Dwyer Instruments MS-021, MS-221, Series MS Magnesense, Magnesense MS-X1X, Magnesense MS-X2X Installation And Operating Instructions Manual

...
Bulletin A-26
Ø3-7/16
[Ø87.31]
2
-41/64
[
67.07]
1
/2 NPT
21/32
[16.67]
2
1/32
[
16.67]
29/32
[23.02]
1/2
[12.70]
5
7/64
[
22.62]
(
3) 3/16 [4.76] HOLES
E
QUALLY SPACED ON A
4
.115 [104.52] BC
2
-11/64
[
55.17]
2-9/16
[65.09]
8-1/8
[206.38]
Ø
35/84 [13.87]
ø3-7/16
[Ø87.31]
1/2 NPT
2
5/64
[
9.96]
1-41/64
[41.71]
2-41/64
[67.24]
21/32
[16.67]
5
7/64
[22.62]
2
1/32
[
16.67] 2
9/32
[
23.02]
1
/2
[
12.70]
2-11/64
[55.17]
3
-11/32
[
84.84] 3-1/2
[88.90]
Series MS Magnesense®Differential Pressure Transmitter
Specifications - Installation and Operating Instructions
Wall Mount Bracket
DIN Mount Bracket
The Series MS Magnesense®Differential Pressure Transmitter is an
extremely versatile transmitter for monitoring pressure and air velocity. This compact package is loaded with features such as: field selectable English or metric ranges, field upgradeable LCD display, adjustable dampening of output signal (with optional display) and the ability to select a square root output for use with pitot tubes and other similar flow sensors. Along with these features, magnetic sensing technology provides exceptional long term performance and enables the Magnesense Differential Pressure Transmitter to be the solution for a myriad of pressure and air flow applications.
®
SPECIFICATIONS Service: Air and non-combustible, compatible gases. Wetted Materials: Consult factory. Accuracy: ±1% for 0.25˝ (50 Pa), 0.5˝ (100 Pa), 2˝ (500 Pa), 5˝ (1250
Pa), ±2% for 0.1˝ (25 Pa), 1˝ (250 Pa) and all bi-directional ranges.
Stability: ±1% F.S./ year. Temperature Limits: 0 to 150°F (-18 to 66°C). Pressure Limits: 1 psi (6.89 kPa) maximum, operation; 10 psi (68.9
kPa) burst. Power Requirements: 2-wire, 10 to 35 VDC; 3-wire, 17 to 36 VDC or isolated 21.6 to 33 VAC.
Output Signals: 2-wire, 4 to 20 mA; 3-wire, 0 to 10 V or 0 to 5 V.
INSTALLATION Mounting:
The transmitter should be mounted on a vertical surface with the connections directed down to prevent moisture from entering either the pressure ports or the electrical cable entry. The diaphragm must be vertical to minimize gravity effects on the diaphragm. Mount the transmitter using #8 x 1/2˝ pan head sheet metal screws in the mounting flanges. Do not over tighten.
Response Time: Adjustable 0.5 to 15 sec. time constant. Provides a 95% response time of 1.5 to 45 seconds.
Zero & Span Adjustments: Digital push button. Loop Resistance: Current output: 0-1250 ohm max; Voltage output:
min. load resistance 1 k ohmΩ.
Current Consumption: 40 mA max. Display (optional): 4 digit LCD. Electrical Connections: 4 to 20 mA units: 2-Wire: European style
terminal block for 16 to 26 AWG; 0 to 10 V units: 3-Wire: European
Duct Mount:
The transmitter should be mounted away from fans, corners, heating and cooling coils and other equipment that will effect the measurement of the pressure.
1. To mount the transmitter, drill a .562 (12.70) diameter hold into the duct.
2. Insert transmitter probe into the duct.
3. Mark location of three mounting holes on duct using mounting flange as template. Drill holes.
4. Attach mounting flange to duct with (3) #8 x 1/2 pan head sheet metal screws. Do not overtighten screws.
style terminal block 16 to 22 AWG. Electrical Entry: 1/2˝ NPS thread.
Accessory: A-151 cable gland for 5 to 10 mm diameter cable. Process Connections: 3/16˝ (5 mm) ID tubing. Maximum OD 9 mm.
Enclosure Rating: NEMA 4X (IP65). Mounting Orientation: Diaphragm in vertical position. Weight: 8.0 oz (230 g). Agency Approval: CE.
The following standards were used for CE approval:
CENELEC EN 61000-4-2: 2001 CENELEC EN 61000-4-3: 2002
Electrical Connection: 2-Wire Operation:
CAUTION
WILL RESULT. 2-WIRE UNITS ARE NOT DESIGNED FOR AC VOLTAGE OPERATION.
