Series IEF Insertion Electromagnetic Flow Transmitter
5-53/64 [148.0]
61/64
[24.2]
22-1/64
7-3/32 [180.2]
®
Specications - Installation and Operating Instructions
5-53/64
[148.0]
[559.2]
-LCD option shown
Shown with A-IEF-VLV-BR
accessory valve
Bulletin F-IEF-F
4-51/64
[121.8]
The SERIES IEF Insertion Electromagnetic Flow Transmitter is an adjustable insertion
owmeter featuring electromagnetic technology that accurately and reliably measures
uid velocity in addition to providing several continuous signal outputs. This series
is specically designed to offer superior performance paired with simple installation
and use. One unit is adjustable to t pipe sizes from 4 to 36˝ (102 to 914 mm), and
offers several output options including selectable BACnet MS/TP or Modbus
communications protocol over 2-wire RS-485 in addition to the standard analog,
frequency and alarm outputs.
FEATURES/BENEFITS
• Field congurable setup displays (-LCD integral option or remote accessory
A-IEF-DSP) allow for ultimate exibility by accommodating a variety of application
congurations with one model through multiple display congurations i.e. pipe
size, pipe material, liquid type, analog output, pulse/frequency output, alarm outputs,
communication outputs, damping, and calibration factor.
• High performance accuracy is maintained through changes in temperature, density
or viscosity.
• Setup Wizard and installation tool are simple to use allowing for quick and precise
installation.
• Accessory setup kit A-IEF-KIT ensures exact installation application depth with
included thickness gage and measuring tape.
• Long Life Cycle and minimal maintenance requirements with no moving parts to
wear or break and electrodes that discourage fouling.
• Isolation valve accessory options allow for installation in operational systems via
hot-tap kit or easy removal without system downtime.
• NIST calibration certicate included standard for Carbon Steel Schedule 40 pipes
sized 4˝ (102 mm), 6˝ (150 mm), 8˝ (200 mm), and 10˝ (250 mm) with high accuracy
option.
APPLICATIONS
• Boiler feed water
• Chilled water
• Open and closed loop condenser water
• Irrigation system
• Municipal water distribution
• Process and coolant ow
• Ground water remediation
• Chemical processing
• Pump protection
• Wastewater
• Mining
®
RTU
SPECIFICATIONS
Service: Compatible clean or dirty non coating, conductive liquids.
Range: 0 to 20 ft/s (0 to 6 m/s).*
Wetted Materials: Body shaft/tting: 316SS; Electrodes: 316SS; Electrode cap:
Polymer/Polystyrene; O-ring: Silicone.
Accuracy: IEF-HX-X: ±0.5% of reading at calibrated velocity; ±1% of reading from
2 to 20 ft/s (0.6 to 6 m/s) ±0.02 ft/s (±0.006 m/s) at < 2 ft/s (0.6 m/s). IEF-SX-X:
±1% FS.
Temperature Limits: Ambient: -20 to 160°F (-29 to 71°C); Process: 15 to 250°F (-9
to 121°C); Storage: -40 to 185°F (-40 to 85°C).
Process Connection: 1˝ NPT or BSPT with accessory full port ball valve options.
Pressure Limits: 400 psi (27.6 bar) @ 100º F (37.8°C).
Pressure Drop: < 0.1 psi at 12 ft/s in 4˝ (101.6 mm) and larger pipe.
Outputs:
(1) Analog: 4 to 20 mA, 0 to 5 V, 0 to 10 V or 2 to 10 V (display selectable);
(1) Pulse/Frequency: 0 to 15 V peak pulse, 0 to 500 Hz or scalable pulse output
(display selectable);
(2) Alarm: (1) Empty pipe detection or minimum/maximum velocity, (display
selectable); (1) Reverse ow output indication.
Power Requirements: 12 to 42.4 VDC, .25 A @ 24 VDC; 12 to 36 VAC.
Electrical Connection: Removable terminal blocks, model selectable 1/2˝ female
NPT conduit connection, PG 16 gland or PG 16 gland with (2) 10 ft (3 m) 9
conductor 22 AWG plenum rated cables, accessory cable lengths up to 200 ft (61
m) optional.
Display (-LCD option): 2˝ ( 5.08 cm) x 2˝ (5.08 cm) graphic LCD with backlight.
Conductivity: >20 microsiemens.
Enclosure Material: Powder coated die cast aluminum.
Enclosure Ratings: NEMA 6P (IP68) (Non display models); NEMA 4X (IP66)
(-LCD option).
Agency Approvals: BTL, CE, NSF/ANSI 61 and 372 pending.
COMMUNICATIONS (-COM OPTION)
Type: BACnet MS/TP or Modbus
display selectable).
Supported Baud Rates: 9600, 19200, 38400, 57600, 76800, or 115200 bps
(display selectable).
Device Load: 1/8 unit load.
®
RTU communication protocol (default disabled,
ADDITIONAL SPECIFICATIONS
Applicable Pipe Material: Most popular plastic and metal pipes; i.e. Carbon steel,
SS, copper, UPVC/PVDF, galvanized steel, mild steel, and brass.
