Dwyer Instruments LPI Operating Manual

Bulletin E-90-LPI
(
)
Series LPI Loop Powered Indicator
Specifications - Installation and Operating Instructions
SWITCH
The Series LPI is a loop powered indicator with a 4-digit red LED display. The Series LPI accepts a 4-20 mA input signal and displays the associated process variable. The instrument configu­ration settings are selectable via a simple to use menu system, which is navigated by the use of three push-button keys located on the rear of the display. The entire assembly is sealed into a cap that fits directly onto the connecting heads.
Please inspect the packaging and instrument thoroughly for any signs of transit damage. If the instrument has been damaged, please notify your supplier immediately.
INSTALLATION
The maximum current rating for this device is 100 mA for 1 minute. Exceeding this value will destroy the device. Fuse protec­tion of the current loop to which this device is connected is high­ly recommended. This unit must only be series connected to 4 to 20 mA current loop. This device will be destroyed if connected directly across any supply with a current output greater than 100 mA. Ensure the instrument is installed with adequate protection against the environment. IP67 rating must be maintained. Try to avoid installing the equipment close to sources of extreme temperature and electrical or electromagnetic interference.
SWITCHES
TERMINAL
(13/16)
(13/64)
(Ø2-5/8)
(Ø66.7)
(20.7)
(5)
(Ø2-7/8)
(Ø73)
(23/64)
8.9
SPECIFICATION @ 68°F (20°C)
Input: 4 to 20 mA. Maximum Input Current: 100 mA for 1 minute. Accuracy: ±0.02% of full scale. Stability: Zero: 0.002%/°C; Span: 100 ppm/°C. Power Requirements: 2-wire 4-20 mA loop powered. Display: 4-digit, 7.6 mm (high) red LED. Maximum Display Range: -1999 to 9999. Ambient Operating Temperature: -4 to 167°F (-20 to 75°C). Storage Temperatures: -58 to 185°F (-50 to 85°C). Weight: 6.0 oz (170 g). Front Panel Protection: NEMA 4X (IP65). Agency Approvals: CE.
Wiring and switch location (viewed looking at connector) LPI Typical Wiring
LPI
Configuration - Connect the device to a 4 to 20 mA loop, set at
any value between 4 and 20 mA. To configure the device follow the simple configuration menus printed on the reverse side of this sheet. Fit the correct units legend to the front panel face.
Enclosure - All external cabling/sensor entries must maintain IP67 rating.
CONFIGURATION MENU
The prime function of the Series LPI device is to sink a 4-20 mA current input and display the associated process variable (PV) in appropriate engineering units.
The section below describes the menus accessible on the LPI. By accessing these menus, the user can modify the instrument con­figuration in many ways. The following section refers to the config­uration menu to describe how to configure the input scaling. The instrument needs to know at least 2 co-ordinate pars to define the relationship between mA input and display PV. The default method is to have SCAL (scaling) set to StNd (standard). This allows the user to edit the ENLO (engineering low) and ENHI (engineering high) PV values that correspond to 4 mA and 20 mA input values, respectively. The default values for ENLO and ENHI are 0 & 100, respectively, giving a linear display range of 0-100 for 4-20 mA input.
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
Alternatively, the user may not know the exact PV values at 4 & 20 mA. You can choose AUtO scaling to solve this problem. This allows the user to edit ENLO and ENHI PV values that correspond to LO mA and HI mA input values, respectively. When the user accesses the SCLO (scale low) menu entry, the display flashes IPLO (input low) to prompt the user to apply the LO mA value. Once the correct input signal is present and stable, the user should press ENT to store. The user is then prompted to apply the HI mA value (in SCHI/IPHI). The user can choose LIN (linearization type) to NONE, 59rt, rt32, rt52 or USEr.
NONE is the default, and sets a straight linear relationship
between mA input and PV. The input will go under/over-range at 3.8/21.5 mA.
59rt (square root), rt32 (root 3/2) and rt52 (root 5/2) set a X1/2,
X3/2, or X5/2 relationship, intended for flow applications where, for example, the flow is proportional to the square root of level. The input will go under/over-range at 3.8/21.5 mA.
USEr allows user-defined linearization using up to 20 co-ordinate
pairs. For example, if the user wanted to apply a 3-segment set of interpolated co-ordinate points as shown below, you would select LIN = USEr, then set StGS = 3. The user would then set the mA interpolation points as IN1, IN2, IN3, IN4 = 5.1, 6.9, 12.3, 16.95. The corresponding PV interpolation points would be set as OUt1, OUt2, OUt3, OUt4 - 21.6, 32.5, 42.5, 75.1. The input would then go under/over-range at 5.1/16.95 mA.
Once the input has been scaled using any of these methods, the user can choose to apply a constant offset to the PV, using the OFSt setting. The user can also select the display resolution using the dECP setting. A menu access passcode can be set using the
PASS setting. The menu timeout period can be changed using the tOUt setting.
MAINTENANCE
Apart from configuration this equipment requires no maintenance. If recalibration is required please contact your supplier for further information. Any cleaning of the instrument should be carried out using a mild detergent and a soft cloth. No solvents or abrasive cleaner should be used.
The Series LPI Loop Powered Indicator is not field serviceable and should be returned if repair is needed (field repair should not be attempted and may void warranty). Be sure to include a brief description of the problem plus any relevant application notes. Contact customer service to receive a return goods authorization number before shipping.
SERIES LPI CONFIGURATION MENU GUIDE
There are three buttons, which the operator must press in various combinations in order to configure the device. These buttons are located on the under­side of the indicator’s circuit board. Viewed from the front, the three buttons (CYCle , INCrement
CYC
and DECrement ) are
INC
shown in the diagram to the left. Pressing 2 buttons simultane­ously causes ENTer or
DEC
ESCape actions.
When cycling around menu, the title (e.g. LIN, SCAL, etc.) is displayed for a second, then the menu entry is displayed ready for editing.
Run-Time
then
CYCle around menu
If no buttons are pressed for a minute or more, the device assumes run-time mode. The display shows the PV (if the input is in range) or shows or to indicate over/under range. In order to access menu configuration mode, the user must press ENTer followed immediately by CYCle . In order to exit the menu and return to run-time, a user must press
ESCape .
INCrement menu entry
DECrement menu entry
ENTer to confirm entry, or:
CYCle to next menu entry
ESCape
©Copyright 2005 Dwyer Instruments, Inc. Printed in U.S.A. 8/05
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
Loading...