Dwyer Instruments IEF Operating Manual

Series IEF Insertion Electromagnetic Flow Transmitter
5-53/64 [148.0]
61/64 [24.2]
22-1/64
7-3/32 [180.2]
®
Specications - Installation and Operating Instructions
5-53/64
[148.0]
[559.2]
-LCD option shown
Shown with A-IEF-VLV-BR
accessory valve
Bulletin F-IEF-F-1
4-51/64
[121.8]
The Series IEF Insertion Electromagnetic Flow Transmitter is an adjustable
insertion owmeter featuring electromagnetic technology that accurately and reliably measures uid velocity in addition to providing several continuous signal outputs. This series is specically designed to offer superior performance paired with simple installation and use. One unit is adjustable to t pipe sizes from 4 to 36˝ (102 to 914 mm), and offers several output options including selectable BACnet MS/TP or Modbus® RTU communications protocol over 2-wire RS-485 in addition to the standard analog, frequency and alarm outputs.
FEATURES/BENEFITS
• Field congurable setup displays (-LCD integral option or remote accessory A-IEF-DSP) allow for ultimate exibility by accommodating a variety of application congurations with one model through multiple display congurations i.e. pipe size, pipe material, liquid type, analog output, pulse/frequency output, alarm outputs, communication outputs, damping, and calibration factor.
• High performance accuracy is maintained through changes in temperature, density or viscosity.
• Setup Wizard and installation tool are simple to use allowing for quick and precise installation.
• Accessory setup kit A-IEF-KIT ensures exact installation application depth with included thickness gage and measuring tape.
• Long Life Cycle and minimal maintenance requirements with no moving parts to wear or break and electrodes that discourage fouling.
• Isolation valve accessory options allow for installation in operational systems via hot-tap kit or easy removal without system downtime.
• NIST calibration certicate included standard for Carbon Steel Schedule 40 pipes sized 4˝ (102 mm), 6˝ (150 mm), 8˝ (200 mm), and 10˝ (250 mm) with high accuracy option.
APPLICATIONS
• Boiler feed water
• Chilled water
• Open and closed loop condenser water
• Irrigation system
• Municipal water distribution
• Process and coolant ow
• Ground water remediation
• Chemical processing
• Pump protection
• Wastewater
• Mining
SPECIFICATIONS
Service: Compatible clean or dirty non coating, conductive liquids. Range: 0 to 20 ft/s (0 to 6 m/s).*
Wetted Materials: Body shaft/tting: 316 SS; Electrodes: 316 SS; Electrode cap: Polymer/Polystyrene; O-ring: Silicone. Accuracy: IEF-HX-X: ±0.5% of reading at calibrated velocity; ±1% of reading from 2 to 20 ft/s (0.6 to 6 m/s) ±0.02 ft/s (±0.006 m/s) at < 2 ft/s (0.6 m/s). IEF-SX-X: ±1% FS. Temperature Limits: Ambient: -20 to 160°F (-29 to 71°C); Process: 15 to 250°F (-9 to 121°C); Storage: -40 to 185°F (-40 to 85°C). Process Connection: 1˝ NPT or BSPT with accessory full port ball valve options.
Pressure Limits: 400 psi (27.6 bar) @ 100º F (37.8°C). Pressure Drop: < 0.1 psi at 12 ft/s in 4˝ (101.6 mm) and larger pipe. Outputs:
(1) Analog: 4-20 mA, 0-5 V, 0-10 V or 2-10 V (display selectable); (1) Pulse/Frequency: 0-15 V peak pulse, 0 to 500 Hz or scalable pulse output (display selectable); (2) Alarm: (1) Empty pipe detection or minimum/maximum velocity, (display selectable); (1) Reverse ow output indication. Power Requirements: 12-42.4 VDC, .25 A @ 24 VDC; 12-36 VAC. Electrical Connection: Removable terminal blocks, model selectable 1/2˝ female NPT conduit connection, PG 16 gland or PG 16 gland with (2) 10 ft (3 m) 9 conductor 22 AWG plenum rated cables, accessory cable lengths up to 200 ft (61 m) optional.