Applicable Pipe Size: IEF-HX-X: 4 to 10˝ (101 to 254 mm); IEF-SX-X: 4 to 36˝
(101 to 914 mm).
• Only qualied professionals equipped with the necessary required trade skills
should install, remove or service this product in any way. Failure to follow the
proper installation procedures could lead to death or permanent injury.
• This product is intended to be installed in pressurized pipe applications. In this
event, product will be under pressure, caution should be taken to properly vent
system prior to installation or removal of the unit. Failure to do so could result in
equipment damage and/or serious bodily injury.
CAUTION
S
N
B
CND
PG
10
Setup kit (includes setup display, thickness gage and measuring
tape)
Setup display
Plenum rated cable 50 ft (15.2 m)
1-1/4˝ full port isolation valve brass
1-1/4˝ full port isolation valve 316SS
Installation alignment kit
AC wall adapter
High accuracy; 1% of reading
Standard accuracy; 1% FS
1˝ NPT
1˝ BSPT
1/2˝ female NPT
PG 16 gland
PG 16 gland with (2) 10´ (3 m) plenum
rated cables
Integral LCD
BACnet or Modbus
COM
protocol (display selectable)
Multiple point NIST traceable calibration
NIST
certicate
Factory calibration certicate for 0.5% of
FC
reading at single point
CC
Custom congured for specic installation
®
communication
INCLUDED WITH THE FLOWMETER
Carefully unpack the shipping container of your new Series IEF Insertion
Electromagnetic Flow Transmitter and remove the following items:
• (1) Series IEF Insertion Electromagnetic Flow Transmitter
1. Although the unit may be installed in any orientation, the ideal mounting position
is on the side of the pipe (2 o’clock or 10 o’clock position)* as this generally
minimizes possible air or sediment interference with the Series IEF. It is not
reccomended to mount the unit below the pipe (6 o’clock position).
When installing a unit with an integral display select an installation
NOTICE
location that allows for clear viewing of the display and proper
earth ground.
Insert the IEF in a pipe via a threaded Tee, Saddle, or welded integrally
reinforced branch connection outlet tting.
If a Hot-Tap option is required, use a 1-1/4˝ valve kit with proper mounting
hardware available in Model A-IEF-VLV-BR or A-IEF-VLV-SS. A 1˝ (25.4 mm)
hole in the pipe is required for proper installation.
Rods (2)
Figure 1
Series IEF
• Refer to Model Chart and Specications for the applicable options to your unit.
• Ensure the unit is sufciently grounded as stated in this bulletin.
• Depressurize and vent systems without Hot-tap valve prior to installation or
removal.
• Conrm the Series IEF wetted material is chemically compatible with process
media prior to installation and use.
• Do not exceed maximum temperature and pressure specications.
• Wear appropriate personal protective equipment during installation, removal and or
service of the unit.
• Altering the product construction in any way may adversely affect product operation
and voids warranty.
• Prior to attempting to wire or service the Series IEF disconnect from power.
OPERATING PRINCIPLE
• Per Faraday’s Law of electromagnetic induction, a voltage is induced in a
conductor when it passes through a magnetic eld, and the induced voltage will be
directly proportional to the velocity of the conductor.
• The Series IEF Flow Transmitter generates pulsating magnetic elds in the probe
to induce a voltage into a conductive uid owing through the pipe.
• Electrodes located on the probe measure the induced voltage. Electronics and
rmware within the enclosure convert the voltage to velocity and ow rate while
using various outputs to convey the data to connected systems (i.e. display
devices, data acquisition systems, or BTU meters).
2. Select a location that will minimize ow distortion with adequate upstream and
downstream pipe diameters as displayed. Ideal installation will have a minimum
of 10 pipe diameters upstream relative to the instrument and a minimum distance
of 5 pipe diameters downstream.
NOT RECOMMENDEDRECOMMENDED
5x
20x
20x
5x
FLOW DIRECTION
Figure 3
INSTALLATION
1. To prepare the meter for installation, mount the provided alignment scale to the
side of the meter with the two provided thumbscrews. The thumbscrews are to be
inserted through the alignment scale slots and into the holes in the side of the lid
as shown in Figure 4, nger tighten only. Be sure to orient the alignment scale as
shown in gure below. Actual scale setting determined in next step.
For Field Congurable Models
2. For eld conguration, a display is required (-LCD option or accessory A-IEF DSP) and needs to be powered via normal eld wiring or with the AC wall adapter
accessory A-IEF-PA ( A-IEF-DSP and A-IEF-PA are also available in the
accessory setup kit A-IEF-KIT).
3. When using the AC wall adapter and the cable is supplied, connect the red
(positive +) and black (common -) wires of the cable bundle marked “A” to the
open terminals of the AC wall adapter. This will provide temporary power to the
meter to complete the installation set up.
4. For eld wiring, refer to the wiring chart tag attached to the Series IEF to identify
the terminal block pins for positive (+) and common (-) connection.
5. Unscrew the four captured cover screws using the supplied 3 mm Allen wrench
to remove and set aside enclosure cover.
