Series IS626 Pressure Transducer
Specifications - Installation and Operating Instructions
The Dwyer Series IS626 Pressure Transducer convert pressure into a
standard 4-20 mA output signal. The Series IS626 can be used to accurately measure compatible gases and liquids. Series IS626 full scale accuracy is 0.25% (see specifications). Designed for industrial
environments with a NEMA 4X (IP66) housing, this transmitter resists
most effects of shock and vibration.
SPECIFICATIONS
Service: Compatible gases and liquids.
Wetted Materials: Type 316, 316L SS.
Accuracy: 0.25% full scale (includes linearity, hysteresis, and repeata-
bility).
Temperature Limit: 0 to 176°F (-18 to 80°C).
Compensated Temperature Range: 0 to 176°F (-18 to 80°C).
Intrinsic Safety Approval Classification
The IS626 is UL listed for use in Hazardous (Classified) Locations. The
protection method is by Intrinsic Safety, “ia”. It was investigated by UL
under UL Standard 913 Sixth Edition and CSA Standard No. 157-92.
Thermal Effect: ±0.02% FS/°F (includes zero and span).
Pressure Limits: See Pressure Range Table (Next Page).
Power Requirements: 10 to 28 VDC.
Output Signal: 4 to 20 mA.
Response Time: 50 msec.
For use in Hazardous (Classified) Locations:
Class I Div. 1 Groups A,B,C,D
Class II Div. 1 Groups E,F,G
Class III Div. 1
Temperature Code: T4 @ 80°C ambient
Install in accordance with control drawing 01-700797-00.
Loop Resistance: 0 - 900 ohms maximum.
Current Consumption: 38 mA (maximum).
Electrical Connections: 3 ft. cable or 4-pin M-12 Connector.
Process Connection: 1/4˝ male/female NPT and BSPT.
Enclosure Rating: NEMA 4X (IP66).
Mounting Orientation: Mount in any position.
Weight: 8.9 oz (252 g).
WARNING: To prevent ignition of flammable or
combustible atmospheres, disconnect power before servicing.
Use with approved safety barriers using entity evaluation.
Agency Approvals: CE, UL Intrinsically Safe to UL Standard 913. (See
Intrinsic Safety Approval Classification)
The following standards were used for CE approval:
IEC 61000-4-8: 2001
CENELEC EN 55011: 2003
CENELEC EN 61326: 2003
89/336/EEC EMC Directive
Phone: 219/879-8000www.dwyer-inst.com
CAUTION: Do not exceed specified supply voltage
POWER
SUPPLY
10-28 VDC
-
RECEIVER
BLACK
RED
PRESSURE
TRANSDUCER
mA
TERMINAL 4 (-)
TERMINAL 1 (+)
ratings. Permanent damage not covered by warranty will result. This device is not designed for 120
or 240 volt AC operation. Use only on 10 to 28
VDC.
5. Wiring
An external power supply delivering 10-28 VDC with minimum current capability of 40 mA DC (per transducer) is required to power the control loop.
See Fig. A for connection of the power supply, transducer and receiver.
The range of appropriate receiver load resistance (RL) for the DC power
supply voltage available is expressed by the formula:
1. Location: Select a location where the temperature of the transducer will
be between 0 and 176°F (-18 to 80°C). Distance from the receiver is limited only by total loop resistance. The tubing or piping supplying pressure
to the unit can be practically any length required but long lengths will increase response time slightly.
2. Position: The transducer is not position sensitive. However all standard models are originally calibrated with the unit in a position with the
pressure connection downward. Although they can be used at other an gles, for best accuracy it is recommended that units be installed in the position calibrated at the factory.
L max
Vps - 12.3V
=
20 mA
R
Shielded cable is recommended for control loop wiring.
Fig. A
When using cable version IS626, black wire is negative (-) and red wire
is positive (+). When using 4-pin M-12 connector models, wire to pins as
shown below in Fig. B.
Fig. B
Male-12 Connector
3. Pressure Connection: Use a small amount of plumber’s tape or other
suitable sealants to prevent leaks. Be sure the pressure passage inside
the port is not blocked.
4. Electrical Connections
Wire Length - The maximum length of wire connecting the transducer
and receiver is a function of wire size and receiver resistance. Wiring
should not contribute more than 10% of the receiver resistance to total
loop resistance. For extremely long runs (over 1000 feet), choose receivers with higher resistance to minimize the size and cost of connecting
leads. Where wiring length is under 100 feet, wire as small as 22 AWG can
be used.
A female 4 position M-12 connector for use in connecting to the M-12
male connector on the IS626. Fit 0.16˝ to 0.29˝ diameter cables with a
maximum wire gage at 18 AWG (0.75 mm2).
