Dwyer Instruments GSTC Series Installation And Operating Instruction Manual

Bulletin AQ-GSTC
3-45/64
[94.06]
3
-1/8
[
107.95]
2
-15/64
[
56.75]
4-17/32
[115.09]
5-7/64
[129.78]
3-59/64
[100]
2-15/64
[57]
2-55/64
[
73]
3
-23/64 [
85]
Series GSTC Carbon Monoxide/Nitrogen Dioxide Gas Transmitter
Specifications - Installation and Operating Instructions
With LCD
he Series GSTC Carbon Monoxide/Nitrogen Dioxide Gas Transmitter
T
Without LCD
monitors the gas concentration in underground parking garages and loading docks. The carbon monoxide transmitter is used to measure the exhaust of gasoline engines, while the nitrogen dioxide transmitter is used for diesel engines. The Series GSTC is compatible with either BACnet or MODBUS
rotocol, allowing the transmitter to be used with almost any building management
ontroller. The GSTC output is communicated over an RS-485 wire via BACnet or
c MODBUS
®
communication protocol. To maximize the accuracy of the Series GSTC, the sensor can be field-calibrated using the A-449 remote LCD display. When the sensor reaches the end of its life, the display will indicate that the sensor needs to be replaced.
BACnet and MODBUS
®
communication protocol recommend limiting the number of nodes in any segment to 32. Therefore, the transceiver may be rated at one unit load. Fractional loads are also acceptable. The Series GSTC accounts as an eighth of a load on the MSTP network.
WARNING
Disconnect power supply before installation to prevent electrical
shock and equipment damage. Make sure all connections are in accordance with the job wiring diagram and in accordance with national and local electrical codes. Use copper conductors only.
NOTICE
Use electrostatic discharge precautions (e.g., use of wrist
straps) during installation and wiring to prevent equipment damage.
NOTICE
Avoid locations where severe shock or vibration, excessive
moisture, or corrosive fumes are present.
NOTICE
Do not exceed ratings of this device, permanent damage not
covered by warranty may result.
NOTICE
The electrochemical sensors should be stored in an
environment with a minimum humidity level of 20% RH. If the sensor dries out, replacements will not be covered under warranty, but they can be revived by allowing them to stabilize in an environment above 40% RH for 10 days. Once revived, they need to be recalibrated before use.
INSTALLATION
NOTICE
These are general guidelines. Local laws or ordinances will take
precedence.
• The transmitter should be mounted at normal breathing height, approximately 5 to 6 ft above the floor.
• The unit may be mounted in the horizontal or vertical position. It should be mounted in an area that is shielded from direct contact with the elements or direct sunlight.
• Mount in an area that will prevent the sensor from having any direct contact with water.
• The unit should be placed in an area that will give an average of the air quality. Do not place the unit so it will receive direct engine exhaust. Prolonged exposure to direct engine exhaust may damage the sensor.
®
communication
Duct MountWall Mount
PECIFICATIONS
S Sensor: Field replaceable
electrochemical, 4 years typical lifespan. Range: CO: 0 to 500 PPM, NO
PM.
P
utput Drift: <5% per year in air.
O Coverage Area: 5000 to 7500 sq ft
typical. Accuracy: CO: 2% FS, NO at the time of calibration. Resolution: CO: 1 PPM; NO PPM. Temperature Limits: -4 to 122°F (-20 to 50°C). Storage Temperature: For best sensor life, 32 to 68°F (0 to 20°C). Humidity Limits: 15 to 90% RH constant; 0 to 99% RH intermittent. Response Time: <45 s to 90% CO, <25 s to 90% NO
2.
Wall Mount Duct MountWall Mount
2: 10
2: 3% FS,
2: 0.1
pan and Zero Adjustment: Via
S
pushbutton, using optional A-449 display. Zero only via BACnet or MODBUS
®
communication protocol.
Housing: UV resistant glass filled
olycarbonate.
utput Signals: BACnet MS/TP or
O
MODBUS
®
RTU (switch selectable)
communication protocol. Power Requirements: 10 to 36 VDC or isolated 21.6 to 33 VAC. Electrical Connection: Removable terminal block, knock outs for conduit fitting. Calibration: Via pushbuttons using A­449 auxiliary display. Span gas concentration is field selectable.
Enclosure Rating: IP64. Weight: 1 lb (0.45 kg). Agency Approvals: CE.
Figure 1 shows the location of the wiring terminal, 8 position DIP Switch SW1, used for configuring the RS-485 address, the 4 position DIP Switch SW2, used for configuring hardware and software options, sensor, span and zero adjustments, and status LEDs.
The device provides three LEDs to indicate status and activity. The LEDs are located to the right of DIP Switch SW1. The yellow LED indicates that the unit is sending a BACnet or MODBUS the unit is receiving a BACnet or MODBUS this specific device. The red LED will flash once periodically if the BACnet or MODBUS
®
communication protocol address is set incorrectly or the red LED will
®
communication protocol. The green LED indicates
®
communication protocol addressed to
flash twice periodically if the auto serial configuration is in progress.