6. Insert one connector of the ribbon cable supplied in the setup kit into the
connector labeled “Display” in the middle of the unit. Be sure to orient the keying
feature/tab. See Figure 5 below:
KEYING
FEATURE
USE LID TO
ENCLOSURE
GAP AS
INDICATOR LINE
Figure 4
For Custom Congured Models (-CC Option)
2. Locate the conguration tag attached to the Series IEF to identify the value of
the alignment scale setting. Position the alignment scale such that the scale
setting is lined-up with the seam of the enclosure as shown in Figure 4. Minor
scale marks are in 1/20ths Securely tighten the thumbscrews.
3. Refer to Preparing the Unit for Installation section.
Figure 5
7. Plug the other end of the cable into the bottom of the supplied portable display
being sure to orient the keying feature/tab as shown:
KEYING
Figure 6
8. Apply power to the unit and the display will turn-on automatically. Follow the on
screen directions for entering the necessary parameters to setup the unit and
obtain the alignment scale setting value.
NOTICE
DSP, thickness gage UTG and measuring tape A-IEF-MSTP used to obtain these
measurements. When the precise pipe measurement information is known select
Option 2 High Performance setup in the Install Kit option of the display selection
Precise pipe measurements are required for high performance
installation. The A-IEF-KIT includes setup display A-IEF-
circumference use the 100ths side to measure the circumference
FLOW
OOL
PIPE ALIGNMENT ROD MUST
g
1
8
Preparing the Unit for installation (Refer to Figure 7)
1. Apply appropriate sealant to the process collet (5) threads such as application
suitable sealant tape or paste.
2. Install the process collet (5) in valve (6) then tighten by hand.
3. Tighten the process collet (5) with a wrench using the hex geometry until snug.
NOTICE
4. Slowly open the valve handle (7) checking for leaks.
5. If leaks occur around threaded connections, close the valve and tighten those
connections.
Use two wrenches, one to hold the valve and another wrench to
turn the process collet.
2
3. Rotate the transmitter so the pipe alignment rod is parallel with the ow in the
pipe.
BE PARALLEL WITH PIPE
FLOW DIRECTION
Figure 9
9
Figure 7
3
7
1. Enclosure
2. Cable Nut
3. Probe Shaft
4. Compression Fitting
5. Process Collet
6. Valve (optional)
7. Valve Handle (optional)
8. Pipe
9. Sensor Probe
4
5
6
Do not adjust housing compression nut at top of probe shaft (3).
NOTICE
Sensor Alignment
A depth and ow alignment installation tool is provided to ensure proper depth insertion
and ow alignment. To set the insertion depth verify the alignment scale has not moved
from its original setting based on the alignment scale value set previously.
Loosen compression nut (4) to allow the shaft (3) freedom to travel up and down and
rotate inside the process collet (5).
Install Depth and Alignment Rods
1. Remove alignment rods from sides of alignment scale by sliding them out.
2. Insert the two rods into the alignment scale as shown.
4. Slide the shaft (3) down into the process collet (5) until the depth rod contacts
the pipe. If pipe insulation is present press the rod through the insulation.
a. Tighten the nut (4) to 15 ft.-lbs (20.3 N m)
b. Remove the ow alignment rod and loosen the thumbscrews to slide the
alignment tool up to allow removal of the depth alignment rod. Store both
rods in the storage slots on the sides of the alignment scale. Tighten
thumbscrews and leave alignment tool mounted on unit for storage.
GROUNDING
Metallic Pipe
For proper operation the instrument must be earth grounded.
Connect a ground wire to meter housing via the ground lug on the housing collet.
Connect the ground wire to a known earth ground.
If the pipe is grounded, connect the ground wire to the metal pipe using suitable
devices such as grounding clamps.
Grounding lu
Figure 10
Non-Metallic Pipes
Connect a ground wire to the transmitter housing per the ground lug on the housing
collet.
Connect the ground wire to a known earth ground.
Ground the uid to earth.
Choose a power supply with a voltage and current rating sufcient to meet the power
specications under all operating conditions.
If the power supply is unregulated, make sure the output voltage remains within the
required voltage range under all power line conditions.
www.GlobalTestSupply.com
GROUNDING
RINGS
Figure 11
WIRING DIAGRAM
CableTerminal # Wire Color DescriptionNote
A
A
A
B
External
Analog Current Output
B
B
Analog Voltage Output
B
B
Frequency Output
B
B
RS-485 Communication (optional)
B
B
Reverse Flow
A
A
Alarm
A
A
Pulse
A
A
No Connection
B
B
A
A
1
2
13
14
3
4
5
6
8
7
11,12
9,10
15
16
17
18
19
20
-
-
-
-
Red
Black
Shield
Shield
-
Brown
Blue
Green
White
Violet
Grey
Orange
Yellow
Brown
Blue
Green
White
Orange
Yellow
Red
Black
Violet
Grey
Power Supply Positive
Power Supply Common
-
Earth/Chassis Ground
(+) Analog current output
(-) Analog output common
(+) Analog voltage output
(-) Analog output common
(+) Frequency output
(-) Analog output common
RS-485 (+)
RS-485 (-)
Isolated solid state output N.O.