Display (-LCD option): 2˝ ( 5.08 cm) x 2˝ (5.08 cm) graphic LCD with backlight. Conductivity: >20 microsiemens. Enclosure Material: Powder coated die cast aluminum. Enclosure Ratings: NEMA 6P (IP68) (Non display models); NEMA 4X (IP66)
(-LCD option).
Agency Approvals: BTL, CE, NSF/ANSI 61 and 372.
COMMUNICATIONS (-COM OPTION) Type: BACnet MS/TP or Modbus® RTU communication protocol (default disabled,
display selectable). Supported Baud Rates: 9600, 19200, 38400, 57600, 76800, or 115200 bps (display selectable).
Device Load: 1/8 unit load.
ADDITIONAL SPECIFICATIONS Applicable Pipe Material: Most popular plastic and metal pipes; i.e. Carbon steel,
SS, copper, UPVC/PVDF, galvanized steel, mild steel, and brass**. Applicable Pipe Size: IEF-HX-X: 4 to 10˝ (101 to 254 mm); IEF-SX-X: 4 to 36˝ (101 to 914 mm).
Diameter Length Requirements: >10 upstream, >5 downstream. Glycol: 0 to 100% display selectable.
*For max owrates >10 ft/s (3 m/s) order option -CC. **Brass ttings and pipe not suitable for use with NSF certied models.
Modbus® is a registered trademark of Schneider Automation, Inc.
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
1
Phone: 219/879-8000
Fax: 219/872-9057
www.dwyer-inst.com
e-mail: info@dwyermail.com
MODEL CHART
THUMBSCREW
BODY
RULER
Example IEF -L N -CND -LCD IEF-LN-CND-LCD Series IEF Insertion electromagnetic ow transmitter
Accuracy L
G
S
F
I
E
T
H
Process Connection Electrical
Housing
Connector
Options LCD
Note: For CC option, must provide completed conguration paperwork.
ACCESSORIES Model Description A-IEF-KIT
A-IEF-DSP A-IEF-CBL-50 A-IEF-VLV-BR A-IEF-VLV-SS A-IEF-INGD A-IEF-PA
Safety Information
WARNING
• Only qualied professionals equipped with the necessary required trade skills should install, remove or service this product in any way. Failure to follow the proper installation procedures could lead to death or permanent injury.
• This product is intended to be installed in pressurized pipe applications. In this event, product will be under pressure, caution should be taken to properly vent system prior to installation or removal of the unit. Failure to do so could result in equipment damage and/or serious bodily injury.
CAUTION
N
B
CND
PG 10
Setup kit (includes setup display, thickness gage and measuring tape) Setup display Plenum rated cable 50 ft (15.2 m) 1-1/4˝ full port isolation valve brass 1-1/4˝ full port isolation valve 316SS Installation alignment kit AC wall adapter
Standard accuracy < 10˝ (250 mm) pipe; 1% FS Standard accuracy > 10˝ (250 mm) pipe; 1% FS Standard accuracy 4 to 36˝ (100 to 900 mm) pipe; 1% FS High accuracy 4˝ (100 mm) pipe; 1% of reading High accuracy 6˝ (150 mm) pipe; 1% of reading High accuracy 8˝ (200 mm) pipe; 1% of reading High accuracy 10˝ (250 mm) pipe; 1% of reading High accuracy 4 to 10˝ (100 to 250 mm) pipe; 1% of reading 1˝ male NPT 1˝ male BSPT 1/2˝ female NPT conduit connection without cable PG gland without cable PG gland with 10’ cable Integral LCD display
COM
BACnet or Modbus® communication protocol (display selectable)
NIST
Six point NIST traceable calibration certicate
FC
Factory calibration certicate for 0.5% of reading at single point
CC
Custom congured for specic installation
OPERATING PRINCIPLE
• Per Faraday’s Law of electromagnetic induction, a voltage is induced in a conductor when it passes through a magnetic eld, and the induced voltage will be directly proportional to the velocity of the conductor.