Span
Sensor
DIP Switch
DIP Switch
SW2
Wiring
Terminal
Figure 1
Zero
SW1
Status
LEDs
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A. Fax: 219/872-9057 e-mail: info@dwyermail.com
Phone: 219/879-8000 www.dwyer-inst.com
TO NEXT
D
EVICE
B(+) A(-)
WR
COM
TO PREVIOUS
D
EVICE
B(+) A
(-)
WR
COM
ATTACH SHIELDS T
OGETHER W/WIRE NUT
WRCOM A(-) B(+)
1234
B(+) A(-)
B(+) A(-)
COM
-+
COM
TO PREVIOUS
DEVICE
TO NEXT
DEVICE
ATTACH SHIELDS TOGETHER W/WIRE NUT
PWRCOM A(-) B(+)
1234
all Mounting
W
. Remove the cover plugs from the face of the unit and the top cover.
. Disconnect the display cable from the USB connector on the main circuit board
if present).
(
3. Remove the desired conduit fitting knock out and install conduit fitting (not provided).
4. Position the transmitter where it is to be mounted and mark the mounting holes n each corner of the housing.
i
. Drill or punch out marked locations.
. Place the transmitter box over mounting holes on wall and align. Install wall
ount screws (not provided) in mounting holes.
m
7. Proceed with wiring diagrams according to Figures 3 and 4.
8. Set DIP Switches SW1 and SW2 as desired. Refer to Figure 5, Figure 6, and
Appendix I.
. Reconnect the LCD cable to the USB port on the main circuit board (if present).
0. Replace cover and cover plugs on the face of the unit.
CO: Locate GSTC carbon monoxide transmitter about 5 ft (1.5 m) off the floor. Carbon monoxide weighs about the same as air and distributes evenly throughout the monitored space. Install GSTC CO alarm at least 15 to 20 ft (4.6 to 6.1 m) away
rom boiler or fuel burning heat source. Avoid extremely dusty, dirty, humid or
f
reasy areas. Do not place in direct sunlight or areas subjected to extreme
emperature. Do not place in turbulent air, near fans, heat vents, air conditioners,
t air returns or open windows. Blowing air may prevent CO from reaching the CO sensor.
NO
:
2
O
ensors should be mounted in the breathing zone, 4 to 6 ft (1.2 to 1.8 m) from
N
s
2
he floor. This is primarily because NO
t
etected in the area where people would be exposed to it, but also because 4 to 6
s a poisonous gas which should be
i
2
gas.
2
Duct Mounting
Duct mounting kit includes an air flow pitot tube, air filter with barbed connections, two short pieces of tubing, and one long piece of tubing.
igure 3 shows how to connect the GSTC in a network containing a common
F
ower supply. Use a cable containing two twisted pairs. One pair is to be used for
he power and common. The other pair is to be used for A(-) and B(+). Attach the
t
hields together with a wire nut. This configuration is not suitable for AC supplies.
s Use a DC supply only. Care should be taken that there are not too many devices powered from the same supply as voltage drops will occur in the wiring. If you have many devices, or have long cable runs, the local supply configuration, shown in
igure 4, may be a better choice.
F
igure 3 - Common Power Supply
F
igure 4 shows how to connect the GSTC in a network containing individual local
F
upplies. Use a cable containing a single conductor and a twisted pair. The single
s conductor is to be used for common, and the pair is to be used for A(-) and B(+). Attach the shields together with a wire nut. Both AC and DC supplies are suitable for this configuration.
1. Mount the pitot tube into the duct observing the flow direction marked on the pitot
tube.
2. Attach the two short pieces of tubing to the barbed connections on each side of
the air filter. See Figure 2.
3. Attach the remaining side of one of the short pieces of tubing to the barbed
connection on the transmitter.
4. Attach the remaining side of the other short piece of tubing to the high port on
the pitot tube.
5. Attach the long piece of tubing to the open barbed connection on the transmitter.
6. Attach the other end of the long tubing to the low port on the pitot tube.
Figure 2
WIRING
NOTICE
Wiring should comply with Electrical Characteristics of Generators and Receivers for Use in Balanced Digital Multipoint
Systems, TIA-EIA-485-A-1998, Telecommunications Industry Association, 1998.
NOTICE
Building Automation and Control Networks, American Society of Heating,
BACnet installations should comply with ANSI/ASHRAE Standard 135-2010 BACnet A Data Communication Protocol for
Refrigerating and Air-Conditioning Engineers, Inc., 2010.
NOTICE
Specification and Implementation Guide V1.02, MODBUS
NOTICE
NOTICE
MODBUS®communication protocol installations should comply with MODBUS
®
communication protocol over Serial Line
Communication wiring must be in a daisy-chain fashion. Star connections are not permitted.
Cable shield must be connected to earth ground at one location only.
®
Organization, Inc., 2006.
Figure 4 - Local Power Supply
All devices in the network should be daisy-chained. Star connections and T connections are not permitted.
