4-3/8
[111.13]
3/16
[4.76]
4
[101.6]
2-7/8
[73.03]
2X 7/16
[11.11]
2X 4-1/4
[107.95]
4X Ø1/4
[Ø6.35]
2X 1/2 [12.7]
5-1/8
[130.18]
5-1/4
[133.35]
13/16
[20.64]
1-3/8
[34.93]
3/4 [19.05]
2X Ø7/8
[Ø22.23]
1/2
[12.7]
Model
4-37/64 [116.46]
4-3/8 [111.20]
25/32 [20.00]
KFD0
Galvanic Barrier
Loop Powered, Intrinsically Safe Isolators
The Model KFD0 Loop Powered, Galvanic Barrier provides complete isolation for
communication with Dwyer
areas. Galvanic barrier eliminates the need for a high integrity earth ground required
when using shunt type diode type safety barriers. Unlike most other isolators, the Model
KFD0 does not require external power and has a low current draw. The housing is designed
to easily mount on most standard DIN rails.
Model
KFD0-SCS-EX1.55
Model
KFD0-SCS-EX1.55
370
DWYER INSTRUMENTS, INC. | www.dwyer-inst.com
®
intrinsically-safe transmitters approved for use in hazardous
Approval
FM for Class I, Zone 1,
Groups IIC, IIB, IIA; Class I, II, III, Div. 2,
Groups A, B, C, D, F, G
Vo (V)
23.1
Io (mA)
38.2
Group
IIC (A, B)
IIB (C)
IIA (D, F, G)
Dwyer Series
HHT-IX
µF
0.042
0.267
0.267
mH
0.5
2.5
2.5
SPECIFICATIONS
Hazardous Area Input:
Signal range: 4 to 20 mA (linear transmission 1 to 22 mA);
Available transmitter voltage: ≥ 16 V for supply voltage > 21 V.
Safe Area Output:
Signal range: 4 to 20 mA;
Transmitter voltage: ≤ 30 VDC.
Response Time: ≤ 20 µs at 0, and ≤ 600 µs at 800 load.
Maximum Power Dissipation: 150 mW @ 20 mA and V <24 V.
Temperature Limits: -4 to 140°F (-20 to 60°C).
Temperature Drift: ≤ 0.5 µA/°C.
Weight: 4.2 oz (120 g).
Agency Approvals: CE, FM.
Model KFD0-SCS-EX1.55, Loop powered galvanic barrier . . . . . . . . . .$484.00b
b Items are subject to Schedule B discounts.
ACCESSORY
A-360, Aluminum DIN Rail 1 m . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .$8.00