Series MS Magnesense®Differential Pressure Transmitter
Specifications - Installation and Operating Instructions
The Series MS Magnesense®Differential Pressure
Transmitter is an extremely versatile transmitter for monitoring
pressure and air velocity. This compact package is loaded with
features such as: field selectable English or metric ranges, field
upgradeable LCD display and the ability to select a square root
output for use with Pitot tubes and other similar flow sensors.
Also, a single digital push button simultaneously calibrates
both zero and span reducing installation and setup time. These
features along with exceptional long term performance
®
enables the Magnesense
to be the solution for a myriad of
pressure and air flow applications.
INSTALLATION
Mounting:
The transmitter should be mounted on a vertical surface with
the connections directed down to prevent moisture fr om entering either the pressure ports or the electrical cable entry.
Mount the transmitter using #8 x 1/2˝ pan head sheet metal
screws in the mounting flanges. Do not over tighten.
Electrical Connection:
2-Wire Operation:
CAUTION: DO NOT EXCEED SPECIFIED SUPPL Y
VOLTAGE RATINGS. PERMANENT DAMAGE
NOT COVERED BY WARRANTY WILL RESULT.
2-WIRE UNITS ARE NOT DESIGNED FOR AC
VOLTAGE OPERATION.
2-41/64
(67.07)
2-11/64
(55.17)
2-9/16
(65.09)
21/32
(16/67)
21/32
(16/67)
29/32
(12.70)
(23.02)
57/64
(22.62)
(3) 3/16 (4.76) HOLES
EQUALLY SPACED ON A
4.115 (104.52) BC
1/2
Ø3-7/16
(Ø87.31)
1/2 NPT
SPECIFICATIONS
Service: Air and non-combustible, compatible gases.
Wetted Materials: Consult Factory.
Accuracy: ±1% @ standard conditions
Stability: ±1% F.S./ year.
Temperature Limits: 0 to 150°F (-18 to 66°C).
Pressure Limits: 1 psi maximum, operation; 10 psi, burst.
Power Requirements: 2-wire, 10 to 35 VDC; 3-wire, 17 to
36 VDC or isolated 21.6 to 33 VAC.
Output Signals: 2-wire, 4 to 20 mA; 3-wire, 0 to 10 V.
Response Time: 300 msec
Pressure Calibration: One Digital push button set both zero &
span simultaneously.
Loop Resistance: Current Output: 0-1250 Ohm max. Voltage
Output: min. load resistance 1 k OhmΩ.
Current Consumption: 40 mA max.
Display (optional): 4 digit LCD.
Electrical Connections: 4-20 mA Units: 2-Wire: European Style
Terminal Block for 16 to 26 AWG; 0-10 V Units: 3-Wire:
European Style Terminal Block 16 to 22 AWG.
Electrical Entry: 1/2˝ NPS Thread.
Accessory: Cable Gland for 5 to 10 mm diameter cable.
Process Connections: 3/16˝ (5 mm) ID tubing. Maximum
OD 9 mm.
Enclosure Rating: NEMA 4X (IP65).
Mounting Orientation: Insensitive to mounting orientation
Weight: 8.0 oz (230 g).
Agency Approvals: CE.
The following standards were used for CE approval:
CENELEC EN 61000-4-2: 2001
CENELEC EN 61000-4-3: 2002
CENELEC EN 61000-4-4: 1995
CENELEC EN 61000-4-5: 2001
CENELEC EN 61000-4-6: 2003
CENELEC EN 61000-4-8: 2001
CENELEC EN 55011: 2003
CENELEC EN 61326: 2002
89/336/EED EMC Directive
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000www.dwyer-inst.com
P.O. Box 373 • Michigan City, IN 46361-0373, U.S.A.Fax: 219/872-9057e-mail: info@dwyer-inst.com
The connections to the transmitter are made through a two circuit
European style terminal block CONN6 located at the bottom of the
main PCB board. Polarity is indicated by + and – signs on the PCB
board. Do not connect to the (V) terminal.
P.S.
–
+
V
+
–
RL
Figure 1
An external power supply delivering 10 to 35 VDC with a minimum
current capability of 40 milliamps must be used to power the control loop in which the Magnesense
®
transmitter is connected. Refer
to Fig. 1 for connection of the power supply , transmitter and receiver. The range of appropriate receiver load resistances (RL) for the
power supply voltage available is given by the formula and graph
in Fig. 2. Shielded two wire cable is recommended for control loop
wiring and the negative side of the loop may be grounded if
desired. Note also that the receiver may be connected in either the
negative or positive side of the loop, whichever is most convenient.
