Bulletin E-20
Model L6
Specifications - Installation and Operating Instructions
Explosion-Proof; UL and CSA Listed Class I, Groups *A, B, C, & D
Class II, Groups E, F & G
Directive 94/9/EC (ATEX) Compliant for
II 2 G Ex d IIC T6 Gb Process Temp≤75°C
IECEx Compliant for Ex d IIC T6 Gb Process Temp≤75°C
*(Group A, stainless steel body only)
Float Switch
SPECIFICATIONS
Service: Liquids compatible with
wetted materials.
Wetted Materials:
Float: Solid polypropylene or 304
SS.
Lower Body: Brass or 303 SS.
Magnet: Ceramic.
External Float Chamber (Tee):
Matches lower body choice of brass
or 303 SS.
Other: Lever Arm, Spring, Pin, etc.:
301 SS.
Temperature Limit: -4 to 220°F (-20 to
105°C) Standard, MT high temperature
option 400°F (205°C)(MT not UL, CSA,
ATEX, IECEx and KC). ATEX compliant
AT, IECEx IEC and KC option ambient
temperature -4 to 167°F (-20 to 75°C)
process temperature: -4 to 220°F (-20
to 105°C).
Pressure Limits: See next page.
Enclosure Rating: Weatherproof and
Explosion-proof. Listed with UL and
CSA for Class I, Groups A, B, C and D;
Class II, Groups E, F, and G. (Group A
on stainless steel body models only).
0518 II 2 G Ex d IIC T6 Gb
Process Temp≤75°C.
EC-Type Certificate No.: KEMA
04ATEX2128.
ATEX Standards: EN 60079-0: 2009;
EN60079-1: 2007.
IECEx Certified: For Ex d IIC T6 Gb
Process Temp≤ 75°C.
IECEx Certificate of Conformity:
IECEx DEK II.0039.
IECEx Standards: IEC 60079-00:
2007; IEC 60079-1: 2007.
Korean Certified (KC) for Ex d IIC T6
Gb Process Temp≤75°C.
KTL Certificate Number: 2012-2454-75.
Switch Type: SPDT snap switch
standard, DPDT snap switch optional.
Electrical Rating: UL models: 5A @
125/250 VAC (V~). CSA, ATEX and
IECEx models: 5A @ 125/250 VAC
(V~); 5A res., 3A ind. @ 30 VDC (V ).
MV option: .1A @ 125 VAC (V~). MT
option: 5A @125/250 VAC (V~). [MT
option not UL, CSA, ATEX or IECEx].
Electrical Connections: UL models:
18 AWG, 18˝ (460 mm) long.
ATEX/CSA/IECEx models: terminal
block.
Upper Body: Brass or 303 SS.
Conduit Connection: 3/4˝ male NPT
standard, 3/4˝ female NPT on junction
box models.
Process Connection: 1˝ male NPT on
models without external float chamber,
1˝ female NPT on models with external
float chamber.
Mounting Orientation: Horizontal with
index arrow pointing down.
Weight: Approximately 1 lb (.5 kg)
without external float chamber, 1.75 lb
(.8 kg) with external float chamber.
Specific Gravity: See next page.
Example
Series
Construction
Upper
Body Material
Lower
Body Material
Circuit (Switch)
Type
Line Size
Tee and Float
Options
Switch Options
Options
* Options that do not have ATEX, IECEx or KC.
L6L6EPEPB
B
S
33B
MT
B
S
B
S
S
D
0
A
B
C
H
L
S
MV
MT
AT
CSA
IEC
KC
GL
ID
JCT
JCTLH
TBC
TOP
L6EPB-B-S-3-B-MT level switch; brass upper housing, brass lower housing, brass tee with
Polypropylene spherical float, SPDT snap switch, and high temperature option
Series L6 level switch
Explosion proof and weatherproof
Brass
303 Stainless Steel
Brass
303 Stainless Steel
SPDT
DPDT
1˝ NPT
No Tee, Solid Polypropylene Spherical Float*
No Tee, 304 SS Cylindrical Float
Brass Tee, Solid Polypropylene Spherical Float*
No Tee, 304 SS Spherical Float
Brass Tee, 304 SS Spherical Float
303 SS Tee, 304 SS Spherical Float
303 SS Tee, Solid Polypropylene Spherical Float*
Gold Contacts on snap switch for dry circuits (see specifications for ratings)
High Temperature switch rated 400°F (205°C) (see specifications for ratings)*
ATEX approved construction (with JCT option standard)
CSA approved construction (with JCT option standard)*
IECEx approved construction (with JCT option standard)
KC approved construction (with JCT option standard)
Ground Lead*
Customer Information on standard nameplate
Weatherproof and explosion-proof junction box*
Weatherproof and explosion-proof junction box, left side
Terminal Block Connector*
Top Mounted (No tee models only)*
Attention: Units without
the “AT” suffix are not
Directive 94/9/EC (ATEX)
compliant. These units are
not intended for use in
potentially hazardous
atmospheres in the EU.
