system in a safe area to instrumentation in a hazardous area or data communications across a hazardous area. It is used to provide a fully floating dc supply for, and serial data communications to MTL640 text displays and MTL650 series text and graphics terminals or to other IS and non-IS instrumentation and keyboards.
6.24 .1 Wiring connections
See figures 6.52 and 6.53 and the terminal specifications in tables 6.11 and 6.12 for wiring connections. See also section 6.22.2 on hazardous­area interfacing.
6.24.2 Hazardous-area interfacing Displays/terminals: For details of interfacing with MTL640 and
MTL650 series displays/terminals (as an alternative to the MTL696 communications interface) see the appropriate product instruction manual.
24
INM5000-6 Jul 2010
from either. For smart two–wire transmitters it provides bi-directional communication signals superimposed on the 4/20mA signal. The MTL5048 can also be used for isolating and passing a 4/20mA signal from the safe area to the hazardous-area. The transmitter can be interrogated either from the operator station or by a hand-held communicator (HHC) for both the channels.The MTL5049 isolates and passes on two 4 to 20mA signals from a controller located in a safe area to two loads in a hazardous area.
6.22.1 Wiring connections
See figure 6.48 for wiring connections.
6.22.2 Testing
Make the safe- and hazardous-area connections shown in figure 6.49 and, using RV1 to vary the output current, carry out the following checks, first on channel 1 and then on channel 2.
6.23 MTL5049 two-channel isolating driver
The MTL5049 isolates and passes on two 4 to 20mA signals from a controller located in a safe area to two loads in a hazardous area.
6.23.1 Wiring connections
See figure 6.50 for wiring connections.
6.23.2 Testing
Make the safe- and hazardous-area connections shown in figure 6.51 and, using the current source to vary the output current, carry out the following checks, first on channel 1 and then on channel 2.
6
5
4
3
2
1
7
8
9
10
11
12
13
14
Vs
Vs+
20 to 35V dc
RS232, TTL or RS422
Rx Tx
5V or 12V supply Common
Tx Rx
Supply Common
Figure 6.52: MTL5051 wiring diagram (to a hazardous area)
Hazardous area Safe area
Output Current current reading (A1)
4 to 20mA <±20μA
6 5 4
3 2 1
7 8
9 10 11 12
13 14
I
I
I
I
Vs Vs+
20 to 35V dc
A1
A2
+
Current source
470W
+
+
+
Ch1
Ch2
Ch1
Ch2
Figure 6.51: Test circuit for MTL5049
RS232, or RS422
RS232, or RS422
6 5 4 3 2 1
7 8
9 10 11 12
13 14
6 5 4 3 2 1
7
8
9 10 11 12
13 14
Vs Vs+
20 to 35V dc
Vs Vs+
20 to 35V dc
Safe area
Hazardous area
Figure 6.53: MTL5051 wiring diagram (across a hazardous area)
Output Current
current (A2) reading (A1)
4 to 20mA <±80μA
6 5 4
3 2 1
7 8
9 10 11 12
13 14
I
I
I
I
P
I
4/20mA
+
P
I
4/20mA
+
+
4/20mA
+
4/20mA
Vs Vs+
20 to 35V dc
Ch 1
Ch 2
Ch 1
Ch 2
Figure 6.50: MTL5049 wiring diagram and connections
Hazardous area Safe area
Terminal Function
1 Output –ve (Ch 1) 2 Output +ve (Ch 1) 4 Output -ve (Ch 2) 5 Output +ve (Ch 2) 8 Input -ve (Ch 2)
9 Input +ve (Ch 2) 11 Input –ve (Ch 1) 12 Input +ve (Ch 1) 13 Supply –ve 14 Supply +ve
6 5 4
3 2 1
7 8
9
10 11 12
I
I
I
I
Ch 2
+
+
Ch 2
24V
+
A1
A2
Ch 1
180W
2k
RV1
W
+
+
240W
Figure 6.49: Test circuit for MTL5048
6.24.3 Testing
Remove all safe- and hazardous-area connections and apply 24V dc to terminals 13 and 14 as shown in figure 6.55. Check that the green power LED (on top of the unit) is on. Put all switches in the On position. With no load, check for nominal current of 60mA ±5mA at terminal 14. Correct operation of the communication modes is indicated by signals received and/or transmitted.
6.25 MTL5053 isolator/power supply for
31.25kbit/s fieldbuses
The MTL5053 has been specifically developed to extend 31.25kbit/s (H1) fieldbus networks into hazardous areas. It provides power, communication and IS isolation to devices powered through the signal conductors. The MTL5053 complies with the requirements of Fieldbus Foundation™ specified power supply Type 133 (IS power supply).
To comply with fieldbus standards, each bus must be terminated at both ends. MTL's FBT1-IS or FCS-MBT fieldbus terminators (see section 6.33) can be supplied for this purpose or, for installations in which the safe­area bus length is small, the MTL5053 includes an internal safe-area terminator which is enabled by a switch located on the top of the unit.
For network and termination criteria, check applicable fieldbus standards and specification
IEC 61158-2, ISA-S50.02 for 31.25kbit/s fieldbus systems, Foundation™ Fieldbus 31.25kbit/s Physical Layer Profile Specification FF-816
and MTL's Application Brief AB002.)
6.25.1 Wiring connections
See figure 6.56 for wiring connections and refer to MTL's Application Brief AB002.
Note: To assist the process of terminating cable screens, screw terminals have been provided in terminal positions 3 and 6 and 7 and 10. Please note, however, that there is no internal connection for these terminals so they are not earthed.
25
INM5000-6 Jul 2010
Across hazardous areas: For communication across hazardous
areas MTL5051 devices are used in pairs to transfer bi-directional full­duplex data across hazardous areas, as shown in figure 6.53. Current switching is used to minimise the bandwidth-limiting effects of long cables.
The maximum baud rate in this mode is the lesser of 19.2k baud or the cable-related rate produced by the following formula.
Remote signalling baud rate formula, for back-to-back mode across a hazardous area:
max baud rate = K/(RxCxL
2
)
where K = 0.25 (constant)
R = cable resistance (Ω/m) C = cable capacitance (F/m) L = length (m)
For example, with a 2km cable of 100pF/m capacitance and 40mΩ/m resistance, the maximum baud rate = 0.25/(40mΩ x 100pFx 2km
2
) = 15k baud. This assumes that the cable is 2 cores plus screen, with the screen used for the 'common' connection.
RS232-level devices: Communication with RS232-level interfaces, such as a suitably certified IS keyboard, mouse, etc, is achieved by using one or more MTL5051 units as required by the IS device.(TTL level interfaces are accommodated by the TTL compatibility of RS232 receivers.)