• The Series IEF Flow Transmitter generates pulsating magnetic elds in the probe to induce a voltage into a conductive uid owing through the pipe.
• Electrodes located on the probe measure the induced voltage. Electronics and rmware within the enclosure convert the voltage to velocity and ow rate while using various outputs to convey the data to connected systems (i.e. display devices, data acquisition systems, or BTU meters).
INCLUDED WITH THE FLOWMETER
Carefully unpack the shipping container of your new Series IEF Insertion Electromagnetic Flow Transmitter and remove the following items:
• (1) Series IEF Insertion Electromagnetic Flow Transmitter
• (1) A-IEF-INGD Installation Alignment Kit: (1) Alignment Scale (2) Alignment Rods (2) Thumbscrews
• (1) 3 mm Allen Wrench (not shown)
(2 PLACES)
Thumbscrews (2)
ROD
Alignment scale (1)
RECOMMENDED TOOLS
• (2) 12˝ (300 mm) adjustable wrenches
• (1) 12˝ (300 mm) pipe wrench
SETUP
Selecting Installation Location
1. Although the unit may be installed in any orientation, the ideal mounting position is on the side of the pipe (2 o’clock or 10 o’clock position)* as this generally minimizes possible air or sediment interference with the Series IEF. It is not reccomended to mount the unit below the pipe (6 o’clock position).
When installing a unit with an integral display select an installation
NOTICE
location that allows for clear viewing of the display and proper earth ground.
Insert the IEF in a pipe via a threaded Tee, Saddle, or welded integrally reinforced branch connection outlet tting.
If a Hot-Tap option is required, use a 1-1/4˝ valve kit with proper mounting hardware available in Model A-IEF-VLV-BR or A-IEF-VLV-SS. A 1˝ (25.4 mm) hole in the pipe is required for proper installation.
Rods (2)
Figure 1
Series IEF
**
• Refer to Model Chart and Specications for the applicable options to your unit.
• Ensure the unit is sufciently grounded as stated in this bulletin.
• Depressurize and vent systems without Hot-tap valve prior to installation or removal.
• Conrm the Series IEF wetted material is chemically compatible with process media prior to installation and use.
• Do not exceed maximum temperature and pressure specications.
• Wear appropriate personal protective equipment during installation, removal and or service of the unit.
• Altering the product construction in any way may adversely affect product operation and voids warranty.
• Prior to attempting to wire or service the Series IEF disconnect from power.
Figure 2
2
2. Select a location that will minimize ow distortion with adequate upstream and
KEYING FEATURE
KEYING FEATURE
downstream pipe diameters as displayed. Ideal installation will have a minimum of 10 pipe diameters upstream relative to the instrument and a minimum distance of 5 pipe diameters downstream.
NOT RECOMMENDED RECOMMENDED
5x
20x
20x
5x
FLOW DIRECTION
Figure 3
INSTALLATION
1. To prepare the meter for installation, mount the provided alignment scale to the side of the meter with the two provided thumbscrews. The thumbscrews are to be inserted through the alignment scale slots and into the holes in the side of the lid as shown in Figure 4, nger tighten only. Be sure to orient the alignment scale as shown in gure below. Actual scale setting determined in next step.
For Field Congurable Models
2. For eld conguration, a display is required (-LCD option or accessory A-IEF­ DSP) and needs to be powered via normal eld wiring or with the AC wall adapter accessory A-IEF-PA ( A-IEF-DSP and A-IEF-PA are also available in the accessory setup kit A-IEF-KIT).
3. When using the AC wall adapter and the cable is supplied, connect the red (positive +) and black (common -) wires of the cable bundle marked “A” to the open terminals of the AC wall adapter. This will provide temporary power to the meter to complete the installation set up.
