Dwyer Instruments Installation And Operating Instruction Manual
Specifications and Main Features
Frequently Asked Questions
User Manual
Bulletin AQ-GSTC
3-45/64
[94.06]
3
-1/8
[
107.95]
2
-15/64
[
56.75]
4-17/32
[115.09]
5-7/64
[129.78]
3-59/64
[100]
2-15/64
[57]
2-55/64
[
73]
3
-23/64
[
85]
Series GSTC Carbon Monoxide/Nitrogen Dioxide Gas Transmitter
Specifications - Installation and Operating Instructions
With LCD
he Series GSTC Carbon Monoxide/Nitrogen Dioxide Gas Transmitter
T
Without LCD
monitors the gas concentration in underground parking garages and loading docks.
The carbon monoxide transmitter is used to measure the exhaust of gasoline
engines, while the nitrogen dioxide transmitter is used for diesel engines. The
Series GSTC is compatible with either BACnet or MODBUS
rotocol, allowing the transmitter to be used with almost any building management
p
ontroller. The GSTC output is communicated over an RS-485 wire via BACnet or
c
MODBUS
®
communication protocol. To maximize the accuracy of the Series GSTC,
the sensor can be field-calibrated using the A-449 remote LCD display. When the
sensor reaches the end of its life, the display will indicate that the sensor needs to
be replaced.
BACnet and MODBUS
®
communication protocol recommend limiting the number of
nodes in any segment to 32. Therefore, the transceiver may be rated at one unit
load. Fractional loads are also acceptable. The Series GSTC accounts as an
eighth of a load on the MSTP network.
WARNING
Disconnect power supply before installation to prevent electrical
shock and equipment damage. Make sure all connections are in
accordance with the job wiring diagram and in accordance with national and local
electrical codes. Use copper conductors only.
NOTICE
Use electrostatic discharge precautions (e.g., use of wrist
straps) during installation and wiring to prevent equipment
damage.
NOTICE
Avoid locations where severe shock or vibration, excessive
moisture, or corrosive fumes are present.
NOTICE
Do not exceed ratings of this device, permanent damage not
covered by warranty may result.
NOTICE
The electrochemical sensors should be stored in an
environment with a minimum humidity level of 20% RH. If the
sensor dries out, replacements will not be covered under warranty, but they can be
revived by allowing them to stabilize in an environment above 40% RH for 10 days.
Once revived, they need to be recalibrated before use.
INSTALLATION
NOTICE
These are general guidelines. Local laws or ordinances will take
precedence.
• The transmitter should be mounted at normal breathing height, approximately 5
to 6 ft above the floor.
• The unit may be mounted in the horizontal or vertical position. It should be
mounted in an area that is shielded from direct contact with the elements or direct
sunlight.
• Mount in an area that will prevent the sensor from having any direct contact with
water.
• The unit should be placed in an area that will give an average of the air quality.
Do not place the unit so it will receive direct engine exhaust. Prolonged exposure
to direct engine exhaust may damage the sensor.
®
communication
Duct MountWall Mount
PECIFICATIONS
S
Sensor: Field replaceable
electrochemical, 4 years typical
lifespan.
Range: CO: 0 to 500 PPM, NO
PM.
P
utput Drift: <5% per year in air.
O
Coverage Area: 5000 to 7500 sq ft
typical.
Accuracy: CO: 2% FS, NO
at the time of calibration.
Resolution: CO: 1 PPM; NO
PPM.
Temperature Limits: -4 to 122°F (-20
to 50°C).
Storage Temperature: For best
sensor life, 32 to 68°F (0 to 20°C).
Humidity Limits: 15 to 90% RH
constant; 0 to 99% RH intermittent.
Response Time: <45 s to 90% CO,
<25 s to 90% NO
2.
Wall MountDuct MountWall Mount
2: 10
2: 3% FS,
2: 0.1
pan and Zero Adjustment: Via
S
pushbutton, using optional A-449
display. Zero only via BACnet or
MODBUS
®
communication protocol.
Housing: UV resistant glass filled
olycarbonate.
p
utput Signals: BACnet MS/TP or
O
MODBUS
®
RTU (switch selectable)
communication protocol.
Power Requirements: 10 to 36 VDC
or isolated 21.6 to 33 VAC.
Electrical Connection: Removable
terminal block, knock outs for conduit
fitting.
Calibration: Via pushbuttons using A449 auxiliary display. Span gas
concentration is field selectable.
Figure 1 shows the location of the wiring terminal, 8 position DIP Switch SW1, used
for configuring the RS-485 address, the 4 position DIP Switch SW2, used for
configuring hardware and software options, sensor, span and zero adjustments,
and status LEDs.