Isolated solid state output N.O.
Isolated solid state output N.O.
Isolated solid state output N.O.
Isolated solid state output N.O.
Isolated solid state output N.O.
Do not connect
Do not connect
Do not connect
Do not connect
Connect to +24VDC or VAC transformer
Connect to 24VDC/VAC common
If used - Application Dependant
If used - Application Dependant
-
4 to 20 mA process output
Current output common
May be congured; 0 to 10 V, 0 to 5 V, 2 to 10 V, etc.
Voltage output common
0 to 500 Hz output (@ 0/15 VDC output level)
Frequency output common
On board short for daisy chain connection
On board short for daisy chain connection
50 V AC/VDC @ 100 mA maximum
50 V AC/VDC @ 100 mA maximum
50 V AC/VDC @ 100 mA maximum
50 V AC/VDC @ 100 mA maximum
50 V AC/VDC @ 100 mA maximum
50 V AC/VDC @ 100 mA maximum
-
-
-
-
The Cable column identifying cable A and B is reective of units that include factory installed cabling.
Wiring PCBA shown in Figure 12 with terminal block numbers as listed in above wiring diagram chart.
Determining probe insertion depth for models with a display
The Series IEF transmitter will calculate the probe insertion depth used with -LCD
display option or A-IEF-DSP display when the steps below are followed.
Follow the on screen directions for entering the circumference and wall thickness
dimensions. See the Electronic Control Data Setup section of this manual for more
information.
NOTICE
A-IEF-MSTP to obtain these measurements. When the precise pipe measurement
information is known, select option 2 (High Performance Setup) under the Install Kit
Menu when prompted by the display as shown below. Precise pipe measurements
are required for a high performance installation.
1. To measure the pipe circumference remove any existing insulation at the
location where the transmitter will be installed. Wrap the tape measure around
the pipe to measure the circumference at the selected location using the
100ths side of the tape. Record this measurement for entering into the unit
when the circumference measurement is requested.
It is recommended to use the A-IEF-KIT which includes a setup
display A-IEF-DSP, thickness gage UTG and measuring tape
Determining probe insertion depth for models without a display
For models without a display the following formulas allow for calculating the alignment
scale value for setting the depth of the probe into the pipe. Also included are wall
thickness charts for various pipe materials and sizes.
Pipes < 11 in (< 279 mm) diameter: 7.1625-1/2*D
Where D represents the pipe outer diameter and WT represents the pipe wall
thickness, both in inches. Measurement of the outside diameter and wall thickness
can be accomplished as described in the previous section, Determining probe insertion
depth for models with a display, or similar method. Precise pipe measurements are
required for a high performance installation.
Position the alignment scale such that the alignment scale setting is lined-up with
the seam of the enclosure as shown in Figure 13. Minor scale marks are in 1/20ths
Securely tighten the thumbscrews.
2. To measure the wall thickness of the pipe use the thickness gage UTG. Following
the separate directions provided with the UTG gage and record the thickness.
This measurement will be needed to enter into the unit after the circumference
data is entered.
After installation is complete a table of conguration values can be gathered from the
transmitter to print out and insert into one of the hanging plastic envelopes for future
reference. The housing cover/display needs to be removed for access to the display
port to retrieve the table of conguration values. To do so:
1. Unscrew the four captured cover screws using the supplied 3 mm Allen wrench
to remove the enclosure cover. Leave the display cable connected to the main
unit.
2. Insert a customer supplied mini-USB cable into the USB connector on the bottom
side of the display PCB.
3. Connect the other end into a standard USB port in a laptop.
4. The Series IEF transmitter will appear as a standard USB drive on the laptop.
5. The le name with the conguration values is in the format of:
serial number.txt. The serial number can be found on the product label on the
side of the transmitter.
6. Print out the conguration values and insert into one of the hanging plastic
envelopes for future reference
7. Re-attach the housing cover/display by reinserting the four 3 mm screws.
CONFIGURATION DATA PRINT OUT EXAMPLE
[Device Information]
1. To remove the transmitter from an installation without a valve depressurize the
pipe and skip to step 4. If installed with a valve loosen compression tting (4) and
withdraw the transmitter shaft fully through the valve until it stops.
2. Tighten compression tting (4) snug.
3. Close valve (6) via valve handle (7).
4. Remove transmitter by unscrewing process collet (5) from value (6).
CAUTION
occur to the probe ns.
Network Termination Jumper
On the terminal block PCBA there is a jumper, J1 (see Figure 15), that enables or
disables a network termination resistor as dened below:
When the network jumper is placed in the ON position there is a 120 ohm termination
resistor in place. When the network jumper is placed in the OFF position there is no
termination resistor in place.
Default: OFF
Be sure to support the housing end of the transmitter to prevent it
from ipping while unscrewing process collet (5) as damage may
The Insertion Magmeter supports BACnet MS/TP and Modbus
485.
Selection of protocol and conguration of serial parameters require the use of the
display.