The supply to IS equipment at terminal 2 can be set to either 5V or 12V, by a switch located on top of the unit, as follows:
+12V mode 12.0V ±5% (load <23mA) +12V mode 8.0V min (load >23mA to <50mA) +5V mode5.6V ±5% (load >23mA to <50mA)
Note: the normal RS232 limitations of bandwidth versus cable length are applicable. As a rule of thumb, speed (baud) x length (metres) <150,000.
6 5 4
3 2 1
7 8
9 10 11 12
13 14
dc supply
 +
Figure 6.55: Test circuit for MTL5051
Terminal Function
1 Hazardous-area fieldbus device(s) connection –ve 2 Hazardous-area fieldbus device(s) connection +ve 4 Optional HHC connection –ve
5 Optional HHC connection +ve 8 & 11 Safe-area fieldbus device(s) connection –ve 9 & 12 Safe-area fieldbus device(s) connection +ve
13 Supply –ve 14 Supply +ve
FBT1 fieldbus terminator
**
6 5 4
3 2 1
7 8
9 10 11 12
13 14
T
*Hand-held communicator ** See section 6.33 for details of FBT1
T
Vs+
Vs
20 to 35V dc
HHC*
Fieldbus devices
T
FBT1 fieldbus terminator
**
+
+
devices
Fieldbus devices
Figure 6.56: MTL5053 wiring diagram and connections
Hazardous area Safe area
2a 2b
ON
MTL5051
PWR
1a 1b
Figure 6.54: Top label, MTL5051
Table 6.11 (see also figure 6.54)
Table 6.12 (see also figure 6.52)
MTL5051 MTL640 MTL650 Comms Other IS
Terminals mode mode mode devices
1 Common Common Common Common 2 V signal 12V - 5V/12V 3 I return Rx Rx ­4 - Tx Tx ­5---Tx
6---Rx
Switch
1a On Off Off Off 1b On On On Off/On
Terminals RS232 mode TTL mode RS422 mode
7 - - Rx ­8 - - Rx+ 9 - Tx Tx+
10 Tx - Tx­11 Common Common Common 12 Rx Rx ­13 Supply -ve Supply -ve Supply -ve 14 Supply +ve Supply +ve Supply +v
Switch
2a Off On On 2b On Off Off
26
INM5000-6 Jul 2010
6.25.2 Testing
Make the safe and hazardous-area connections shown in figure 6.56 and, substituting appropriate resistors at R
test
, carry out the following
checks.
6.26 MTL5061 two-channel loop-powered fire/smoke detector interface
The MTL5061 isolates two conventional fire and smoke detectors located in hazardous areas. The triggering of a detector causes a corresponding change in the safe-area circuit. The unit has reverse input polarity, and 'non-fail' earth fault detection on either line can be provided.
6.26.1 Wiring connections
See figure 6.59 for wiring connections.
6.26.2 'No-fail' earth fault protection
Protection is enabled by connecting earth leakage detectors, such as MTL2220s (not CE marked), to the MTL5061; via terminal 3 or 6, or both. To maintain isolation between the two channels, separate earth leakage detectors are required. If a fault on either line of each channel is detected, the unit continues working.
Note: The MTL2220 introduces a 100µA, 1Hz ripple to the field circuit.
6.26.3 Testing
Make the safe- and hazardous-area connections shown in figure 6.60 and, using RV1 to vary the output current, carry out the following check for both channel 1 and channel 2:
6.27 MTL5074 temperature converters, THC or RTD input
The MTL5074 converts low-level signals from temperature sensors located in a hazardous area into 4 to 20mA signals for driving safe-area loads.
Note: The earlier model MTL5073 had an internal link between terminals 11 and 13. The MTL5073 model is discontinued.
6.27.1 Wiring connections
See figure 6.61 for wiring connections.
Note: for THC inputs requiring cold-junction compensation, a HAZ-CJC hazardous-area connector (with integrated CJC sensor) is required not a HAZ1-3 signal plug.
6 5 4
3 2 1
7 8
9
10 11 12
I
I
I
I
Ch 2
Fire detectors
+
To earth leakage detector
Ch 1
Fire detectors
+
6 to 35V dc
6 to 35V dc
Ch 2
Ch 1
+
+
Figure 6.59: MTL5061 wiring diagram and connections
Hazardous area Safe area
Output Current current reading
(A2) (A1)
10 to 40mA <±400µA
6 5 4
3 2 1
7 8
9
10 11 12
I
I
I
I
Ch 2
+
+
Ch 2
24V
+
A1
A2
Ch 1
180W
2k
RV1
W
+
+
Figure 6.60: Test circuit for MTL5061
Hazardous area Safe area
Figure 6.61: MTL5073/74 wiring diagram
7 8 9
10 11 12
13 14
6 5 4
3 2 1
mV
I
Vs Vs+
20 to 35V dc
+
mV
Load
4-wire 3-wire
+
4/20mA
MTL5053
PWR
TERMINATOR
Figure 6.58: Top label, MTL5053
Voltage across
R
test
terminals 2 and 1 (V1)
Open-circuit 17.8 < V
1
<19V
220Ω 11.5V <V1<13.5V
10Ω V
1
<5V
6 5 4
3 2 1
7 8
9 10 11 12
13 14
T
V
V
Vs+
Vs
20 to 35V dc
R
test
V
1
+
Figure 6.57 : Test circuit for MTL5053
Terminal Function
1 THC/EMF/RTD input –ve 3 THC/EMF/RTD input +ve 4 3-wire RTD input –ve
5 4-wire RTD input +ve 11 Output –ve 12 Output +ve 13 Supply –ve 14 Supply +ve
Terminal Function
1 Output –ve (Ch 1) 2 Output +ve (Ch 1) 3 Earth leakage detection (Ch 1) 4 Output –ve (Ch 2) 5 Output +ve (Ch 2) 6 Earth leakage detection (Ch 2) 8 Input –ve (Ch 2)
9 Input +ve (Ch 2) 11 Input –ve (Ch 1) 12 Input +ve (Ch 1)
A switch located on top of the module enables or disables a safety drive in the event of thermocouple burnout or cable breakage; a second switch permits the selection of upscale or downscale drive as required.
6.28.1 Safety drive
Please note that the safety drive on the MTL5081 responds to line breakage (an open circuit) or in the event of thermocouple burnout. It does not provide detection of a short circuit. It can, however, be set upscale or downscale. Selection is made by switches located on top of the module (see figure 6.64)
* Note that the above statement Vout = Vin is subject to transfer accuracy and drift specified in the MTL Intrinsic Safety catalogue.