The device provides three LEDs to indicate status and activity. The LEDs are
located to the right of DIP Switch SW1. The yellow LED indicates that the unit is
sending a BACnet or MODBUS
the unit is receiving a BACnet or MODBUS
this specific device. The red LED will flash once periodically if the BACnet or
MODBUS
®
communication protocol address is set incorrectly or the red LED will
®
communication protocol. The green LED indicates
®
communication protocol addressed to
flash twice periodically if the auto serial configuration is in progress.
. Remove the cover plugs from the face of the unit and the top cover.
1
. Disconnect the display cable from the USB connector on the main circuit board
2
if present).
(
3. Remove the desired conduit fitting knock out and install conduit fitting (not
provided).
4. Position the transmitter where it is to be mounted and mark the mounting holes
n each corner of the housing.
i
. Drill or punch out marked locations.
5
. Place the transmitter box over mounting holes on wall and align. Install wall
6
ount screws (not provided) in mounting holes.
m
7. Proceed with wiring diagrams according to Figures 3 and 4.
8. Set DIP Switches SW1 and SW2 as desired. Refer to Figure 5, Figure 6, and
Appendix I.
. Reconnect the LCD cable to the USB port on the main circuit board (if present).
9
0. Replace cover and cover plugs on the face of the unit.
1
CO:
Locate GSTC carbon monoxide transmitter about 5 ft (1.5 m) off the floor. Carbon
monoxide weighs about the same as air and distributes evenly throughout the
monitored space. Install GSTC CO alarm at least 15 to 20 ft (4.6 to 6.1 m) away
rom boiler or fuel burning heat source. Avoid extremely dusty, dirty, humid or
f
reasy areas. Do not place in direct sunlight or areas subjected to extreme
g
emperature. Do not place in turbulent air, near fans, heat vents, air conditioners,
t
air returns or open windows. Blowing air may prevent CO from reaching the CO
sensor.
NO
:
2
O
ensors should be mounted in the breathing zone, 4 to 6 ft (1.2 to 1.8 m) from
N
s
2
he floor. This is primarily because NO
t
etected in the area where people would be exposed to it, but also because 4 to 6
d
ft from the floor is an appropriate elevation to detect NO
s a poisonous gas which should be
i
2
gas.
2
Duct Mounting
Duct mounting kit includes an air flow pitot tube, air filter with barbed connections,
two short pieces of tubing, and one long piece of tubing.
igure 3 shows how to connect the GSTC in a network containing a common
F
ower supply. Use a cable containing two twisted pairs. One pair is to be used for
p
he power and common. The other pair is to be used for A(-) and B(+). Attach the
t
hields together with a wire nut. This configuration is not suitable for AC supplies.
s
Use a DC supply only. Care should be taken that there are not too many devices
powered from the same supply as voltage drops will occur in the wiring. If you have
many devices, or have long cable runs, the local supply configuration, shown in
igure 4, may be a better choice.
F
igure 3 - Common Power Supply
F
igure 4 shows how to connect the GSTC in a network containing individual local
F
upplies. Use a cable containing a single conductor and a twisted pair. The single
s
conductor is to be used for common, and the pair is to be used for A(-) and B(+).
Attach the shields together with a wire nut. Both AC and DC supplies are suitable
for this configuration.
1. Mount the pitot tube into the duct observing the flow direction marked on the pitot
tube.
2. Attach the two short pieces of tubing to the barbed connections on each side of
the air filter. See Figure 2.
3. Attach the remaining side of one of the short pieces of tubing to the barbed
connection on the transmitter.
4. Attach the remaining side of the other short piece of tubing to the high port on
the pitot tube.
5. Attach the long piece of tubing to the open barbed connection on the transmitter.
6. Attach the other end of the long tubing to the low port on the pitot tube.
Figure 2
WIRING
NOTICE
Wiring should comply with Electrical Characteristics of
Generators and Receivers for Use in Balanced Digital Multipoint
Systems, TIA-EIA-485-A-1998, Telecommunications Industry Association, 1998.
NOTICE
Building Automation and Control Networks, American Society of Heating,
BACnet installations should comply with ANSI/ASHRAE
Standard 135-2010 BACnet A Data Communication Protocol for
Refrigerating and Air-Conditioning Engineers, Inc., 2010.
NOTICE
Specification and Implementation Guide V1.02, MODBUS
NOTICE
NOTICE
MODBUS®communication protocol installations should comply
with MODBUS
®
communication protocol over Serial Line
Communication wiring must be in a daisy-chain fashion. Star
connections are not permitted.
Cable shield must be connected to earth ground at one location
only.
®
Organization, Inc., 2006.
Figure 4 - Local Power Supply
All devices in the network should be daisy-chained. Star connections and T
connections are not permitted.
The A(-) and B(+) lines must be terminated at both ends with a 120 ohm resistor.
If the GSTC is an end device it has an on-board resistor that may be used. See
Table 1 to enable it.