Should polarity of the transmitter or receiver be inadvertently
reversed, the loop will not function properly but no damage will be
done to the transmitter.
1500
1400
1300
1200
1100
1000
900
800
700
600
500
400
TOTAL RECEIVER RESISTANCE ( )
300
200
100
50
0
RL MAX =
5101315
MAXIMUM VALUE (1250 )
V
ps - 10.0
20mA DC
OPERATING
REGION
2025303540
POWER SUPPLY VOLTAGE
Figure 2
The maximum length of connecting wire between the transmitter
and the receiver is a function of wire size and receiver resistance.
That portion of the total current loop resistance represented by the
resistance of the connecting wires themselves should not exceed
10% of the receiver resistance. For extremely long runs (over 1,000
feet), it is desirable to select receivers with higher resistances in
order to keep the size and cost of the connecting leads as low as
possible. In installations where the connecting run is no more than
100 feet, connecting lead wire as small as No. 22 Ga. can be used.
The connections to the transmitter are made through a three circuit European style terminal block. Connect the power and signal
leads to the corresponding terminals as shown in Fig. 3. When
using a DC supply, the positive of the supply should be connected
to (+) and the negative connected to (-). Connecting the leads in
reverse will not damage the device but it will not operate. The DC
supply should be capable of providing 20 mA or more of current
per Magnesense
®
transmitter.
When using an isolated AC supply, either leads of the supply may
be connected to (-) and (+). The input diode of the device half wave
rectifies and filters the applied AC voltage. A small DC current of
less than 20 mA is thus drawn through the transformer. The transformer used for the AC supply must be capable of handling this
small DC current. Use a UL 1584 Class 2 rated transformer rated
between 24 V and 30 VAC, 40 VA or larger, 50/60 Hz. UL 1584
Class 2 rated transformers are limited to 30 VAC maximum under
any conditions at nominal line. The AC input voltage to the device
is thus limited to a minimum of 21.6 at low line (24 V-10%) and 33
V at high line (30 V+10%).
CONN6
+
V
Ø
RECEIVER
R
L
POWER SUPPLY
17 TO 36 VDC
OR
21.6 TO 33 VAC
Figure 3
The output of (V) is 0 to 10 VDC. As much as 10 mA may be drawn
from (V) without affecting accuracy. This limits the minimum load
RL connected to Vo to 1 KΩ or higher. Remember to keep the
wiring resistance between the output and the receiver R
L
low compared to value of RL. While the voltage at the terminals remains
unchanged with a 10 mA current flow, resistive losses in the wiring
do cause errors in the voltage delivered to RL. For a 1% accurate
gauge, a good rule of thumb would be to keep the resistance of
L
the leads less than 0.1% of the value of R
. This will keep the error
caused by current flow below 0.1%.
To minimize noise in the signal use shielded cable. The common
line may also be grounded.
Pressure Connections
Two integral tubing connectors are provided. They are designed to
fit 3/16˝ (5 mm) ID tubing. Connect the high pressure to the High
side as shown in Fig. 4. Be sure the pressure ratings of the tubing
exceed that of the operating ranges.
3-Wire Operation:
CAUTION: DO NOT EXCEED SPECIFIED SUPPLY
VOLTAGE RATINGS. PERMANENT DAMAGE NOT
COVERED BY WARRANTY WILL RESULT.
HIGHLOW
Figure 4
Select Operation Mode:
The operating modes and ranges are controlled by a shorting
jumper on jumper block J2. This jumper block is shown in Fig. 5.
Figure 5, Mode Programming Jumpers
Bulletin A-26P
FULL SCALE ANALOG OUTPUT
ModelEnglishMetric
MS-X
31 10 in w.c. 2 kPa
MS-X
4115 in w.c. 3 kPa
51 25 in w.c. 5 kPa
MS-X
Table 2
Page 3
Jumper block J2 primary function is to control the operating mode.
There are two operating modes, Normal and Velocity. The Normal
operating mode provides for zero pressure to corr espond to 0 V or
4 mA output. This mode is selected by placing the supplied shorting jumper for J2 on the pins next to the letter “N”. The jumper for
J2 is factory installed to the Normal Mode. If no jumper is installed
on J2, the device defaults to the “N” selection.