These units may be CE
marked for other
Directives of the EU.
W.E. ANDERSON DIV., DWYER INSTRUMENTS, INC.
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com

AXIMUM PRESSURE CHART
FRONT VIEW DETAIL SIDE VIEW DETAIL
CLAMP
SCREW
LOCKWASHER
CONDUCTOR
M
Model Number
L6EPB-B-S-3-A
L6EPB-B-S-3-B
6EPB-B-S-3-C
L
6EPB-B-S-3-H
L
6EPB-B-S-3-O
L
6EPB-S-S-3-A
L
L6EPB-S-S-3-C
L6EPB-S-S-3-L
L6EPB-S-S-3-O
6EPB-S-S-3-S
L
Float
Cylindrical SS
Polypropylene
ound SS
R
ound SS
R
olypropylene
P
ylindrical SS
C
Round SS
Round SS
Polypropylene
olypropylene
P
ressure Rating
P
psig (kg/cm
200 (13.8)
250 (17.2)
50 (24.1)
3
50 (17.2)
2
000 (69)
1
00 (13.8)
2
350 (24.1)
350 (24.1)
2000 (138)
000 (138)
2
ETTED MATERIALS CHART
W
2
)
Model
B-S-3-A
-S-3-B
B
-S-3-C
B
-S-3-H
B
-S-3-O
B
S-S-3-A
S-S-3-C
S-S-3-L
-S-3-O
S
-S-3-S
S
Brass
X
X
X
X
X
Bronze
X
X
Ceramic
X
X
X
X
X
X
X
X
X
X
Polypropylene
X
X
X
X
X
301SS
X
X
X
X
X
X
X
X
X
X
303SS
X
X
X
X
304SS
X
X
X
X
X
INSTALLATION
Unpack switch and remove any packing material found inside lower housing or float
hamber.
c
witch must be installed with body in a horizontal plane and arrow on side pointing
S
down.
If switch has an external float chamber (tee), connect it to vertical sections of 1˝
NPT pipe installed outside vessel walls at appropriate levels. If unit has no external
loat chamber, it must be mounted in a 1˝ NPT half coupling welded to the vessel
f
all. The coupling must extend through the wall.
w
Inspect and clean wetted parts at regular intervals.
ELECTRICAL CONNECTIONS
onnect wire leads in accordance with local electrical codes and switch action
C
equired. N.O. contacts will close and N.C. contacts will open when liquid level
r
auses float to rise. They will return to “normal” condition on decreasing liquid level.
c
Black = common, Blue = N.O. and Red = N.C.
For units supplied with both internal ground and external bonding terminals, the
ground screw inside the housing must be used to ground the control. The external
bonding screw is for supplementary bonding when allowed or required by local
code. When external bonding conductor is required, conductor must be wrapped a
minimum of 180° about the external bonding screw. See below. Some CSA listed
models are furnished with a separate green ground wire. Such units must be
equipped with a junction box, not supplied but available on special order.
Note: ATEX, IECEx and KC units only: The temperature class is determined by the
maximum ambient and or process temperature. Units are intended to be used in
mbient of -20°C≤ Tamb ≤75°C. Units may be used in process temperatures up to
a
05°C providing the enclosure and switch body temperatures do not exceed 75°C.
1
he standard Temperature Class is T6 Process Temp ≤75°C.
T
Refer to Certificate No: IECEx DEK 11.0039 for conditions of safe use for IECEx
compliant units.
ll wiring, conduit and enclosures must meet applicable codes for hazardous
A
reas. Conduits and enclosures must be properly sealed. For outdoor or other loca-
a
ions where temperatures vary widely, precautions should be taken to prevent con-
t
densation inside switch or enclosure. Electrical components must be kept dry at all
times.
CAUTION: To prevent ignition of hazardous atmospheres, disconnect the device
rom the supply circuit before opening. Keep assembly tightly closed when in use.
f
AINTENANCE
M
Inspect and clean wetted parts at regular intervals. The cover should be in place at
all times to protect, the internal components from dirt, dust and weather and to
maintain hazardous location ratings. Disconnect device from the supply circuit
before opening to prevent ignition of hazardous atmosphere. Repairs to be conducted by Dwyer Instruments, Inc. Units in need of repair should be returned to the
factory prepaid.