6.28.2 Wiring connections
See figure 6.65 for wiring connections.
27
INM5000-6 Jul 2010
6.27.2 Testing
Default parameters for the MTL5074, unless custom configured by MTL, are:
Input type 3-wire RTD Linearisation enabled Units °C Cj compensation disabled Damping value 0 sec Smoothing value 0 sec Output zero 0°C Output span 250°C Tag and description fields clear Open circuit alarm high Transmitter failure alarm low Cj failure alarm low Line frequency 50Hz
Note: the configuration of MTL5074 cannot be changed without the aid
of a PCS/PCL45 configurator (see INM073A Connection and Configuration Manual for full details). These devices also enable more comprehensive testing of the converters.
Make the safe- and hazardous-area connections shown in figure 6.62. Note that the range of the dc ammeter 'A' must be suitable for 4 to 20mA currents and the variable resistor 'R' should have a range of 0­200Ω and, ideally, should be a decade resistance box. Switch on the power supply and check that the green power LED comes on (if it flashes, the unit is incorrectly configured or the test wiring setup is faulty). Check that the loop output current at 'A' varies as the variable resistance at 'R' is altered and check the table below for particular settings (194Ω @250°C and 100Ω @0°C for a PT100 sensor).
6.28 MTL5081 millivolt isolator
The MTL5081 takes a low level dc signal from a voltage source in a hazardous area, isolates it and passes it to a receiving instrument located in the safe area. Although used with thermocouples, this unit does not have cold junction compensation facility. It is intended for use with thermocouples utilising external cold junction compensation. When using with thermocouples, in order to minim ise the temperature gradient between the safe- and hazardous-area terminals, it is recommended that the units are mounted on vertical DIN rail (see figure 6.63).
Input Loop output Power
resistance current LED
(R) (A) (green)
194Ω 20mA On 100Ω 4mA On
Open circuit 22.25mA Flashing
Short circuit 22.25mA Flashing
7 8 9
10 11 12
13 14
6 5 4
3 2 1
mV
I
20 to 35V dc
Note: The MTL5073 (which is no longer manufactured) had an internal link between terminals 11 and 13.
Vs Vs+
+
Loop output 4 to 20mA
A
+
VR1
200W lin
Figure 6.62: Test circuit for MTL5074
Figure 6.63: MTL5000 Series units mounted on vertical DIN rail
ON
MTL5081
PWR
LF PR CH1
ON
OFF
+
SAFETY
DRIVE
SAFETY DRIVE LINE
ON/OFF +/- BREAKAGE Vout
OFF N/A NO Vin* OFF N/A YES undetermined ON + NO Vin* ON + YES >+100mV ON – NO Vin* ON YES <–100mV
Figure 6.64: Top label of MTL5081 showing positions of safety drive switches and an explanation of their functions
Terminal Function
1 THC/mV input –ve
2 THC/mV input +ve 11 Output –ve 12 Output +ve 13 Supply –ve 14 Supply +ve
7 8 9
6 5 4 3 2 1
13 14
10 11 12
mV
mV
Vs+
Output
Vs
20 to 35V dc
mV
+
+
Figure 6.65: MTL5081wiring diagram and connections
Hazardous area
Safe area
INM5000-6 Jul 2010
6.29.1 Input mode selection
The unit is factory set for 3-wire RTD mode. To select 2-wire or 4-wire RTD modes, configure the switches located on the top of the unit in accordance with the diagrams in figure 6.68.
6.29.2 Wiring connections Warning: Check polarity of terminals used for safe-area connections.
Safe-area terminals 9, 10, 11 and 12 are unipolar so it is essential to select a positive terminal on the MTL5082 for connection to the positive of the RTD input card.
See figure 6.67 for wiring connections.
6.29.3 Testing
Make the safe- and hazardous-side connections shown in figure 6.69, ensuring that the configuration switches on top of the unit are set to 3­wire RTD input mode (see figure 6.68). Carry out the following tests and checks using a resistance box, with a range of 0 to 400Ω, and a voltmeter, covering the range 47.0mV to 2.100V.
1. Set the resistance box to any value in the range 10Ω to 400Ω, switch on the power supply and check that the green power (PWR) LED comes on and remains steady. If the LED is flashing after 5 seconds, either the test-wiring set-up is faulty or the unit is faulty.
2. Check that the output voltage changes as the input resistance is varied within the range 10Ω to 400Ω.
3. Short circuit the input and check that the output voltage is 51.6mV after 5 seconds.
4. Open circuit the input and check that the output voltage is 2.071V after 5 seconds and that the green PWR LED is flashing.
5. Set the input resistance to 200Ω and check that the output voltage settles to 1.0V ±32mV.
6.30 MTL5099 dummy isolator
The MTL5099 is used with other MTL5000 Series units to provide termination and earthing facilities for unused cable cores from hazardous areas.
6.30.1 Wiring connections
See figure 6.70 for wiring connections.
6.28.3 Testing
Make the safe and hazardous-area connections shown in figure 6.66
Note: A millivoltmeter capable of measuring to within 1µV should be used for V1.
Carry out the checks shown in table 6.13, using RV1 to vary the output at V2 for the first test.
Table 6.13
6.29 MTL5082 resistance isolator
The MTL5082 connects to a 2-, 3- or 4-wire resistance temperature device (RTD) or other resistance located in a hazardous area, isolates it and repeats the resistance to a monitoring system in the safe area. The module drives upscale in the case of open circuit detection. The number of wires which can be connected on the safe-area side of the unit is independent of the number of wires connected on the hazardous-area side.
The module is intended typically, but not exclusively, for use with Pt100 3­wire RTDs. Switches located on top of the module allow selection of 2-, 3­or 4-wire connection. The MTL5082 is also used as an alternative, non­configurable MTL5074, for use in RTD applications where a resistance input is preferred or needed instead of 4 to 20mA.