4. For eld wiring, refer to the wiring chart tag attached to the Series IEF to identify the terminal block pins for positive (+) and common (-) connection.
5. Unscrew the four captured cover screws using the supplied 3 mm Allen wrench to remove and set aside enclosure cover.
6. Insert one connector of the ribbon cable supplied in the setup kit into the connector labeled “Display” in the middle of the unit. Be sure to orient the keying feature/tab. See Figure 5 below:
Figure 5
7. Plug the other end of the cable into the bottom of the supplied portable display being sure to orient the keying feature/tab as shown:
USE LID TO ENCLOSURE GAP AS INDICATOR LINE
Figure 4
For Custom Congured Models (-CC Option)
2. Locate the conguration tag attached to the Series IEF to identify the value of the alignment scale setting. Position the alignment scale such that the scale setting is lined-up with the seam of the enclosure as shown in Figure 4. Minor scale marks are in 1/20ths Securely tighten the thumbscrews.
3. Refer to Preparing the Unit for Installation section.
Figure 6
8. Apply power to the unit and the display will turn-on automatically. Follow the on screen directions for entering the necessary parameters to setup the unit and obtain the alignment scale setting value.
NOTICE
DSP, thickness gage UTG and measuring tape A-IEF-MSTP used to obtain these measurements. When the precise pipe measurement information is known select Option 2 High Performance setup in the Install Kit option of the display selection
When using measuring tape A-IEF-MSTP to measure pipe
NOTICE
of the pipe without insulation.
Precise pipe measurements are required for high performance installation. The A-IEF-KIT includes setup display A-IEF-
circumference use the 100ths side to measure the circumference
3
FLOW
OOL
PIPE ALIGNMENT ROD MUST
g
1
8
Preparing the Unit for installation (Refer to Figure 7)
1. Apply appropriate sealant to the process collet (5) threads such as application suitable sealant tape or paste.
2. Install the process collet (5) in valve (6) then tighten by hand.
3. Tighten the process collet (5) with a wrench using the hex geometry until snug.
NOTICE
4. Slowly open the valve handle (7) checking for leaks.
5. If leaks occur around threaded connections, close the valve and tighten those connections.
Use two wrenches, one to hold the valve and another wrench to turn the process collet.
2
3. Rotate the transmitter so the pipe alignment rod is parallel with the ow in the pipe.
BE PARALLEL WITH PIPE
FLOW DIRECTION
Figure 9
9
Figure 7
3
7
1. Enclosure
2. Cable Nut
3. Probe Shaft
4. Compression Fitting
5. Process Collet
6. Valve (optional)
7. Valve Handle (optional)
8. Pipe
9. Sensor Probe
4
5
6
Do not adjust housing compression nut at top of probe shaft (3).
NOTICE
Sensor Alignment
A depth and ow alignment installation tool is provided to ensure proper depth insertion and ow alignment. To set the insertion depth verify the alignment scale has not moved from its original setting based on the alignment scale value set previously.
Loosen compression nut (4) to allow the shaft (3) freedom to travel up and down and rotate inside the process collet (5).
Install Depth and Alignment Rods
1. Remove alignment rods from sides of alignment scale by sliding them out.
2. Insert the two rods into the alignment scale as shown.
4. Slide the shaft (3) down into the process collet (5) until the depth rod contacts the pipe. If pipe insulation is present press the rod through the insulation.
a. Tighten the nut (4) to 15 ft.-lbs (20.3 N m) b. Remove the ow alignment rod and loosen the thumbscrews to slide the alignment tool up to allow removal of the depth alignment rod. Store both rods in the storage slots on the sides of the alignment scale. Tighten thumbscrews and leave alignment tool mounted on unit for storage.