The Velocity mode provides the ability for the unit in conjunction
with a Pitot tube or similar flow sensor with known K factor to give
a direct output in air velocity. This mode is selected by placing the
supplied shorting jumper for J2 on the pins next to the letter “V”.
If the optional display is present, this mode prompts the display to
read in air velocity. The current or voltage output is modified such
that full scale output is 4004* K* √(ΔP) feet per minute or its metric equivalent in meters per second depending upon which units
are selected. The factory programming for the K factor is 1.00 but
may be adjusted (see Adjust K Factor). The velocity displayed for
the various models can be found in Table 1.
Velocity Displayed
ModelEnglishMetric
3XK* 12.66 x 1000 fpmK* 57.7 m/s
MS-X
MS-X
4XK* 15.51 x 1000 fpmK* 70.7 m/s
MS-X5X K* 20.02 x 1000 fpm K* 91.2 m/s
Table 1
SETUP
Set Measurement Units:
Magnesense
TM
transmitters can be easily set to operate in either
English or metric units.
The programming jumper is CONN3. A representation of this
jumper is shown in Fig. 6. English units are selected by placing the
provided shorting jumper on the lower two pins of the block. Metric
units are selected by placing the provided shorting jumper on the
upper two pins of the block. If no jumper is present English units
are selected by default.
Install Optional Display:
The A-435 LCD conversion kit allows any non display model to
have the LCD added at a later time. The kit contains an LCD display and replacement cover with LCD window. The optional display may be set to read pressure either in Inches Water Column or
Kilopascal. The optional display can be also set to display air
velocity in X1000 feet per minute or meters per second when used
with a Pitot tube or similar flow sensor with a known K factor.
®
The optional display for the Magnesense
is mounted on the main
board by connectors CONN4 and CONN5. The display is properly mounted when CONN4 and CONN5 on the display are connected to the corresponding CONN4 and CONN5 on the main
board. See Fig. 4. Installing the display upside down causes no
harm the display or the main board. The display just simply reads
upside down.
Label (Included with display):
The optional LCD display does not contain engineering unit indication. So that the display may be appropriately marked, four adhesive labels have been provided with the units. The unit labels are
INWC, kPa, X1000 fpm, and M/S. Attach the appropriate provided units label above the display window on the cover of the device
to indicate to which units the display has been set.
Adjust K Factor:
If the optional display is present, the K factor used in velocity measurements may be adjusted. This is done by activating the K factor adjustment function of the unit. To activate the K factor adjustment function, take the shorting jumper from programming block
J2 and place it on the upper two terminals next to the letter “K”.
See Fig. 5. The display will now show the programmed Pitot tube
K factor. The K factor can be adjusted up and down by using the
up and down buttons as up and down buttons. Once the desired
K factor has been set, replace the shorting jumper on J2 to its
velocity position (“V”). The shorting jumper must not be left in the
“K” position for proper operation of the unit. The factory setting for
the K factor is 1.0 and it is adjustable from 0.5 to 3.
English
Metric
CONN3
Figure 6, Measurement Units Programming Jumper
In addition to the obvious change in the scale of the LCD display,
the full scale range and corresponding analog outputs are also
affected by the measurement units selection. The analog output
goes to full scale output (10 volts or 20 mA depending on model)
of the selected range and units. See Table 2.
One button pressure calibration – Leaving the hose barbs vented, press and hold the “Zero/Up” switch for about 4-5 seconds.
The zero point should now be set and if the display is present, the
display will read zero. Span is also simultaneously adjusted at the
time the zero is set. No further calibration is required. It does not
matter if in metric or English unit made when performing this “one
button” calibration of both zero & span.
Bulletin A-26P
Page 4
MAINTENANCE
Annual recalibration is suggested. No lubrication or other periodic
servicing is required. Keep exterior and cover clean. Occasionally
disconnect pressure lines to vent both sides of gauge to atmosphere and re-zero. Do not use solvent to clean transmitter. Use
only plastic compatible cleaners or water.
The Series MS is not field serviceable and should be returned if
repair is needed (field repair should not be attempted and may void
warranty). Be sure to include a brief description of the problem plus
any relevant application notes. Contact customer service to receive
a return goods authorization number before shipping.