Bulletin E-IS-626
M
ALE NPT/BSPT CONNECTOR WITH CABLE GLAND
1
/4 NPT or
1/4 BSPT
1
-1/16 [26.99] HEX
5
-3/16 [131.75]
6
-1/4 [158.75] MAX
ø
1 [25.40]
1
/4 NPT OR
1
/4 BSPT
1
-1/16 [26.99] HEX
M
ALE NPT/BSPT CONNECTOR WITH MALE M-12 CONNECTOR
5-1/16 [128.58]
5-21/32 [143.67]
ø1 [25.40]
ø1 [25.40]1-1/16 [26.99] HEX
5-1/16 [128.58]
5-21/32 [143.67]
FEMALE NPT/BSPT CONNECTOR WITH MALE M-12 CONNECTOR
1
/4 NPT OR
1
/4 BSPT
F
EMALE
C
D
= CRITICAL DIMENSION
STANDARD TOLERANCES UNLESS NOTED:
ALL DECIMAL DIMENSIONS ± /005
ALL ANGLES ± 1’
F
EMALE NPT/BSPT CONNECTOR WITH CABLE GLAND
1
-1/16 [26.00] HEX
5-3/16 [131.76]
5-1/4 [158.75]
1
/4 NPT OR
1
/4 BSPT
F
EMALE
ø
1 [25.40]
Series IS626 Pressure Transducer
Specifications - Installation and Operating Instructions
The Dwyer Series IS626 Pressure Transducer convert pressure into a
standard 4-20 mA output signal. The Series IS626 can be used to accurately measure compatible gases and liquids. Series IS626 full scale accuracy is 0.25% (see specifications). Designed for industrial
environments with a NEMA 4X (IP66) housing, this transmitter resists
most effects of shock and vibration.
SPECIFICATIONS
Service: Compatible gases and liquids.
Wetted Materials: Type 316, 316L SS.
Accuracy: 0.25% full scale (includes linearity, hysteresis, and repeata-
bility).
Temperature Limit: -4 to 176°F (-20 to 80°C).
Compensated Temperature Range: -4 to 176°F (-20 to 80°C).
Intrinsic Safety Approval Classification
The IS626 is UL listed for use in Hazardous (Classified) Locations. The
protection method is by Intrinsic Safety, “ia”. It was investigated by UL
under UL Standard 913 8th Edition, CAN/CSA C22.2 No. 60079-0:15 and
CAN/CSA C22.2 No. 60079-11:14.
Thermal Effect: ±0.02% FS/°F (includes zero and span).
Pressure Limits: 2X full scale.
Power Requirements: 10 to 28 VDC.
Output Signal: 4 to 20 mA.
Response Time: 50 msec.
Loop Resistance: 0 - 900 ohms maximum.
Hazardous (Classified) Location Intrinsically Safe For:
Class I Div. 1 Groups A,B,C,D
Class II Div. 1 Groups E,F,G
Class III Div. 1
Class I Zone 0 AEx ia IIC T4 Ga
Zone 20 AEx ia IIIC T135°C Da
Ex ia IIC T4 Ga
Ex ia IIIC T135°C Da
Current Consumption: 38 mA (maximum).
Electrical Connections: 3 ft. cable or 4-pin M-12 Connector.
Process Connection: 1/4˝ male/female NPT and BSPT.
Enclosure Rating: NEMA 4X (IP66) (Self Declared by Dwyer Instru-
ments, Inc.).
Mounting Orientation: Mount in any position.
Weight: 8.9 oz (252 g).
Agency Approvals: CE, See Intrinsic Safety Approval Classification.
Ta = -20°C to 80°C
Install in accordance with Control Drawing 001833-42.
See Control Drawing 001833-42 for Entity Parameters.
ATEX: EU TYPE CERTIFICATE NO. DEMKO 18 ATEX 2080
ATEX STANDARDS: EN 60079-0:2012/A11:2013
EN 60079-11:2012
ATEX CLASSIFICATION: 0518 II 1 G Ex ia IIC T4 Ga (-20°C ≤
Tamb ≤ 80°C)
0518 II 1 D Ex ia IIIC T135°C Da (-20°C ≤ Tamb ≤ 80°C)
IECEx CERTIFICATE OF CONFORMITY: IECEx UL 18.0086
IECEx STANDARDS: IEC 60079-0: 2011 6TH ED.