GROUNDING
Metallic Pipe
For proper operation the instrument must be earth grounded. Connect a ground wire to meter housing via the ground lug on the housing collet. Connect the ground wire to a known earth ground. If the pipe is grounded, connect the ground wire to the metal pipe using suitable devices such as grounding clamps.
Grounding lu
Figure 10
Non-Metallic Pipes
Connect a ground wire to the transmitter housing per the ground lug on the housing collet. Connect the ground wire to a known earth ground. Ground the uid to earth.
ALIGNMENT ROD
Figure 8
ALIGNMENT T
DEPTH ROD
GROUNDING
RINGS
Figure 11
POWER SUPPLY
Choose a power supply with a voltage and current rating sufcient to meet the power specications under all operating conditions. If the power supply is unregulated, make sure the output voltage remains within the required voltage range under all power line conditions.
4
WIRING DIAGRAM
Cable Terminal # Wire Color Description Note A A A B External
Analog Current Output
B B
Analog Voltage Output
B B
Frequency Output
B B
RS-485 Communication (optional)
B B Reverse Flow
A A Alarm
A A
Pulse
A A No Connection
B B A A
1 2 13 14
3 4
5 6
8 7
11,12 9,10
15 16
17 18
19 20
-
-
-
-
Red
Black Shield Shield
-
Brown Blue
Green
White
Violet Grey
Orange Yellow
Brown Blue
Green
White
Orange Yellow
Red
Black Violet Grey
Power Supply Positive Power Supply Common
-
­Earth/Chassis Ground
(+) Analog current output (-) Analog output common
(+) Analog voltage output (-) Analog output common
(+) Frequency output (-) Analog output common
RS-485 (+) RS-485 (-)
Isolated solid state output N.O. Isolated solid state output N.O.
Isolated solid state output N.O. Isolated solid state output N.O.
Isolated solid state output N.O. Isolated solid state output N.O.
Do not connect Do not connect Do not connect Do not connect
Connect to +24VDC or VAC transformer Connect to 24VDC/VAC common If used - Application Dependant If used - Application Dependant
-
4 to 20 mA process output Current output common
May be congured; 0 to 10 V, 0 to 5 V, 2 to 10 V, etc. Voltage output common
0 to 500 Hz output (@ 0/15 VDC output level) Frequency output common
On board short for daisy chain connection On board short for daisy chain connection
50 V AC/VDC @ 100 mA maximum 50 V AC/VDC @ 100 mA maximum
50 V AC/VDC @ 100 mA maximum 50 V AC/VDC @ 100 mA maximum
50 V AC/VDC @ 100 mA maximum 50 V AC/VDC @ 100 mA maximum
-
-
-
-
The Cable column identifying cable A and B is reective of units that include factory installed cabling.
Wiring PCBA shown in Figure 12 with terminal block numbers as listed in above wiring diagram chart.
Figure 12
5
Determining probe insertion depth for models with a display
The Series IEF transmitter will calculate the probe insertion depth used with -LCD display option or A-IEF-DSP display when the steps below are followed.
Follow the on screen directions for entering the circumference and wall thickness dimensions. See the Electronic Control Data Setup section of this manual for more information.
NOTICE
A-IEF-MSTP to obtain these measurements. When the precise pipe measurement information is known, select option 2 (High Performance Setup) under the Install Kit Menu when prompted by the display as shown below. Precise pipe measurements are required for a high performance installation.
1. To measure the pipe circumference remove any existing insulation at the location where the transmitter will be installed. Wrap the tape measure around the pipe to measure the circumference at the selected location using the 100ths side of the tape. Record this measurement for entering into the unit when the circumference measurement is requested.
It is recommended to use the A-IEF-KIT which includes a setup display A-IEF-DSP, thickness gage UTG and measuring tape
Determining probe insertion depth for models without a display
For models without a display the following formulas allow for calculating the alignment scale value for setting the depth of the probe into the pipe. Also included are wall thickness charts for various pipe materials and sizes.