The network must be biased properly. If needed, there are bias resistors on-board
the GSTC. No more than two sets of bias resistors should be enabled in the
network. See Table 1 to enable them.
ip Switch Configurations
D
se DIP Switch SW1 (see Figure 5) to configure the RS-485 address of the device.
U
valid address depends on the protocol selected. Valid BACnet addresses range
A
rom 1 to 127. Valid MODBUS
f
247. By default, the device is shipped with MODBUS
®
ommunication protocol addresses range from 1 to
c
®
communication protocol
selected and the address set to 127, as shown in Figure 5. A valid and unused
address should be set before connecting to an existing network. See Appendix I to
onfigure the required address using DIP Switch SW1. The device will not function
c
roperly if an invalid address is set. During the power up sequence, the LCD (if
p
resent) will display the RS-485 address as the primary value and either “BAC” to
p
ndicate BACnet or “MOD” to indicate MODBUS
i
®
ommunication protocol as the
c
primary text. If the RS-485 address is invalid, the invalid address is shown as the
primary value with “ERR” as the primary text, and the red LED will periodically blink
once.
o activate auto serial configuration, set a valid RS-485 address using DIP Switch
T
W1, connect the serial bus, common and power wires, and apply power. The
S
evice will power up and begin examining the serial bus for communication.
d
When the device is installed offline or away from the main network, it is necessary
to generate the appropriate traffic in order to configure the serial communication
whether BACnet or MODBUS
onfiguration is in progress, the device may not respond. The device may require
c
ultiple read requests to complete the serial configuration process.
m
he auto serial configuration process is completed once a message addressed to
T
®
communication protocol is selected. While the serial
the device is received and processed successfully. If the serial configuration of the
bus changes, a power cycle of the device is required to restart the auto serial
configuration process.
ore detailed information for BACnet protocol can be found in Appendix II, and
M
nformation for MODBUS
i
®
ommunication protocol can be found in Appendix III.
c
MENU
The menu is only shown if a display is present. Figure 7 below outlines the display
components. To enter the menu, press and hold both the SPAN and ZERO
ushbuttons for at least 3 seconds. The menu descriptions and list of the available
p
alues for each standard menu item is shown on in Table 3. Table 4 lists the
v
vailable values for each manual menu item.
a
igure 5
F
Use DIP Switch SW2 (see Figure 6) to configure other hardware and software
511Ω Pull-up to 5V
511Ω Pull-down to GND
120Ω between A(-) and B(+)
Off
BACnet
Pull-up not connected
Pull-down not connected
Open
Table 1: Dip Switch SW2 Functions
Auto Serial Configuration
Use the auto serial configuration to enable the device to determine the baud rate,
parity, and stop bits directly from the serial traffic. After a valid RS-485 address is
chosen, the GSTC can be quickly and easily deployed. The auto serial
configuration procedure assumes a serial configuration appropriate to the chosen
protocol, shown in Table 2. Otherwise, the serial communication must be
configured manually in the setup menu.
Stop Bits
Protocol
BACnet
Supported Baud Rates
9600
Data Size
Parity
None
1
19200
1
MODBUS
®
38400
57600
76800
8
Even
Odd
None
2
115200
Table 2: Supported Configurations
Text
econdary
S
isplay
D
Text
Primary
Display
Numeric
Figure 7
Standard Menu Descriptions
BAC or MOD: Displays the RS-485 address
CAL:Start user CO or NO2 calibration process
AUT:Auto serial configuration enabled
RST:Reset settings to factory default
Manual Menu Descriptions
BAU:Baud rate selection (only available if AUT = OFF)
PAR:Parity selection (only available if AUT = OFF)
STP:Stop bits selection (only available if AUT = OFF)
Menu Navigation
A menu flowchart, located in Appendix IV, illustrates the navigation process.
1. Press and hold the SPAN pushbutton while in the menu to move to the previous
menu item.
2. Press and hold the ZERO pushbutton while in the menu to move to the next
menu item.
3. Press and hold both the SPAN and ZERO pushbuttons for 5 seconds to activate
the current menu item. In the lower left corner of the display “SET” is shown to
indicate a setting change.
4. Press and hold either the SPAN or ZERO pushbutton to change the setting.
5. Press and hold both the SPAN and ZERO pushbuttons for 5 seconds to accept
the setting.
6. After 30 seconds of inactivity, the display will return to normal operation.
Menu Name
BAC or MOD
CAL
AUT
RST
Value
xxx ADR
xxx PPM
ON
OFF
NO
YES
Description
RS-485 address (view only)
Current CO or NO2 concentration
Auto-baud will start and return to the main menu
Starts the manual serial configuration menu sequence
Will reset settings to factory default
Table 3: Standard Menu Options
Loading...
+ 5 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.