BACNET
BACnet Object Overview
Supported BACnet Objects
Object Type
Device
Analog Input
Analog Value
Binary Value
BitString Value
BACnet Objects: Device Object
Property Default ValueProperty Data TypeAccess
Object Identier
Object Name
ObjectType
System Status
Vendor Name
Vendor Identier
Model Name
Firmware Revision
Application Software Version
Location
Description
Protocol Version
Protocol Revision
Protocol Services Supported
Protocol Object Types Supported
Object List
Active COV Subscriptions
Maximum APDU Length Accepted
Maximum APDU Length Accepted
APDU Timeout
Number of APDU Retries
Max Master
Max Info Frames
Device Address Binding
Database Revision
Property List
Serial Number
The default object identier is 607xxx, where xxx is replaced by the MS/TP MAC
address set in the Network Address menu. The object identier value will change as
the MS/TP MAC address changes. However, if a specic object identier is written
via BACnet, then that value is stored and changes to the MS/TP MAC address will no
longer affect the object identier.
Dynamically
Creatable
No
No
No
No
No
Dynamically
Creatable
No
No
No
No
No
Object
Identier Object Name
607xxx
AV1
AV1
AV2
BV1
BV2
BV3
BSV1
607xxx
“Series IEF 607xxx”
DEVICE(8)
Operational(0)
“Dwyer Instruments, Inc.”
607
“IEF-HN-10-COM”
“x.x.x”
“x.x”
“ ”
“ ”
1
14
See BACnet Services below
See Table Above
See Table Above
BACnetServicesSupported
BACnetObjectTypesSupported
BACnetArray
List of BACnetCOVSubscription
Unsigned
BACnetSegmentation
Unsigned
Unsigned
Unsigned
Unsigned
BACnetAddressBinding Unsigned
BACnetARRAY[N] of
BACnetPropertyIdentier
CharacterString
Read/Write
Read/Write
Read
Read
Read
Read
Read
Read
Read
Read/Write
Read/Write
Read
Read
Read
Read
Read
Read
Read
Read
Read/Write
Read/Write
Read/Write
Read
Read
Read
Read
Similarly, the default object name includes 607xxx. The object name will reect the
current object identier. If a specic object name is written via BACnet, then that value
is stored and changes to the object identier will no longer affect the object name.
APDU Timeout values are rounded to the nearest second (1000ms). Values less than
500 will be rounded to 0 and Number of APDU Retries will be set to 0.
Property Default ValueProperty Data TypeAccess
Object Identier
Object Name
ObjectType
Present Value
Status Flags
Event State
Reliability
Out Of Service
Property List
This object provides a simple indication of the direction of process ow. When the
process uid is detected as owing in the normal direction, the present value will return
inactive(0). When the process uid is detected as owing in the reverse direction, the
present value will return active(1).
This object supports COV subscription to allow a monitoring system to easily detect
changes in ow direction.
Binary Value – Empty Pipe
Property Default ValueProperty Data TypeAccess
Object Identier
Object Name
ObjectType
Present Value
Status Flags
This object provides a simple indication of an error state where no process ow is
in contact with the probe. When the process uid is detected, the present value will
return inactive(0). When the process uid is not detected, the present value will return
active(1).
This object supports COV subscription to allow a monitoring system to easily detect
this error condition.
Binary Value – Reset Total Flow
Property Default ValueProperty Data TypeAccess
Object Identier
Object Name
ObjectType
Present Value
Status Flags
Event State
Reliability
Out Of Service
Property List
Writing a value of 1 to the present value of this object will reset the value of Total Flow
to 0. Writing a value of 0 has no effect.
BV3
“Reset Total Flow”
BINARY_VALUE (5)
Inactive (0)
0
NORMAL (0)
NO_FAULT_DETECTED(0)
FALSE (0)
This device supports the Device Communication Control Service BIBB. The optional
time duration in minutes is also supported. This device is congured with a password
that must be provided to successfully execute this command. The password is
“Dwyer”.
Reinitialize Device Service (DM-RD-B)
This device supports the Reinitialize Device Service BIBB. The supported device
states are COLDSTART and WARMSTART. All other states return error. This device
is congured with a password that must be provided to successfully execute this
command. The password is “Dwyer”.
SubscribeCOV Service (DS-COV-B)
This device supports the SubscribeCOV Service BIBB to allow easy monitoring of
input data.
• Up to seven (7) concurrent subscriptions
• Conrmed and Unconrmed COV Notications
• Fixed lifetime value up to 86400 seconds (24 hours).
• Indenite lifetime supported.
MODBUS
Modbus® Functions
The device supports the following functions
Modbus
Input Registers
®
Function NameFunction Code
Read Holding Registers
Read Input Registers
0 – Normal
1 – Reverse
0 – Process detected
1 – Process not detected
See BACnet BitString
Object “Status Flags”
“IEF-HN-10-COM”
“xxxxxxxx”
“x.x.x”
“xxxxxxxx”
The String data type is read as a
stream of ASCII characters with the rst
character sent in the MSB of the rst
register and the second character sent
in the LSB of the rst register and so on.