The A(-) and B(+) lines must be terminated at both ends with a 120 ohm resistor. If the GSTC is an end device it has an on-board resistor that may be used. See Table 1 to enable it.
The network must be biased properly. If needed, there are bias resistors on-board the GSTC. No more than two sets of bias resistors should be enabled in the network. See Table 1 to enable them.
ip Switch Configurations
D
se DIP Switch SW1 (see Figure 5) to configure the RS-485 address of the device.
U
valid address depends on the protocol selected. Valid BACnet addresses range
A
rom 1 to 127. Valid MODBUS
f
247. By default, the device is shipped with MODBUS
®
ommunication protocol addresses range from 1 to
c
®
communication protocol selected and the address set to 127, as shown in Figure 5. A valid and unused address should be set before connecting to an existing network. See Appendix I to
onfigure the required address using DIP Switch SW1. The device will not function
c
roperly if an invalid address is set. During the power up sequence, the LCD (if
resent) will display the RS-485 address as the primary value and either “BAC” to
ndicate BACnet or “MOD” to indicate MODBUS
i
®
ommunication protocol as the
c primary text. If the RS-485 address is invalid, the invalid address is shown as the primary value with “ERR” as the primary text, and the red LED will periodically blink once.
o activate auto serial configuration, set a valid RS-485 address using DIP Switch
T
W1, connect the serial bus, common and power wires, and apply power. The
S
evice will power up and begin examining the serial bus for communication.
When the device is installed offline or away from the main network, it is necessary to generate the appropriate traffic in order to configure the serial communication whether BACnet or MODBUS
onfiguration is in progress, the device may not respond. The device may require
c
ultiple read requests to complete the serial configuration process.
m
he auto serial configuration process is completed once a message addressed to
T
®
communication protocol is selected. While the serial
the device is received and processed successfully. If the serial configuration of the bus changes, a power cycle of the device is required to restart the auto serial configuration process.
ore detailed information for BACnet protocol can be found in Appendix II, and
M
nformation for MODBUS
i
®
ommunication protocol can be found in Appendix III.
c
MENU
The menu is only shown if a display is present. Figure 7 below outlines the display components. To enter the menu, press and hold both the SPAN and ZERO
ushbuttons for at least 3 seconds. The menu descriptions and list of the available
alues for each standard menu item is shown on in Table 3. Table 4 lists the
v
vailable values for each manual menu item.
igure 5
F
Use DIP Switch SW2 (see Figure 6) to configure other hardware and software
ptions. Table 1 shows available options. Table 2 shows supported configurations
or either BACnet or MODBUS
f
®
ommunication protocol.
c
Figure 6
Switch
1 - Protocol 2 - B(+) Bias Resister 3 - A(-) Bias Resister 4 - Terminating Resister
On
MODBUS
®
511Ω Pull-up to 5V 511Ω Pull-down to GND 120Ω between A(-) and B(+)
Off
BACnet Pull-up not connected Pull-down not connected Open
Table 1: Dip Switch SW2 Functions
Auto Serial Configuration
Use the auto serial configuration to enable the device to determine the baud rate, parity, and stop bits directly from the serial traffic. After a valid RS-485 address is chosen, the GSTC can be quickly and easily deployed. The auto serial configuration procedure assumes a serial configuration appropriate to the chosen protocol, shown in Table 2. Otherwise, the serial communication must be configured manually in the setup menu.
Stop Bits
Protocol
BACnet
Supported Baud Rates
9600
Data Size
Parity
None
19200
MODBUS
®
38400 57600 76800
Even Odd None
115200
Table 2: Supported Configurations
Text
econdary
S
isplay
D
Text
Primary
Display
Numeric
Figure 7
Standard Menu Descriptions
BAC or MOD: Displays the RS-485 address CAL: Start user CO or NO2 calibration process AUT: Auto serial configuration enabled RST: Reset settings to factory default
Manual Menu Descriptions
BAU: Baud rate selection (only available if AUT = OFF) PAR: Parity selection (only available if AUT = OFF) STP: Stop bits selection (only available if AUT = OFF)
Menu Navigation
A menu flowchart, located in Appendix IV, illustrates the navigation process.
1. Press and hold the SPAN pushbutton while in the menu to move to the previous menu item.
2. Press and hold the ZERO pushbutton while in the menu to move to the next menu item.
3. Press and hold both the SPAN and ZERO pushbuttons for 5 seconds to activate the current menu item. In the lower left corner of the display “SET” is shown to indicate a setting change.
4. Press and hold either the SPAN or ZERO pushbutton to change the setting.
5. Press and hold both the SPAN and ZERO pushbuttons for 5 seconds to accept the setting.
6. After 30 seconds of inactivity, the display will return to normal operation.
Menu Name
BAC or MOD CAL AUT
RST
Value
xxx ADR xxx PPM ON OFF NO YES
Description
RS-485 address (view only) Current CO or NO2 concentration Auto-baud will start and return to the main menu Starts the manual serial configuration menu sequence
Will reset settings to factory default
Table 3: Standard Menu Options
Loading...
+ 5 hidden pages