2
4
3
4
2
3
MTL5082
PWR
WIRE
Switch positions
4-wire 2-wire 3-wire
Figure 6.68: Top label, MTL5082, showing positions of configuration switches and switch-position configurations for different input modes
SAFETY DRIVE
ON/OFF +/- LINK V1 V2
OFF N/A CLOSED <0.05mV 0 V2 50 mV ON + OPEN N/A > +100 mV ON - OPEN N/A < -100 mV
+
4-wire 3-wire 2-wire
7 8 9
6 5 4 3 2 1
13 14
10 11 12
W
W
+
+
Vs+
Vs
20 to 35V dc
Figure 6.67: MTL5082 wiring diagram and connections
Hazardous area Safe area
7 8 9
6 5 4 3 2 1
13 14
10 11 12
W
W
Vs+
Vs
20 to 35V dc
V
Voltmeter
+
+
Current Source
5.0mA ± 150µA
4-wire 3-wire 2-wire
+
Resistance
box
Figure 6.69: Test circuit for MTL5082
28
Terminal Function
1 RTD input –ve 3 RTD input +ve 4 3-wire RTD input –ve 5 4-wire RTD input +ve
9 RTD output –ve 10 RTD output +ve 11 RTD output –ve 12 RTD output +ve 13 Supply –ve 14 Supply +ve
7 8 9
6 5 4 3 2 1
13 14
10 11 12
mV
mV
Vs+
+
+
Vs
20 to 35V dc
39kW
RV1
100W
V1
V2
Figure 6.66: Test circuit for MTL5081
6.31 MTL5113P fail-safe switch/proximity detector interface
With the MTL5113P, a fail-safe switch/proximity detector located in the hazardous area can control an isolated, fail-safe electronic output. The MTL5113P unit also provides line-fault detection alarm contacts.
The MTL5113P is for use with P + F TÜV-approved fail-safe sensors. Correct operation of fail-safe output and LFD, where applicable, is
indicated by amber and red LEDs on top of the unit. Amber is ON when fail-safe output is energised. Red is ON if a line fault is detected. Fail-safe output is OFF if the incorrect sensor current, an open circuit or a short circuit is present in the sensor circuit.
MTL5113P input/output characteristics are shown in table 6.14.
Table 6.14
6.31.1 Wiring connections
See figure 6.71 For wiring connections.
Note: Switch-type sensors must always be fitted with resistors, as shown.
*
Series resistor should be in the range 1k3Ω- 1k5
Ω
6.31.2 Line fault detection
(See section 3.1.4 for definition of a line fault
)
If an input line fault (open- or short-circuit) is detected, a red LED on top of the unit goes ON, the LFD contacts open and the LFD output is de­energised providing an alarm output. The fail-safe output is also de­energised and the amber output status LED on top of the unit goes OFF.
29
INM5000-6 Jul 2010
6.31.3 Testing
Make the safe- and hazardous-side connections shown in figure 6.72. With an ohmmeter, check that the status of the outputs is as follows:
6.32 MTL5314 trip amplifier for 2– or 3– 2 wire transmitters
The MTL5314 connects to a 2– or 3– wire 4 to 2mA transmitter or current source located in the hazardous area. It supplies one or two configurable alarm signals to the safe area via changeover relays. Each relay may be configured individually to signal an alarm condition when the input signal is greater than or less than a pre-set value.
In addition, the MTL5314 can be connected in series to the hazardous­area side of an MTL5042 4 to 20mA repeater power supply (or equivalent device) to provide two trip alarm outputs direct from the transmitter signal (see schematic diagram). Looping the transmitter signal through the MTL 5314 (via terminals 1 and 3) does not affect HART® communications. Terminals 1 and 3 meet clause 5.4 of EN50020: 1994 and have the following parameters: U ≤ 1.5V, I 0.1A, P 25mW. They can be connected without further certification into an IS loop with open circuit voltage of not more than 28V. See certificate for further details.
6.32.1 Wiring connections
See figure 6.73 for wiring connections. If terminals 1 and 3 provide a 4 to 20mA loop to a HART transmitter,
HART communication can be superimposed on the 4 to 20mA signal.
Note: Reactive loads must be adequately suppressed
.
Unused hazardous­area cores
3 2 1
6 5 4
7 8 9
10 11 12
13 14
Unused safe-area cores
Figure 6.70: MTL5099 wiring diagram and connections
Hazardous area Safe area
Input value in Fail-safe Operation LFD contacts sensor circuit output
2.9mA < Is < 3.9mA ON Normal Closed
Is<1.9mA and Is>5.1mA OFF Normal Closed
Is<50µA OFF Broken line Open
Is>66mA OFF Shorted line Open
Terminal Function
1 Input –ve 2 Input +ve 3 Output –ve
7 Output +ve 10 LFD 11 LFD 13 Supply –ve 14 Supply +ve
Figure 6.71: MTL5113P wiring diagram and connections
Hazardous area Safe area
Input Fail-safe Line fault
output contacts output
open-circuit de-energised open de-energised short-circuit de-energised open de-energised 1k4Ω energised closed energised 10kΩ de-energised closed energised
6 5 4
3 2 1
7 8 9
10 11 12
13 14
+
+
Failsafe output
LFD
Vs Vs+
20 to 35V dc
SW
1k4W 10kW
Figure 6.72: Test circuit for MTL5113P
Terminal Function
1 Hazardous-area core 2 Hazardous-area core 3 Hazardous-area core 4 Hazardous-area core 5 Hazardous-area core 6 Earth 7 Safe-area core 8 Safe-area core
9 Safe-area core 10 Safe-area core 11 Safe-area core 12 Safe-area core
6 5 4
3 2 1
7 8 9
10 11 12
13 14
+
+
Failsafe output
LFD
Vs Vs+
20 to 35V dc
1k4W*
10kW
Resistors are required for switch inputs
30
INM5000-6 Jul 2010
6.32.2 Trip calibration
Switches and multiturn potentiometers for setting the trip points are located on top of the unit (see figure 6.74). For each of channels A and B:
i Set trip switch to H (high) or L (low) as required (see table 6.15
for relay operation). ii Set input current to the required value for trip-point. iii Adjust SET A/SET B until LED A/B is on: then slowly adjust until
LED goes out. iv Relays are energised in normal operation and de-energised when
tripped. A lit LED shows the safe condition (not tripped).
Table 6.15
– = Either option = LED On • = LED Off
6.32.3 Testing
Make the safe- and hazardous-area connections shown in figure 6.75 and carry out the following procedure:
a Set the current source or sink to 12mA b Adjust each trip potentiometer until the associated LED just
extinguishes.