Pipes < 11 in (< 279 mm) diameter: 7.1625-1/2*D Pipes 12 inches to 36 inches: 7.1625-(0.1*(D-2*WT))+WT
Position the alignment scale such that the alignment scale setting is lined-up with the seam of the enclosure as shown in Figure 13. Minor scale marks are in 1/20ths Securely tighten the thumbscrews.
2. To measure the wall thickness of the pipe use the thickness gage UTG. Following the separate directions provided with the UTG gage and record the thickness. This measurement will be needed to enter into the unit after the circumference data is entered.
Figure 13
USE LID TO ENCLOSURE GAP AS INDICATOR LINE
6
WALL THICKNESS
Carbon Steel
Pipe Diameter (in) DN (mm) SCH5 (in) SCH5 (mm) SCH10 (in) SCH10 (mm) SCH40 (in) SCH40 (mm) SCH80 (in) SCH80 (mm)
4.5
5.563
6.625
8.625
10.75
12.75 14 16 18 20 24 32 36
WALL THICKNESS
Stainless Steel
Pipe Diameter (in) DN (mm) SCH5 (in) SCH5 (mm) SCH10 (in) SCH10 (mm) SCH40 (in) SCH40 (mm) SCH80 (in) SCH80 (mm)
4.5
5.563
6.625
8.625
10.75
12.75 14 16 18 20 24 32 36
114.30
141.30
168.28
219.08
273.05
323.85
355.60
406.40
457.20
508.00
609.60
813.00
914.40
114.30
141.30
168.28
219.08
273.05
323.85
355.60
406.40
457.20
508.00
609.60
813.00
914.40
0.083
0.109
0.109
0.109
0.134
0.156
0.156
0.165
0.165
0.188
0.218
0.250
0.250
0.083
0.109
0.109
0.109
0.134
0.156
0.156
0.165
0.165
0.188
0.218
0.250
0.250
2.110
2.770
2.770
2.770
3.400
3.960
3.960
4.190
4.190
4.780
5.540
6.350
6.350
2.110
2.770
2.770
2.770
3.400
3.960
3.960
4.190
4.190
4.780
5.540
6.350
6.350
0.120
0.134
0.134
0.148
0.165
0.180
0.250
0.250
0.250
0.250
0.250
0.312
0.312
0.120
0.134
0.134
0.148
0.165
0.180
0.188
0.188
0.188
0.218
0.250
0.312
0.312
3.050
3.400
3.400
3.760
4.190
4.570
6.350
6.350
6.350
6.350
6.350
7.920
7.920
3.050
3.400
3.400
3.760
4.190
4.570
4.780
4.780
4.780
5.540
6.350
7.920
7.920
0.237
0.258
0.280
0.322
0.365
0.406
0.437
0.500
0.562
0.593
0.688
0.688
0.750
0.237
0.258
0.280
0.322
0.365
0.375
0.375
0.375
0.375
0.375
0.375
0.375
0.375
6.020
6.550
7.110
8.180
9.270
10.310
11.130
12.700
14.270
15.090
17.480
17.480
19.050
6.020
6.550
7.110
8.180
9.270
9.525
9.525
9.525
9.525
9.525
9.525
9.525
9.525
0.337
0.375
0.432
0.500
0.593
0.687
0.750
0.843
0.937
1.031
1.218
1.218
1.218
0.337
0.375
0.432
0.500
0.500
0.500
0.500
0.500
0.500
0.500
0.500
0.500
0.500
8.560
9.530
10.970
12.700
15.090
17.480
19.050
21.440
23.830
26.190
30.960
30.960
30.960
8.560
9.525
10.970
12.700
12.700
12.700
12.700
12.700
12.700
12.700
12.700
12.700
12.700
WALL THICKNESS
Copper Pipe
Diameter (in) DN (mm)
4.125
5.125
6.125
8.125
10.25
12.25 14 16 18 20 24 32 36
WALL THICKNESS PVC
Pipe
Diameter (in) DN (mm)
4.5
5.563
6.625
8.625
10.75
12.75 14 16 18 20 24 32 36
104.78
130.18
155.58
206.38
257.18
307.98
355.60
406.40
457.20
508.00
609.60
813.00
914.40
114.00
141.00
168.00
219.00
273.00
324.00
356.00
406.00
457.20
508.00
609.60
813.00
914.40
Type K Type L Type M
in mm in mm in mm
0.134
3.400
0.114