IEC 60079-11:2011 6TH ED.
IECEx CLASSIFICATION: Ex ia IIC T4 Ga (-20°C ≤ Tamb ≤ 80°C)
Ex ia IIIC T135°C Da (-20°C ≤ Tamb ≤ 80°C)
INSTALL IN ACCORDANCE WITH CONTROL DRAWING 001833-45
SEE CONTROL DRAWING 001833-45 FOR ENTITY PARAMETERS.
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. Fax: 219/872-9057 e-mail: info@dwyer-inst.com
Phone: 219/879-8000 www.dwyer-inst.com
WARNING: Use with approved safety barriers
POWER
SUPPLY
10-28 VDC
-
R
ECEIVER
BLACK
R
ED
PRESSURE
TRANSDUCER
mA
TERMINAL 4 (-)
TERMINAL 1 (+)
using entity evaluation.
Aluminum tag must be removed prior to installation for all units supplied
with aluminum tag option Suffix "AT".
CAUTION: Do not exceed specified supply voltage
ratings. Permanent damage not covered by warranty will result. This device is not designed for 120
or 240 volt AC operation. Use only on 10 to 28
VDC.
INSTALLATION
1. Location: Select a location where the temperature of the transducer will
be between -4 and 176°F (-20 to 80°C). Distance from the receiver is limited only by total loop resistance. The tubing or piping supplying pressure
to the unit can be practically any length required but long lengths will increase response time slightly.
2. Position: The transducer is not position sensitive. However all standard models are originally calibrated with the unit in a position with the
pressure connection downward. Although they can be used at other an gles, for best accuracy it is recommended that units be installed in the position calibrated at the factory.
3. Pressure Connection: Use a small amount of plumber’s tape or other
suitable sealants to prevent leaks. Be sure the pressure passage inside
the port is not blocked.
5. Wiring
An external power supply delivering 10-28 VDC with minimum current capability of 40 mA DC (per transducer) is required to power the control loop.
See Fig. A for connection of the power supply, transducer and receiver.
The range of appropriate receiver load resistance (RL) for the DC power
supply voltage available is expressed by the formula:
L
max
Vps - 12.3V
=
20 mA
R
Shielded cable is recommended for control loop wiring.
Fig. A
When using cable version IS626, black wire is negative (-) and red wire
is positive (+). When using 4-pin M-12 connector models, wire to pins as
shown below in Fig. B.
Fig. B
4. Electrical Connections
Wire Length - The maximum length of wire connecting the transducer
and receiver is a function of wire size and receiver resistance. Wiring
should not contribute more than 10% of the receiver resistance to total
loop resistance. For extremely long runs (over 1000 feet), choose receivers with higher resistance to minimize the size and cost of connecting
leads. Where wiring length is under 100 feet, wire as small as 22 AWG can
be used.
Male-12 Connector
.160
STRIPPING
1.380
WRAP SHIELD WIRE BACK OVER
THIS INSERT DURING ASSEMBLY.
O-RING
.240 SHEATHING
REMOVED
ACCESSORIES
FEMALE M-12 CONNECTOR
2-13/64 [55.96]
M12 X 1
FEMALE
ø51/64 [20.24]
ACCESSORY A-295
A-295 Female M-12 Connector
A female 4 position M-12 connector for use in connecting to the M-12
male connector on the IS626. Fit 0.16˝ to 0.29˝ diameter cables with a
maximum wire gage at 18 AWG (0.75 mm2).
MAINTENANCE
After final installation of the pressure transducer and its companion receiver, no routine maintenance is required. A periodic check of system
calibration is suggested. The Series IS626 transducers are not field repairable and should be returned if repair is needed (field repair should
not be attempted and may void warranty). Be sure to include a brief description of the problem plus any relevant application notes. Contact customer service to receive a return goods authorization number before
shipping.
A-231 Shielded Cable
A pre-made 16.4 ft (5 m) cable with a 4 pin Female M-12 connector is
available for use when connecting to the male M-12 connector on the
IS626. Black wire is negative and the brown wire is positive.