c With sources of 11.5mA and 12.5mA carry out the following
checks:
6 5 4
3 2 1
7 8 9
10 11 12
13 14
6 5 4
3 2 1
7 8 9
10 11 12
13 14
Vs Vs+
20 to 35V dc
Trip B
Trip A
Vs Vs+
20 to 35V dc
+
4/20mA
Load
+
4/20mA
* Hand-held communicator
6 5 4 3 2 1
7 8
9 10 11 12
13 14
I
I
Vs Vs+
20 to 35V dc
Trip B
Trip A
+
HHC*
HHC*
+
4/20mA
4/20mA
+
+
MTL5314
MTL5042
MTL5314
Figure 6.73: MTL5314 wiring diagram and connections
Terminal Function
1 Current input 2 Transmitter supply +ve 3 Common 7 Trip B (NC) 8 Trip B (COM)
9 Trip B (NO) 10 Trip A (NC) 11 Trip A (COM) 12 Trip A (NO) 13 Supply –ve 14 Supply +ve
Hazardous area
Safe area
H H
SET
A
MTL5314
PWR
LF PR CH1
ON
L L
SET
B
A B
Figure 6.74: Top label, MTL5314, showing positions of trip switches and multiturn potentiometers
Trip Operation PWR A or B Relay contacts switch LED LED 11-12 10-11 A or B 8-9 7-8
H (high) Input >Trip setting open closed H (high) Input <Trip setting ✫✫closed open
L (low) Input >Trip setting ✫✫closed open L (low) Input <Trip setting open closed
open closed
6 5 4
3 2 1
7 8 9
10 11 12
13 14
Vs Vs+
20 to 35V dc
Trip B
Trip A
Source
or
sink
I
I
+
High alarm Low alarm
Relay Relay
LED 11-12 10-11 LED 11-12 10 -11
Current 8 - 9 7 - 8 8 - 9 7 - 8
11.5mA On Closed Open Off Open Closed
12.5mA Off Open Closed On Closed Open
Figure 6.75: Test circuit for MTL5314
31
INM5000-6 Jul 2010
6.33 MTL5344 Repeater power supply
The MTL5344 provides fully-floating dc supplies for two conventional 2­wire 4 to 20mA transmitters located in a hazardous area and repeats the current in two floating circuits to drive two safe-area loads.
Note that although this module is similar in function to the MTL5044, the safety description parameter are very different. Refer to the datasheet and the ATEX certificate available from the MTL website.
6.33.1 Wiring connections
See figure 6.76 for wiring connections.
6.33.2 Testing
Make the safe- and hazardous-area connections shown in figure 6.77 and, using RV1 to vary the output current, carry out the following checks, first on channel 1 and then on channel 2:
6 5 4
3 2 1
7 8
9 10 11 12
13 14
I
I
I
I
Ch 2
Ch 1
Vs Vs+
20 to 35V dc
4/20mA
Load
+
4/20mA
Load
+
+
4/20mA
+
4/20mA
Ch 2
Ch 1
Figure 6.76: MTL5344 wiring diagram and connections
Hazardous area Safe area
Terminal Function
1 Input –ve (Ch 1) 2 Input +ve (Ch 1) 4 Input –ve (Ch 2) 5 Input +ve (Ch 2) 8 Output –ve (Ch 2)
9 Output +ve (Ch 2) 11 Output –ve (Ch 1) 12 Output +ve (Ch 1) 13 Supply -ve 14 Supply +ve
7 8 9
6 5 4
3 2 1
13 14
10 11 12
I
I
I
I
+
+
Ch 1
10k
W
lin
RV1
A1
A2
Ch 1
Ch 2
Ch 2
Vs Vs+
20 to 35V dc
+
+
Figure 6.77: Test circuit for MTL5344
Output Current Voltage channel 1 Voltage channel 2 current reading (terminal 2 with (terminal 5 with
(A2) (A1) respect to terminal 1) respect to terminal 4)
4 to 20mA <±20µA
20ma >14V
20ma >14V
6.34 MTL5349 two-channel isolating driver
The MTL5349 isolates and passes on two 4 to 20mA signals from a controller located in a safe area to two loads in a hazardous area.
Note that although this module is similar in function to the MTL5049, the safety description parameter are very different. Refer to the datasheet and the ATEX certificate available from the MTL website.
6.34.1 Wiring connections
See figure 6.78 for wiring connections.
6.34.2 Testing
Make the safe- and hazardous-area connections shown in figure 6.79 and, using the current source to vary the output current, carry out the following checks, first on channel 1 and then on channel 2.
6 5 4
3 2 1
7 8
9 10 11 12
13 14
I
I
I
I
P
I
4/20mA
+
P
I
4/20mA
+
+
4/20mA
+
4/20mA
Vs Vs+
20 to 35V dc
Ch 1
Ch 2
Ch 1
Ch 2
Figure 6.78: MTL5349 wiring diagram and connections
Hazardous area Safe area
Terminal Function
1 Output –ve (Ch 1) 2 Output +ve (Ch 1) 4 Output -ve (Ch 2) 5 Output +ve (Ch 2) 8 Input -ve (Ch 2)
9 Input +ve (Ch 2) 11 Input –ve (Ch 1) 12 Input +ve (Ch 1) 13 Supply –ve 14 Supply +ve
Output Current current reading (A1)
4 to 20mA <±20μA
6 5 4
3 2 1
7 8
9 10 11 12
13 14
I
I
I
I
Vs Vs+
20 to 35V dc
A1
A2
+
Current source
470W
+
+
+
Ch1
Ch2
Ch1
Ch2
Figure 6.79: Test circuit for MTL5349
6.35 MTL5991 24V dc power supply
The MTL5991 provides a convenient source of power for MTL5000 Series units in locations where a dc supply is not readily available. The 2A capability at 24V dc is sufficient to drive at least fifteen (15) MTL5000 Series modules, or more in appropriate combinations (see table 6.16), and the wide mains power supply range makes this unit universally applicable.
Table 6.16
Note:The maximum current drawn from the load unit is taken at 24V. The maximum current drawn from the MTL5991 was taken to be 1.6A
6.35.1 Wiring connections
See figure 6.80 for wiring connections.
32
INM5000-6 Jul 2010
Current
MTL5000 unit Drawn mA Maximum
(Vs=24V) number of units
MTL5011B 35 46 MTL5012 30 53 MTL5014 45 36 MTL5015 44 36 MTL5017 50 32 MTL5018 60 27 MTL5023 100 16 MTL5024 100 16 MTL5031 80 20 MTL5032 65 25 MTL5040 95 17 MTL5041 70 23 MTL5042 75 21 MTL5044 110 15 MTL5045 50 32 MTL5046 65 25 MTL5048 40 35 MTL5049 65 25 MTL5051 90 18 MTL5074 68 24 MTL5081 20 80 MTL5082 55 29 MTL5113P 70 23 MTL5314 85 19 MTL5344 122 13 MTL5349 67 24
WARNING
Segregation between hazardous- and safe-area wiring must always be maintained
4
5
6
7 8
+
1
2
3
Figure 6.80: MTL5991 wiring diagram and connections
Terminal Function
1 AC Line 2 Earth 3 AC neutral 4 +24V 5 +24V 6OV 7OV 8 Do not use
Safe area
6.35.2 Testing
Using the terminal assignments shown in figure 6.81, make the following tests and checks.
1. Connect a supply voltage of between 85V and 264V ac to the live and neutral terminals. Check that the voltage measured across these terminals is within the range 85V to 264V ac.