If the string is shorter than the allotted
size, the remaining bytes will be zero
padded.
Device Name: A string, up to 40 characters long, that will be displayed on the LCD (if
present). When reading or writing, all 20 registers must be requested. Strings less than
40 characters shall be 0 padded.
Velocity Unit: Selects the unit of velocity for the value in the velocity register. See
Table 1.
Flow Unit: Selects the unit of ow for the value in the Flow register. See Table 2.
Volume Unit: Selects the unit of volume for the value in the Total Flow register. See
Table 3.
Reset Total Flow: When a value of 1 is written to this register, the value in the Total
Flow register is reset to 0. Writing a value of 0 has no effect. This register will always
return a 0 when read.
Reset Device: When a value of 1 is written to this register, the device will perform a
warm reset after 5 seconds. Writing a value of 0 has no effect. This register will always
return 0 when read.
TABLE 1: VELOCITY UNIT VALUES
Value Unit
*0
Feet-per-second (ft/s)
1
Feet-per-minute (ft/min)
2
Feet-per-hour (ft/hr)
3
Feet-per-day (ft/day)
4
Meters-per-second (m/s)
5
Meters-per-minute (m/min)
6
Meters-per-hour (m/hr)
7
Meters-per-day (m/day)
Multi-Address Support
Multi-Address support allows a register to be read or written to using different byte
orientations specied by the address range. For example, input register 0003 can
also be read at 2003, 4003 and 6003 with different byte orientations as listed in Table
7. Registers that do not have multi-address support are only available in Big-Endian
byte orientation (Modbus
Electronic Control Setup -LCD Display Option or A-IEF-DSP Accessory
Basic information
1. Turn on the power to the Display/Menu.
NOTICE
2. If a Transmitter is NOT congured, a main conguration wizard starts.
3. If the Transmitter is congured, the process data is displayed.
At power ON, the Dwyer Logo, Serial Number and Firmware
Version of the Transmitter is displayed.
Main Conguration Wizard
1. Language Selection:
• At the Language Screen elect the Language:
NOTICE
• If necessary, select another language by moving the highlighted bar with
the UP /DOWN Arrows and press the Enter Button to select the
Language.
The menu default language is English.
SERIAL
NUMBER
Navigation Basics
1. The UP /DOWNbuttons change the selected option or increase or
decrease the current value.
2. The RIGHT button advances the display to the next menu without
changing the current setting.
3. The LEFT button returns the display to the previous menu without
changing the current setting.
4. The ENTER button accepts the selected setting or value and advances to
the next menu.
5. The MENU button transitions the display to the main menu. Any unsaved
changes will be lost.
FIRM
WARE
VERSION
2. Unit System Selection Menu:
• This option determines which units will be available in future menus.
• The Default is English
• If necessary, select a different Unit of measure by moving the highlighted
bar with the UP /DOWN Arrows and press the Enter button to
select he Unit.
3. Velocity Unit Menu:
• This option determines how the calculated volume velocity is displayed.
• The Default is Feet-Per-Second.
Menu Basics
1. Option Menus:
• The current option is indicated by a highlight bar. The highlight bar is
moved with the UP and DOWN buttons.
• The active option is indicated by an asterisk (*) symbol to the far right of the
option name.
2. Value Menus:
• The active value is always displayed when the menu is displayed.
• To reset a changed value to the active value, use the LEFT button to
return to the previous menu, then the RIGHT button to advance to the
value menu again.
3. Press & Hold the UP or DOWN button to continuously increase or
decrease the value.
Note: The value will be increased or decreased by a larger amount the longer
the button is held.
• This option determines how the calculated volume ow is displayed.
• The Default is Cubic-Feet-Per-Second.
5. Volume Unit Menu:
• This option determines how the totalized ow is displayed.
• The Default is Gallons.
Pipe Conguration Wizard
1. Pipe Material Menu:
• This option helps determine the pipe dimensions as well as account for
different material properties.
• The Default is Carbon Steel
b. Wall Thickness Menu (High Performance):
• This value is the pipe wall thickness where the Transmitter is installed.
• The thickness can be measured with the gauge included in the high
performance installation kit.
• Default: 0.322in
3. Install Kit Menu (Standard):
• Nominal Pipe Size Menu
• Select the diameter of the installation pipe from the list of standard pipe
diameters. If your nominal diameter is not listed or you have actual OD data,
select Other and enter the pipe diameter directly.
• Default: 8 in
2. Install Kit Menu (High Performance):
• This option determines how the pipe dimensions will be collected.
• If a high accuracy Transmitter was purchased, then a high accuracy
installation kit must be used to ensure correctness.
• Default: High Performance Setup.
a. Pipe Circumference Menu (High Performance):
• This value is the outside circumference of the pipe where the Transmitter
is installed.
• The circumference can be measured with the tape included in the high
performance installation kit.
• Default: 27.096in (~8in diameter)
a. Install Kit Menu (Standard):
• Wall Thickness Menu:
• Select the wall thickness of the installation pipe from the list of standard
pipe wall thicknesses.
• If your wall thickness is not listed, select Other and enter the pipe wall
thickness directly.