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS. PERMANENT DAMAGE NOT COVERED BY WARRANTY
CENELEC EN 61000-4-4: 1995 CENELEC EN 61000-4-5: 2001 CENELEC EN 61000-4-6: 2003 CENELEC EN 61000-4-8: 2001 CENELEC EN 55011: 2003 CENELEC EN 61326: 2002 89/336/EED EMC Directive
Phone: 219/879-8000 www.dwyer-inst.com
Electrical Connection:
RECEIVER
R
L
TB1
+
+
POWER SUPPLY 10-35V
POWER SUPPLY VOLTAGE
0
5101315
20 25 30 35 40
MAXIMUM VALUE (1250 W )
OPERATING
REGION
TOTAL RECEIVER RESISTANCE (W )
RL MAX =
V
ps - 10.0
20mA DC
1500
1400
1300
1200
1100
1000
900
8
00
7
00
600
500
400
300
200
100
50
POWER SUPPLY
17 TO 36 VDC
O
R
2
1.6 TO 33 VAC
R
ECEIVER
TB1
V
+
V
o
COM
R
L
PJ1 PJ2
PJ2
P
J1
S
W1
SW2
TB1
HIGH
LOW
2-Wire Operation, continued:
The connections to the transmitter are made through a two circuit European style terminal block TB1 located at the bottom left of the main PB board. Polarity is indicated by + and – signs on the P.C. board.
Figure 1
An external power supply delivering 10 to 35 VDC with a minimum current capability of 40 milliamps must be used to power the control loop in which the Magnesense®transmitter is connected. Refer to Fig. 1 for connection of the power supply, transmitter and receiver. The range of appropriate receiver load resistances (RL) for the power supply voltage available is given by the formula and graph in Fig. 2. Shielded two wire cable is recommended for control loop wiring and the negative side of the loop may be grounded if desired. Note also that the receiver may be connected in either the negative or positive side of the loop, whichever is most convenient. Should polarity of the transmitter or receiver be inadvertently reversed, the loop will not function properly but no damage will be done to the transmitter.
When using an isolated AC supply, either leads of the supply may be connected to Com and V+. The input diode of the device half wave rectifies and filters the applied AC voltage. A small DC current of less than 20 mA is thus drawn through the transformer. The transformer used for the AC supply must be capable of handling this small DC current. Use a UL 1584 Class 2 rated transformer rated between 24 V and 30 VAC, 40 VA or larger, 50/60 Hz. UL 1584 Class 2 rated transformers are limited to 30 VAC maximum under any conditions at nominal line. The AC input voltage to the device is thus limited to a minimum of 21.6 at low line (24 V-10%) and 33 V at high line (30 V+10%).
Figure 3
The output of Vo is 0 to 10 VDC or 0 to 5 VDC depending on model. As much as 10 mA may be drawn from Vo without affecting accuracy. This limits the minimum load RL connected to Vo to 1 KΩ or higher. Remember to keep the wiring resistance between the output and the receiver RLlow compared to value of RL. While the voltage at the terminals remains unchanged with a 10 mA current flow, resistive losses in the wiring do cause errors in the voltage delivered to RL. For a 1% accurate gauge, a good rule of thumb would be to keep the resistance of the leads less than 0.1% of the value of RL. This will keep the error caused by current flow below 0.1%.
Figure 2
The maximum length of connecting wire between the transmitter and the receiver is a function of wire size and receiver resistance. That portion of the total current loop resistance represented by the resistance of the connecting wires themselves should not exceed 10% of the receiver resistance. For extremely long runs (over 1,000 feet), it is desirable to select receivers with higher resistances in order to keep the size and cost of the connecting leads as low as possible. In installations where the connecting run is no more than 100 feet, connecting lead wire as small as No. 22 Ga. can be used.
3-Wire Operation:
CAUTION
WILL RESULT.
The connections to the transmitter are made through a three circuit European style terminal block. Connect the power and signal leads to the corresponding terminals as shown in Fig. 3. When using a DC supply, the positive of the supply should be connected to V+ and the negative connected to Com. Connecting the leads in reverse will not damage the device but it will not operate. The DC supply should be capable of providing 20 mA or more of current per Magnesense®transmitter.
DO NOT EXCEED SPECIFIED SUPPLY VOLTAGE RATINGS. PERMANENT DAMAGE NOT COVERED BY WARRANTY
To minimize noise in the signal use shielded cable. The common line may also be grounded.
Pressure Connections
Two integral tubing connectors are provided. They are designed to fit 3/16˝ (5 mm) ID tubing. Connect the high pressure to the High side as shown in Fig. 4. Be sure the pressure ratings of the tubing exceed that of the operating ranges.
Figure 4
Select Operation Mode and Range:
The operating modes and ranges are controlled by two shorting jumpers on a pair of jumper blocks, PJ3 and PJ5. These two jumper blocks are shown in Fig. 5.
Loading...
+ 2 hidden pages