2 With no load connected to the unit's output, measure, in turn, the
voltage between terminals 4 and 6 then 5 and 7. Check that the measurements are in the range 23.64V to 24.36V.
3 Connect to the output, a load that draws up to 2A from a supply
voltage between 105V and 264V ac, and draws 1.7A when the supply voltage is less than 105V ac. Measure, in turn, the voltage across terminals 4 and 6 and 5 and 7. Check that these measurements are in the range 23.64V to 24.36V with a ripple not greater than 100mV.
6.36 MTL5995 fieldbus power supply for
31.25kbit/s fieldbuses
The MTL5995 is a general purpose power supply unit designed for use in 31.25kbit/s (H1) fieldbus systems. The MTL5995 complies with the requirements of Fieldbus Foundation™ power supply Type 131 (non-IS supply intended for feeding an IS barrier).).
To allow adequate heat dissipation under all likely thermal conditions, it is recommended that MTL5995s are installed on DIN rail with a 10mm space between adjacent units. MTL MS010 10mm DIN-rail module spacers are available for this purpose (see section 4.2.1).
To comply with fieldbus standards, each bus must be terminated at both ends. MTL's FBT1-IS or FCS-MBT fieldbus terminators (see section 6.37) can be supplied for this purpose or, for installations in which the MTL5995 is located at one end of the fieldbus trunk, it includes an internal terminator which is enabled by a yellow switch (B) located on the base of the unit (see figure 6.82). A second, red switch (A) in the base of the unit should be kept in the normal mode position.
(For network and termination criteria
, see applicable fieldbus standards
and specification
IEC 61158-2, ISA-S50.02 for 31.25kbit/s fieldbus systems, Foundation™ Fieldbus 31.25kbit/s Physical Layer Profile Specification FF-816
and MTL's Application Brief AB001.)
4
5
6
L
E
N
7 8
+
Figure 6.81: Terminal assignments for MTL5991
A
B2
1
NORMAL MODE SW1
TERMINATOR OUT SW2
NOT USED
Red
Yellow
TERMINATOR IN
Label face
Base of unit
Figure 6.82: Functions of switches on the base of an MTL5995
and specifications are
IEC61158-2, ISA-S50.02 for 31.25kbit/s fieldbus systems and FOUNDATION™ Fieldbus 31.25kbit/s Physical Layer Profile Specification FF816.
Additional information on fieldbus termination can be found in
MTL's
AB001
and
AB002
application briefs.
6.37.1 Package details
The FBT1-IS terminator is designed for mounting on 35 x 7.5 mm or 35 x 15 mm DIN rail to EN50022.
6.37.2 Fitting FBT1-IS
Orientate the FBT1-IS as shown in Figure 6.82a and locate it on the DIN rail. Using the DIN rail edge as the pivot point, press down the other end until the package clicks into place on the other side of the rail.
6.37.3 Removal
Removal requires a screwdriver or similar flat blade. Locate the screwdriver into the slot provided in the fixing bracket on the 'device' side of the spur connector (see Figure 6.86). Carefully lever towards the spur connector body until the mounting is released from the DIN rail and lift it off the rail.
6.37.4 Connections
The +, - and cable screen (S) connections are indicated in Figure 6.87. The terminals will accept cables with a cross sectional area of up to 4 mm2. A straight blade screwdriver with a maximum blade width of 3.5 mm is required to operate the terminals. The recommended tightening torque is <0.9 Nm.
6.36.1 Wiring connections
See figure 6.83 for wiring connections and refer to MTL's Application Brief AB001.
Note: To assist the process of terminating cable screens, terminals 7 and 10 are linked internally. Please note however that these terminals are not earthed.
**Where supply voltage is 20 to 30V dc, ambient temperature limits are –20°C to 60°C. If supply voltage is 20 to 35V dc, the ambient temperature limits are –20°C to +55°C.
Table 6.17
**Where supply voltage is 20 to 30V dc, ambient temperature limits are
-20°C to 60°C. If supply voltage is 20 to 35V dc, the ambient temperature limits are -20°C to +55°C.
6.36.2 Testing
Make the safe-area connections shown in figure 6.84 and, substituting appropriate resistors for R
test
, carry out the checks shown in table 6.17
6.37 FBTI-IS fieldbus terminator
The FBT1-IS is a DIN rail mounting unit that provides the correct termination for fieldbus circuits in either safe or hazardous areas.
The unit is certified for use in Zone 0, IIC, T4 locations, and fully complies with the electrical characteristics requirements of section
22.7.5 of appropriate fieldbus standards. Applicable fieldbus standards
33
INM5000-6 Jul 2010
7 8 9
10 11 12
13 14
PSU
Switch
T
Fieldbus
T
T
+
20 to 30V dc
Vs Vs+
+
FBT1* Fieldbus terminator
Fieldbus device(s)
FBT1* Fieldbus terminator
Safe area
Figure 6.83: MTL5995 wiring diagrams and connections
R
test
Current (I1) Voltage across terminals
8 and 9 (V1)
1.8kΩ - 18.6V ≤ V
1
19.4V
56Ω 10W ~ 340mA -
0Ω < 500mA -
7 8 9
10 11 12
13 14
PSU
T
+
20 to 30V dc**
Vs Vs+
+
R
test
R
test
I
1
6
5
4
3
2
1
Figure 6.84: Test circuit for MTL5995
S
S
+
+
F
E
GH
D
C
AB
63 mm
18 mm
64 mm
Figure 6.81: Terminator/Spur connector package
a) b )
Figure 6.86: a) fitting and b) removal
FBT1-IS
S
S
+
+
T
CAD
H FE
Figure 6.87: Terminal assignments
Terminal Function
7 Internally linked to 10 8 & 11 Safe-area fieldbus device(s) connection –ve 9 & 12 Safe-area fieldbus device(s) connection +ve
10 Internally linked to 7 13 Supply –ve 14 Supply +ve
7 MAINTENANCE
Note: Limit tests and routine maintenance to those described in this
section and section 4. Return any isolator identified as faulty to the MTL group company or representative from which it was purchased, for repair or replacement.
7.1 Routine maintenance
Occasionally check the general condition of the installation to make sure that no deterioration has occurred. At least once every two years (and more frequently for particularly harsh environments), check that:
isolators are of the types specified in the relevant documentation;
isolators and connectors are correctly and legibly tagged,
connectors are plugged into the corresponding isolators and tag details given comply with the relevant documentation;
isolators are securely clipped to the DIN rail;
all cable connections are properly made to the plugs;
all plugs are fully inserted;
all connecting cables are of the specified type and rating, are
correctly routed and segregated (particularly when fitted in enclosures), and are not frayed or otherwise damaged;
all cable screens are properly earthed;
there is no sign of damage or corrosion.