• The options available depend on the pipe material selected.
• This screen shows the calculated insertion depth based on the values
previously entered.
• Using the installation alignment kit provided with the IEF, set the depth
to the value displayed:
5. Liquid Type Menu:
• This option species the process liquid to be measured.
• If Ethylene Glycol is selected, another menu will allow the concentration to
be entered.
• Default: Water
8. Analog Conguration Wizard:
• Analog Output Setup Menu:
• This option determines the type of analog output from the Transmitter.
• Default: Current 4 to 20mA
9. Process Variable Menu:
• This option determines which variable is output on the analog signal.
• Default: Velocity
10. Analog Output High Menu:
• This value determines the process value at which the analog output will be
at maximum (e.g. 20 mA, 10 V, 5 V).
• Default: 20.0 ft/s.
6. Pipe Conguration Summary Display: High Performance:
• This screen shows a summary of the settings entered in the pipe
conguration wizard when a high performance installation kit is used.
High performance Setup
7. Continue to Analog Conguration Wizard Question:
• If Continue is selected, the next menu displayed will be in the Analog
conguration wizard.
• If Save & Exit is selected, the settings and values entered during the Pipe
conguration wizard will be stored and put into effect.
• Then the display will show process data. Regardless of selection, the
ENTER button must be used to choose either option.
• This value determines the process value at which the analog output will be
at minimum (e.g. 4mA, 0V).
• Default: 0.0 ft/s
12. Analog Conguration Summary Display:
• This screen shows a summary of the settings entered in the Analog
conguration wizard.
Pulse/Frequency Wizard:
1. Continue to Pulse/Frequency Conguration Wizard Question:
• If Continue is selected, the next menu displayed will be in the Pulse/
Frequency conguration wizard.
• If Save & Exit is selected, the settings and values entered during the Analog
conguration wizard will be stored and put into effect.
• Then the display will show process data.
• Regardless of selection, the ENTER button must be used to choose
either option.
• Default: Continue.
3. Digital Output: Pulse
• Pulse Scale Menu:
◦ This value determines the amount to totalized volume between each pulse
of the output.
◦ Default: 7 gallons/pulse
• Pulse Width Menu:
◦ This value determines the duration of the pulse when active.
◦ Default: 150 milliseconds
• Pulse/Frequency Summary Display:
• This screen shows a summary of the pulse settings entered in the Pulse/
Frequency conguration wizard.
2. Pulse/Frequency Output Menu:
• This option determines the type of digital output from the Transmitter.
• Default: Disabled. If correct press the Enter Button.
• Frequency Output High Menu:
◦ This value determines the process value at which the frequency output will
be at maximum (500Hz).
◦ Default: 20.0 ft/s
1. If Continue is selected, the next menu displayed will be in the Communication
conguration wizard.
2. If Save & Exit is selected, the settings and values entered during the Alarm
conguration wizard will be stored and put into effect.
3. Then the display will show process data. Regardless of selection, the ENTER
button must be used to choose either option.
• Default: Continue
4. Select Protocol Menu:
• This option determines the protocol used by the Transmitter over the
RS-485 interface.
• Default: Disabled.
5. Network Address Menu:
• This value sets the device address on the RS-485 bus. Address range
depends on protocol; BACnet Communications Protocol (0-127), Modbus
Communications Protocol (1-247)
• Default: 127
®
7. Serial Parity Menu (Modbus
Communications Protocol Only):
• This option sets the serial parity on the RS-485 bus.
• Default: Even
®
8. Serial Stopbits (Modus
Communications Protocol Only):
• The option sets the serial Stopbits on the RS-485 bus.
• Default: 1
®
9. Communication Summary Display:
• This screen shows a summary of the settings entered in the Communication
conguration wizard.
6. Baud Rate Menu:
• The option selects the communication speed of the RS-485 bus.
• Default: 19200 (Modbus
®
Communications Protocol), 38400 (BACnet
Communications Protocol)
• After the Communication Wizard is complete, the Transmitter setup is
complete:
• The display will show Setup Complete and transition to display process
Data
Process Value Display:
• This display is the default view after power on of a congured Transmitter.
When the Save & Exit option is chosen from a wizard, this is the next view.
• Use the LEFT and RIGHT buttons to toggle between Flow/Velocity and
Total Flow/Process Temperature view.
• Use the MENU or ENTER button to go to the main menu.
13. Save Default: Save the current settings as the user default values.
14. Restore Defaults: Restore the previously saved user settings.
Device Information
• A list of all setting summaries. Use RIGHT and LEFT to move between
the various summary pages. The last page provided information about the
Transmitter and display.
Create a setup le containing all the options and values selected from the
wizards. This le is stored in the display and can be retrieved by connecting a
USB cable.
Restore Defaults
• This menu restores the saved user conguration to the current conguration.
This provides a means to restore the Transmitter to a known working state.
Reset Total Flow
This menu allows the totalized ow value to be reset to
Damping
• This value determines the amount of time the velocity is averaged. The
display value will reach 99% of the measured value within this time.