0.160
4.064
0.192
4.876
0.271
6.883
0.341
8.661
0.411
10.439
0.471
11.963
0.471
11.963
0.541
13.741
0.610
15.494
0.680
17.272
0.818
20.777
1.096
27.838
SCH40 SCH80
in mm in mm
0.237
6.020
0.258
6.550
0.280
7.110
0.322
8.180
0.365
9.270
0.406
10.300
0.437
11.100
0.500
12.700
0.562
14.274
0.593
15.062
0.687
17.450
0.874
22.200
0.968
24.587
0.125
0.140
0.200
0.356
0.411
0.459
0.459
0.513
0.568
0.623
0.732
0.950
0.337
0.375
0.432
0.500
0.593
0.687
0.750
0.843
0.937
1.031
1.218
1.572
1.754
2.895
3.175
3.556
5.080
9.042
10.439
11.658
11.658
13.030
14.427
15.824
18.593
24.130
8.560
9.520
11.000
12.700
15.100
17.400
19.000
21.400
23.800
26.187
30.937
39.929
44.552
0.095
0.109
0.122
0.170
0.308
0.356
0.398
0.398
0.445
0.493
0.541
0.636
0.826
2.413
2.768
3.098
4.318
7.823
9.042
10.109
10.109
11.303
12.522
13.741
16.154
20.980
7
Printing out conguration values
1
8
NETWORK TERMINATION JUMPER
After installation is complete a table of conguration values can be gathered from the transmitter to print out and insert into one of the hanging plastic envelopes for future reference. The housing cover/display needs to be removed for access to the display port to retrieve the table of conguration values. To do so:
1. Unscrew the four captured cover screws using the supplied 3 mm Allen wrench to remove the enclosure cover. Leave the display cable connected to the main unit.
2. Insert a customer supplied mini-USB cable into the USB connector on the bottom side of the display PCB.
3. Connect the other end into a standard USB port in a laptop.
4. The Series IEF transmitter will appear as a standard USB drive on the laptop.
5. The le name with the conguration values is in the format of: serial number.txt. The serial number can be found on the product label on the side of the transmitter.
6. Print out the conguration values and insert into one of the hanging plastic envelopes for future reference
7. Re-attach the housing cover/display by reinserting the four 3 mm screws.
CONFIGURATION DATA PRINT OUT EXAMPLE [Device Information]
MeterTag=Series IEF SerialNumber=Andrew2 ModelNumber=IEF-XX-COM-LCD DateCode=20180101
[Setup Information]
CalibratedBy= Date= Units=English VelocityUnit=ft/s FlowUnit=ft³/s VolumeUnit=gal
[Pipe Conguration]
LiquidType=Water PipeMaterial=Carbon Steel PipeCircumference=27.096 in PipeWallThickness=0.322 in AlignmentScaleValue=1.85
[Analog Output]
AnalogOutputType=Current 4-20mA AnalogOutputVariable=Velocity ft/s AnalogOutputHigh=20.00 AnalogOutputLow=0.00
[Pulse/Freq. Output Setup]
Pulse/Freq. Output=Disabled
[Alarm Output Setup]
AlarmOutput=Empty Pipe Alarm
[Communication]
CommunicationProtocol=Disabled
Removing Series IEF Transmitter
1. To remove the transmitter from an installation without a valve depressurize the pipe and skip to step 4. If installed with a valve loosen compression tting (4) and withdraw the transmitter shaft fully through the valve until it stops.