7.2 Enclosures
The only maintenance needed for enclosures is cleaning and periodic visual inspections. Clean external surfaces only, using soap and water; do not use chemical solvents or proprietary cleaning fluids. Every year (more frequently in harsh environments), inspect enclosures and check that:
they are attached securely to their mountings;
any accumulation of water inside has been removed (using the
drain plug, if fitted);
cable gland nuts are tight;
there are no signs of any damage;
all connections are properly made.
8 OTHER USEFUL DOCUMENTATION
MTL Hazardous Area Products Catalogue AB001 Application Brief AB002 Application Brief INA5000 DofC and ATEX Safety Instructions INM073A Connection and Configuration Manual
Customer drawings
CD5001-30 MTL5000 Power Bus Kits CD5001-41 MTL5000 Series Tagging and Earth Rail
Accessories
CD5001-42 MTL5000 Tag and Earth Accessories IEC 61158-2 ISA-S50.02 for 31.25kbit/s fieldbus systems F
OUNDATION™ Fieldbus 31.25kbit/s Physical Layer Profile
Specification FF-816
HART® is a registered trademark of the HART Communication Foundation Fieldbus Foundation™ is a trademark of Fieldbus Foundation, Austin, Texas, USA F
OUNDATION
™ is a trademark of Fieldbus Foundation, Austin, Texas, USA
34
INM5000-6 Jul 2010
WARNING
If an isolator is faulty, DO NOT make repairs or modifications as these may affect the intrinsic safety of the unit.
35
INM5000-6 Jul 2010
9 APPENDIX A - INSTRUCTIONS FOR
MTL5500 SERIES
9.1 MTL5521 rotational speed monitor
A rotational speed monitor with over- and under-speed monitoring, has proximity detector input, conforming to NAMUR/DIN 19234 standard. Easy configuration is by two push buttons on the top of the unit and the unit has a frequency range of 0.001Hz to 10kHz (0.06 to 600000 min-
1
). A liquid crystal display on the top of the unit displays the current frequency. The 0/4 to 20mA current output is proportional to the rotational speed, and the unit has SPDT relay output for over- and under-speed indication. Start-up delay is initiated by the closure of a normally open contact. Three power supply versions are available – 24V DC, 115V AC and 230V AC.
9.1.1 Wiring connections
Hazardous-area terminals 5 & 6 NAMUR sensor input connection. 7 & 8 Normally open switch contact for Start-up delay
function. Safe-area terminals 9 & 13 0/4 to 20mA analogue output. 10, 11 & 12 Over- and under-speed relay output. 15 & 16 Power supply connection.
9.1.2 LED indications.
Pulse indication:
Yellow - indicates an input pulse
Red - input circuit fault Pwr Supply voltage:
Green - device is operational K
1
Limit value relay
Yellow - relay energized
9.1.3 Mounting instructions
The rotational speed monitor is suitable for either panel or DIN-rail mounting. A minimum spacing of 3.5mm between the modules is required when the modules are mounted horizontally. There is no minimum spacing for vertically mounted units.
9.1.4 Configuration (figures 9.1 and 9.2)
Buttons S1 and S2 on the top of the unit are used to configure the individual parameters of the unit. The required parameter Id, tb etc is selected by pressing S2 until the parameter to be configured is displayed and then, S1 must be pressed and held for approximately 3 seconds. The left decimal will start flashing and the value can then be set, using S1. S2 can then be used to adjust further decimals, the decimal point and the exponent, in turn, returning eventually to the parameters menu.
Note: The unit does not have internal error detection. Incorrect parameters can lead to malfunction or failure of the device.
Note: All MTL products are tested for electrical safety to EN 61010 to comply with the EC Low Voltage Directive.
See also warning on page 1.
9.1.4.1 Menu parameters
The following parameters can be configured: id User-specified identification number. tb Time basis. The standard time base setting is
frequency (Hz). If other units are required, a conversion factor has to be used. A conversion from Hz to revolutions per minute requires a tb value of 60, the measured rotational speed is then multiplied by the factor tb.
nt Number of targets. The input frequency is divided by
the number of targets, nt.
F-0 Zero speed detection. If the input frequency falls
below the value F-0, the LCD display will show '0000'. The value of F-0 must be less than the switching threshold values, F-0<Uof.
Uof Switch-off threshold for under-speed monitoring. If the
input frequency falls below the value Uof, the limit value relay will de-energise.
Uon Switch-on threshold for under-speed monitoring. If the
input frequency rises above the value Uon, the limit value relay will energise (Uof < Uon).
Oon Switch-on threshold for over-speed monitoring. If the
speed falls below the value Oon , the limit value relay will energise.
Oof Switch-off threshold for over-speed monitoring. If the
speed rises above the value Oof, the limit value relay will de-energise (Oon < Oof).
9.1.4.2 Switching thresholds (figure 9.1)
Once the parameters tb and nt have been set, all the threshold values will be in the user-defined units. The difference between the switch-on and switch-off threshold values allows user-defined switching hysteresis to be set. The limit value relay and current output performance are illustrated in figure 9.1.
To deactivate under-speed monitoring set Uof and Uon to 0.To deactivate over-speed monitoring set Oof and Oon to 9999*10
3
.
If both the over- and under-speed monitoring modes are deactivated the relay operates as an alarm relay. If no errors occur during operation, the relay is energized. If an error occurs in the input circuit, the relay de­energizes.
Iout Output current range: 0 to 20 mA or 4 to 20 mA. F-IL The minimum frequency to be indicated by either 0 or
4 mA, depending upon Iout.
F-IH The maximum frequency for an output current of
20 mA. If F-IL > F-IH the output curve is reversed.
Tc Filter reaction time in seconds for smoothing the
Start
8888
8888
8888
8888
8888
tb Soft
S2
S1 (3 sec)
S1
S1
S1
S1
S2
S2
S2
S2
S2 S2
S2
8888
8888
8888
8888
S1
S1
S1
S1
S1
S2
S2
S2
S2
S2
. . .
S1
10
3
Figure 9.2: Configuration steps
24 22 20
4 0
Relay
status
OUT
m A
Relay de-energised
F-0 F-IL Uof Uon Oon Oof F-IH
f
Relay energised
Relay de-energised
Figure 9.1: Configuration values
36
INM5000-6 Jul 2010
current signal. The current output follows the rotational speed change according to the preset time
-Br The value of the output current which indicates a
broken wire on the input circuit.
I-Sh The value of the output current indicating a short circuit on
the input circuit.