• Default: 30 s
Reset to Factory Default
This special menu is accessed by press & holding ENTER and MENU
buttons on the Device Information screen above. Answering Yes, will reset all
selections and values to factory default values.
NOTICE
Key Pad Lockout Feature
• For units with the LCD option a switch (shown in Figure 16) is located on
the display that allows the keypad to be “locked out” to prevent undesired key
presses that could potentially change the transmitter conguration. When the
switch is in the “locked” position the display will generate a padlock symbol in
the lower right corner as shown below.
• Default: Unlocked.
All BACnet Communications settings will be reset as well, including
the values that can only be set via BACnet Communications.
Cal. Factor
• This value sets a custom multiplier of the measured velocity.
Save Defaults
• This menu saves the current conguration as the user default values. This
provides a means to save a known good conguration before making other
changes.
A status blink code is conveyed by the blinking of the status LED (Figure 17) using
the following parameters.
A blink is dened as the LED is ON for 200ms followed by the LED being OFF for
200ms.
If a status code has a tens digit, the tens digit blink code is created and then
followed by a 750ms delay OFF time. Then the ones digit blink code is created.
After a blink code is displayed, there is an OFF time of 2 sec before the blink code
is displayed again.
If more than one condition is true, the condition with the highest code will be
displayed.
Example: Item 3, Invalid Factory Conguration with a blink code of 11.
There would be a state of the LED being ON for 200 msec, then OFF for 200 msec,
then OFF for 750 msec, then ON for 200 msec, then OFF for 200 msec followed by
off for 2 sec before repeating this sequence.
Status
Item Condition
Invalid value
1
Empty pipe
2
Invalid factory conguration
3
NV access failed
4
NV write failed
5
Wiring board not installed
6
Flyback board not installed
7
Analog front end board not installed
8
Coil driver board not installed
9
Process temperature fault
10
Factory variable unlocked
11
Failure to measure process
12
Communication failure
13
Communication failure
14
Communication failure
15
Settings not saved
16
Settings not saved
17
Settings not saved
18
Settings not saved
19
Settings not saved
20
LED Blink
CodeDescriptionCorrective Action
1
2
11
12
13
21
22
24
25
26
33
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
Invalid calibration (Value display on LCD)
The probe is not submerged in the process uid
The factory non-volatile conguration is invalid
The meter failed to read its non-volatile memory
The meter failed to write its non-volatile memory
The wiring board was not detected
The Flyback board was not detected
The Analog Front End board was not detected
The Coil Driver board was not detected
Temperature sensor not responding
The factory variables are unlocked and can be modied
Critical Error! Failed to measure process. (On-screen only)
Communication with the meter has failed. Settings not saved to
meter (On-screen only)
Communication with meter has failed. Attempting to re-establish.
Please wait … (On-screen only)
Critical Error! Failed to access settings in non-volatile storage.
(On-screen only)
Error: File Not Saved! Access Denied (On-screen only)
Error: File Not Saved! Storage Media Timeout (On-screen only)
Error: File Not Saved! Storage Media Not Ready (On-screen
only)
Error: File Not Saved! Storage Media Not Found (On-screen
only)
Error: File Not Saved! Unknown (On-screen only)
Figure 17
Return to factory, calibration required
Ensure the pipe is properly lled, ensure proper
installation depth
Return to factory, conguration and calibration
required
Return to factory for repair
Return to factory for repair
Return to factory for repair
Return to factory for repair
Return to factory for repair
Return to factory for repair
Return to factory for repair
Power cycle, reset, or send lock command to
meter
Power cycle, reset via BACnet/Modbus
Disconnect and reconnect display
Disconnect and reconnect display
Power cycle, reset via BACnet/Modbus
consult factory
Disconnect and reconnect display,
replace SD card on display PCBA
Disconnect and reconnect display,
replace SD card on display PCBA
Disconnect and reconnect display,
replace SD card on display PCBA
Verify SD card is fully inserted into SD card
socket on display PCBA
Disconnect and reconnect display,
replace SD card on display PCBA
If a reverse ow condition exists an “R” with an exclamation mark in a triangle will
appear as shown below:
If an empty pipe condition exists an “E” with an exclamation mark in a triangle will
appear as shown below:
If velocity alarm condition exists a “V” with an exclamation mark in a triangle will
appear as shown below:
MAINTENANCE/REPAIR
Upon nal installation of the Series IEF, no routine maintenance is required, however
if recalibration is desired the unit must be returned to Dwyer Instruments, Inc. to be
calibrated. Contact customer service to receive a Return Goods Authorization number
before shipping you product back for calibration. The Series IEF is not eld serviceable
and should be returned if repair is needed. Field repair should not be attempted and
may void the warranty.
WARRANTY/RETURN
Refer to “Terms and Conditions of Sale” in our catalog or on our website. Contact
customer service to receive a Return Goods Authorization number before shipping
your product back for repair. Be sure to include a brief description of the problem plus
any relevant application notes.
This product uses FreeRTOS (www.FreeRTOS.org) version 9.0.0.
A copy of the original FreeRTOS source shall be provided upon request.