EC-Type Certificate IECEX and KC Installation Instructions:
Cable Connection
The cable entry device shall be certified in type of explosion protection flameproof
enclosure “d”, suitable for conditions of use and correctly installed. For Ta ≥ 65°C
cable and cable gland rated ≥ 90°C shall be used.
Conduit Connection
An Ex d certified sealing device such as a conduit seal with setting compound shall
be provided immediately to the entrance of the valve housing. For Ta ≥ 65°C wiring
and setting compound, in the conduit seal, rated ≥ 90°C shall be used.
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com

MODEL L-6 FLOAT SWITCH — DIMENSION DRAWINGS
Ø
1 [25.40]
1
MALE NPT
1
-3/4
[44.45]
3/4
[
19.05]
6
[
152.40]
Ø
1-1/16
[26.99]
3/4 MALE NPT
C
ONDUIT
CONNECTION
Ø1
[
Ø25.40]
FLOAT
1
MALE NPT
1-27/32
[
46.83]
1
-1/16
[26.99]
6
-1/2
[165.10]
Ø1-1/16
[
Ø26.99]
3/4 MALE
NPT CONDUIT
C
ONNECTION
Ø
1 [25.40] x 2 [50.80]
L
ONG FLOAT
1 MALE NPT
2-7/8
[73.03]
1-1/16
[26.99]
6-1/2
[165.10]
Ø1-1/16
[26.99]
3/4 MALE NPT CONDUIT
CONNECTION
3-5/64
[78.18]
1-9/64
[28.97]
2 [50.80]
HEX
8-9/16
[217.49]
Ø1-1/16
[26.99]
3
/4 MALE NPT
C
ONDUIT
C
ONNECTION
1
FEMALE NPT
T
YP 2 PLACES
3-1/2
[88.90]
4-3/8
[111.13]
Ø3-11/32
[84.93]
4-1/4 [107.95]
CLEARANCE FOR
COVER REMOVAL
2-15/16
[74.63]
25/32
[19.86]
Ø3-3/8
[85.73]
3/4 FEMALE NPT
CONDUIT CONNECTION
TYP 2 PLACES
olypropylene Float
P
ound Stainless Steel Float
R
Cylindrical Stainless Steel Float With External Chamber (Tee)
Terminal Connections CSA, ATEX Enclosures
Find Quality Products Online at: sales@GlobalTestSupply.com
CSA, ATEX Conduit Enclosure
www.GlobalTestSupply.com

Limited Warranty: The Seller warrants all Dwyer instruments and equipment to be
free from defects in workmanship or material under normal use and service for a period of one year from date of shipment. Liability under this warranty is limited to repair
or replacement F.O.B. factory of any parts which prove to be defective within that time
or repayment of the purchase price at the Seller’s option provided the instruments
have been returned, transportation prepaid, within one year from the date of purchase. All technical advice, recommendations and services are based on technical
data and information which the Seller believes to be reliable and are intended for use
by persons having skill and knowledge of the business, at their own discretion. In no
case is Seller liable beyond replacement of equipment F.O.B. factory or the full purchase price. This warranty does not apply if the maximum ratings label is removed or
if the instrument or equipment is abused, altered, used at ratings above the maximum
specified, or otherwise misused in any way.
THIS EXPRESS LIMITED WARRANTY IS IN LIEU OF AND EXCLUDES ALL OTHER
REPRESENTATIONS MADE BY ADVERTISEMENTS OR BY AGENTS AND ALL
OTHER WARRANTIES, BOTH EXPRESS AND IMPLIED. THERE ARE NO IMPLIED
WARRANTIES OF MERCHANTABILITY OR OF FITNESS FOR A PARTICULAR
PURPOSE FOR GOODS COVERED HEREUNDER.
Buyers Remedies: THE BUYER’S EXCLUSIVE AND SOLE REMEDY ON
ACCOUNT OF OR IN RESPECT TO THE FURNISHING OF NON-CONFORMING
OR DEFECTIVE MATERIAL SHALL BE TO SECURE REPLACEMENT THEREOF
AS AFORESAID. THE SELLER SHALL NOT IN ANY EVENT BE LIABLE FOR THE
COST OF ANY LABOR EXPENDED ON ANY SUCH MATERIAL OR FORM ANY
SPECIAL, DIRECT, INDIRECT OR CONSEQUENTIAL DAMAGES TO ANYONE BY
REASON OF THE FACT THAT IT SHALL HAVE BEEN NON-CONFORMING OR
DEFECTIVE.