ICM Input circuit monitoring
off - disabled Br - wire-break monitoring Sh - short-circuit monitoring Both - wire-break and short-circuit monitoring
Sud Start-up time delay in seconds. The start-up time delay
function is activated when the normally open contacts across terminals 7 and 8 close, energizing the limit value relay for a preset time. Consequently, an under-speed indication is inhibited during system start-up.
Soft Software version number.
9.2 MTL5531 voltage/current converter
Device provides hazardous-area current and voltage inputs (only one to be used at any one time). It has short circuit protected voltage input and active current output. Input, output and power supply are galvanically isolated.
9.2.1 Wiring connections
Hazardous area terminals 1 & 2 Current input (passive). 3 & 4 Voltage input. Safe area terminals 5 & 6 Output circuit.
MTL5531-xxx Li - active current output. MTL5531-xxx LU - voltage output.
7 & 8 Power supply connection.
9.2.2 LED indications
Pwr Supply voltage:
(Green indicates that device is operational)
9.2.3 Mounting instructions
The MTL5531 is suitable for either panel or DIN-rail mounting.
9.2.4 Transfer characteristics
9.3 MTL5536 potentiometer converter
Provides repeat of a potentiometer input through an analogue signal in the safe area. Accepts 3- or 5- wire potentiometer input, 800Ω to20kΩ input range, with line resistance <50Ω. Two output versions are available 0 to 20mA (MTL5536-11Li) or 0 to 10V (MTL5536-11LU). No configuration is required, and input, output and power supply are galvanically isolated.
9.3.1 Wiring connections
Hazardous area terminals 1 & 3 3- and 5- wire potentiometer power. 2 Potentiometer wiper 4 & 5 5-wire potentiometer sense. Safe area terminals 7 & 8 Output:
MTL5536-11Li : 0 to 20mA output. MTL5536-11LU : 0 to 10V output
11 & 12 Power supply connection.
9.3.2 LED indications
Pwr Supply voltage:
(Green indicates that device is operational)
9.3.3. 3- or 5-wire operation
3-wire configuration gives high enough accuracy for standard operation. If a higher accuracy is required, or there is a problem with high resistance lines due to long cable runs, then the 5-wire operation is recommended.
9.3.4 Mounting instructions
The MTL5531 is suitable for either panel or DIN-rail mounting
Current input Voltage input
I (mA) RI(ΩΩ)I
max
(mA) V Ri (ΩΩ)V
max
Output circuit RL (ΩΩ)
MTL5531-11Li 0/4 to 20 100 < 40 0/2 to 10 50k < 39 0/4 to 20mA < 500 MTL5531-11LU 0/4 to 20 100 < 40 0/2 to 10 50k < 39 0/2 to 10V > 500 MTL5531-111Li 0 to 20 100 < 40 0 to 10 50k < 39 4 to 20mA < 500 MTL5531-112LU 4 to 20 100 < 40 2 to 10 50k < 39 0 to 10V > 500 MTL5531-113Li 0 to 10 175 < 40 0 to 5 70k < 39 4 to 20mA < 500 MTL5531-115Li 0/2 to 10 175 < 40 0/1 to 5 70k < 39 0/4 to 20mA < 500 MTL5531-115LU 0/2 to 10 175 < 40 0/1 to 5 70k < 39 0/2 to 10V > 500 MTL5531-119LU 2 to 10 175 < 40 1 to 5 70k < 39 0 to 10V > 500
MTL Instruments Pty Limited
9 /12 Billabong Street Stafford Queensland 4053 Australia Tel: + 61 1300 308 374 Fax: + 61 1300 308 463 E-mail: enquiries@mtlaus.com.au
Cooper Electric (Shanghai) Co. Ltd.
Room 2001, China Life Tower 16 Chao Yang Men Wai Street Chao Yang District, Beijing China 100020 Tel: + 86 10 5980 0288 Fax: + 86 10 8562 5725 E-mail: bjsales@mtl-inst.cn
MTL Instruments sarl
Les Carrés du Parc 10 rue des Rosiéristes 69410 Champagne au Mont d’Or France Tel: +33 (0)4 78 64 98 32 Fax: +33 (0)4 78 35 79 41 E-mail: info@mtl-inst.fr
MTL Instruments GmbH
An der Gümpgesbrücke 17 D-41564 Kaarst Germany Tel: +49 (0)2131 718930 Fax: +49 (0)2131 7189333 E-mail: info@mtl.de
MTL India
No. 36, Nehru Street Off Old Mahabalipuram Road Sholinganallur Chennai - 600 119 India Tel: + 91 (0)44 24501660/24501857 Fax: + 91 (0)44 24501463 E-mail: sales@mtlindia.com
MTL Italia srl
Via Cantù 11 I - 20092 Cinisello Balsamo MI Italy Tel: +39 (0)2 61802011 Fax: +39 (0)2 61294560 E-mail: info@mtl-inst.it
Cooper Crouse-Hinds Japan KK
MT Building 3F 2-7-5 Shiba Daimon Minato-ku Tokyo Japan 105-0012 Tel: +81 (0)3 6430 3128 Fax: +81 (0)3 6430 3129 E-mail: sales@mtlkk.co.jp
Cooper Crouse-Hinds Korea
12F, Vision Tower 707-2 Yeoksam-dong, Gangnam-gu Seoul 135-080 South Korea Tel: +82 2 3484 6795 Fax: +82 2 3484 6778
MTL Instruments BV
MTL Instruments BV Terheijdenseweg 465 4825BK Breda The Netherlands Tel: +31(0)76 7505360 Fax: +31(0)76 7505370 E-mail: info@mtlbenelux.com
Cooper Crouse-Hinds Pte Ltd.
No.2 Serangoon North Avenue 5 #06-01 Fu Yu Building Singapore 554911 Tel: +65 6 487 7887 Fax: +65 6 487 7997 E-mail: sales@mtlsing.com.sg
MTL Instruments
Villa No. 4, Sector 2-17, Street 6 PO Box 53234, Abu Dhabi, UAE Tel: +971 2 446 6840 Fax: +971 2 446 6841 E-mail: mtlgulf@mtl-inst.com
Measurement Technology Limited
Great Marlings, Butterfield, Luton, Beds England LU2 8DL Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283 E-mail: enquiry@mtl-inst.com
Cooper Crouse-Hinds MTL Inc
3413 N. Sam Houston Parkway W. Suite 210 Houston TX 77086 USA Tel: +1 281 571 8065 Fax: +1 281 571 8069 E-mail: csinfo@mtl-inst.com
Group Internet home page http://www.mtl-inst.com/
Members of The MTL Instruments Group
Loading...