WRAP SHIELD WIRE BACK OVER
THIS INSERT DURING ASSEMBLY.
O-RING
.240 SHEATHING
REMOVED
.160
STRIPPING
1.380
MAINTENANCE
After final installation of the pressure transducer and its companion receiver, no routine maintenance is required. A periodic check of system
calibration is suggested. The Series IS626 transducers are not field repairable and should be returned if repair is needed (field repair should
not be attempted and may void warranty). Be sure to include a brief description of the problem plus any relevant application notes. Contact customer service to receive a return goods authorization number before
shipping.
A-231 Shielded Cable
A pre-made 16.4 ft (5 m) cable with a 4 pin Female M-12 connector is
available for use when connecting to the male M-12 connector on the
IS626. Black wire is negative and the brown wire is positive.
2. NO REVISIONS WITHOUT PRIOR UNDERWRITERS LABORATORY APPROVAL.
3. (ENTITY CONCEPT DEFINITIONS)
IMPORTANT! NO REVISIONS WITHOUT
PRIOR UNDERWRITERS LABORATORIES
APPROVAL CAN BE IMPLEMENTED
THE ENTITY CONCEPT ALLOWS INTERCONNECTION OF INTRINSICALLY SAFE APPARATUS TO ASSOCIATED APPARATUS
NOT SPECIFICALLY EXAMINED IN SUCH COMBINATION. THE CRITERIA FOR INTERCONNECTION IS THAT THE VOLTAGE AND
CURRENT WHICH INTRINSICALLY SAFE APPARATUS CAN RECEIVE AND REMAIN INTRINSICALLY SAFE, CONSIDERING FAULTS, MUST BE
EQUAL TO OR GREATER THAN THE VOLTAGE (Voc) AND CURRENT (Isc) LEVELS WHICH CAN BE DELIVERED BY THE
ASSOCIATED APPARATUS. CONSIDERING FAULTS AND APPLICABLE FACTORS. IN ADDITION, THE MAXIMUM UNPROTECTED CAPACITANCE AND
INDUCTANCE (Ci & Li) OF THE INTRINSICALLY SAFE APPARATUS. INCLUDING INTERCONNECTING WIRING. MUST BE EQUAL TO OR LESS THAN
THE CAPACITANCE AND INDUCTANCE WHICH CAN BE SAFELY CONNECTED TO ASSOCIATED APPARATUS.
4. INSTALLATION MUST BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NFPA 70, ARTICLE 504) AND ANSI/ISA-RP12.6.
HAZARDOUS (CLASSIFIED) LOCATION
INTRINSICALLY SAFE
FOR CLASS I DIV.1 GROUPS A,B,C,D
CLASS II DIV. 1 GROUP E,F,G
NONHAZARDOUS LOCATION
CLASS III DIV. 1
T4 TEMPERATURE CODE BASED ON 80˚C AMBIENT
IS626, PBLTX OR SBLTX SERIES
TRANSDUCERS
ASSOCIATED APPARATUS
WITH ENTITY PARAMETERS
RED
V
= 28VDC
max
I
= 93mA
max
Ci = .051µF
Li = 240µH
Pi = 0.651W
OR PIN 1
BLACK
OR PIN 4
Voc ≤ 28 V
Isc ≤ 93 mA
Ca ≥ 0.051 µF + C
La ≥ 240 µH + L
Po ≤ 0.651W
CABLE
CABLE
CATALOG NUMBERS:
IS626-aa-bb-cc-dd-ee-ffff
PBLTX-aaa-bbb-cccc
SBLTX-aa-bb-cccc
WHERE:
a,b,c,d,e & f = ANY LETTER OR NUMBER
DATE
DATE
7-14-06
7-14-06
DWN BY
2
ADDED LABELS TO PLUS & MINUS TERMINALS.
1
ADDED Pi & Po = 0.651W TO BOXES. ECR #21141.
NO.
NOTICE: This drawing and the principles and elements of design embodied therein are the exclusive property of DWYER INSTRUMENTS, INC. and are not
to be communicated, disclosed, reproduced or used except as previously authorized in writing by such corporation and must not be submitted to outside
parties for examination without the written consent of said corporation.
CHANGES
BRENT
1-22-07
BY/DATE
DGH
CHKD
CAT
APPD
SE
NAME
IS626, PBLTX & SBLTX SERIES
SCALE 1:1
BULLETIN ARTWORK
INTRINSIC SAFETY
CONTROL DRAWING FOR
ACAD2002
3
MATERIAL
FINISH
FR. NO.
CD = CRITICAL DIMENSION
STANDARD TOLERANCES UNLESS NOTED:
ALL DECIMAL DIMENSIONS ± .005
ALL ANGLES ± 1˚