2. Tighten compression tting (4) snug.
3. Close valve (6) via valve handle (7).
4. Remove transmitter by unscrewing process collet (5) from value (6).
CAUTION
occur to the probe ns.
Network Termination Jumper
On the terminal block PCBA there is a jumper, J1 (see Figure 15), that enables or disables a network termination resistor as dened below: When the network jumper is placed in the ON position there is a 120 ohm termination resistor in place. When the network jumper is placed in the OFF position there is no termination resistor in place. Default: OFF
Be sure to support the housing end of the transmitter to prevent it from ipping while unscrewing process collet (5) as damage may
2
4
5
6
3
9
Figure 14
7
1. Enclosure
2. Cable Nut
3. Probe Shaft
4. Compression Fitting
5. Process Collet
6. Valve
7. Valve Handle
8. Pipe
9. Sensor Probe
Figure 15
8
Communication Overview
The Insertion Magmeter supports BACnet MS/TP and Modbus® RTU over 2-wire RS-
485. Selection of protocol and conguration of serial parameters require the use of the display.
BACNET
BACnet Object Overview Supported BACnet Objects
Object Type Dynamically Creatable Dynamically Deletable Object Identier Object Name Device No No 607XXX “Series IEF 607xxx” Analog Input No No AI1
Analog Value No No AV1
Binary Value No No BV1
Bit String
Value
No No BSV1
AI2 AI3
AV2 AV3 AV4 AV5 AV6 AV7 AV8 AV9 AV10 AV11 AV12 AV13 AV14 AV15 AV16 AV17
BV2 BV3 BV4
BSV2
Velocity Inlet Temperature Outlet Temperature Volume Flow Mass Flow Total Flow Power Total Energy Heat Energy Cooling Energy Differential Temperature YTD Max Power YTD Min Power MTD Max Power MTD Min Power Inlet YTD Average Temperature Outlet YTD Average Temperature Heat Changeover Temperature Process Pressure Ethylene Glycol Concentration Reverse Flow Empty Pipe Reset Total Flow Reset Energy Statistics Flow Meter Status Flags Energy Meter Status Flags
BACnet Objects: Device Object
Property Default Value Property Data Type Access Object Identier Object Name Object Type System Status Vendor Name Vendor Identier Model Name
Firmware Revision
Application Software Version
Location
Description Protocol Version
Protocol Revision
Protocol Services Supported Protocol Object Types Supported Object List Active COV Subscriptions Maximum APDU Length Accepted Segmentation Supported
Local Time
Local Date UTC Offset Daylight Savings Status APDU Timeout Number of APDU Retries Max Master Max Info Frames Device Address Binding Database Revision Property List Serial Number Property List
607xxx “Series IEF 607xxx” DEVICE(8) Operational(0) “Dwyer Instruments, Inc.” 607 “IEF-??-??-COM” “?.?” “?.?.?”
1 14 See PICS See Table Above See Table Above
480 NO_SEGMENTATION (3)
0
False
6000 3 127 1 Empty 1
“xxxxxxxx”
BACnetObjectIdentier CharacterString(40) BACnetObjectType BACnetDeviceStatus CharacterString Unsigned CharacterString CharacterString CharacterString CharacterString(32) CharacterString(32) Unsigned Unsigned BACnetServicesSupported BACnetObjectTypesSupported BACnetArray List of BACnetCOVSubscription Unsigned BACnetSegmentation Time Date Integer Boolean Unsigned Unsigned Unsigned Unsigned BACnetAddressBinding Unsigned BACnetARRAY[N] of BACnetPropertyIdentier CharacterString BACnetARRAY[N] of BACnetPropertyIdentier
Read/Write Read/Write
Read Read Read Read Read Read Read
Read/Write Read/Write
Read Read Read Read Read Read Read Read Read Read
Read/Write Read/Write Read/Write Read/Write Read/Write
Read Read Read
Read Read
9
Loading...
+ 19 hidden pages