Dwyer Instruments GSTA, GSTC Operating Manual

Bulletin AQ-GSTC
3-23/64
®
Series GSTC Carbon Monoxide/Nitrogen Dioxide Gas Transmitter
Specications - Installation and Operating Instructions
Wall mount
with LCD
The Series GSTC Carbon Monoxide/Nitrogen Dioxide Gas Transmitter monitors the gas concentration in underground parking garages and loading docks. The carbon monoxide transmitter is used to measure the exhaust of gasoline engines, while the nitrogen dioxide transmitter is used for diesel engines. The Series GSTC is compatible with either BACnet or Modbus to be used with almost any building management controller. The GSTC output is communicated over an RS-485 wire via BACnet or Modbus
To maximize the accuracy of the Series GSTC, the sensor can be eld-calibrated using
the A-449 remote LCD display. When the sensor reaches the end of its life, the display will indicate that the sensor needs to be replaced.
BACnet and Modbus nodes in any segment to 32. Therefore, the transceiver may be rated at one unit load. Fractional loads are also acceptable. The Series GSTC accounts as an eighth of a load on the MSTP network.
WARNING
accordance with the job wiring diagram and in accordance with national and local electrical codes. Use copper conductors only.
NOTICE
NOTICE
NOTICE
NOTICE
replacements will not be covered under warranty, but they can be revived by allowing them to stabilize in an environment above 40% RH for 10 days. Once revived, they need to be recalibrated before use.
INSTALLATION
NOTICE
• The transmitter should be mounted at normal breathing height, approximately 5 to 6
ft above the oor.
• The unit may be mounted in the horizontal or vertical position. It should be mounted in an area that is shielded from direct contact with the elements or direct sunlight.
• Mount in an area that will prevent the sensor from having any direct contact with water.
• The unit should be placed in an area that will give an average of the air quality. Do not place the unit so it will receive direct engine exhaust. Prolonged exposure to direct engine exhaust may damage the sensor.
communication protocol recommend limiting the number of
Disconnect power supply before installation to prevent electrical shock and equipment damage. Make sure all connections are in
Use electrostatic discharge precautions (e.g., use of wrist straps) during installation and wiring to prevent equipment damage.
Avoid locations where severe shock or vibration, excessive moisture, or corrosive fumes are present.
Do not exceed ratings of this device, permanent damage not covered by warranty may result.
The electrochemical sensors should be stored in an environment with a minimum humidity level of 20% RH. If the sensor dries out,
These are general guidelines. Local laws or ordinances will take precedence.
Wall mount
without LCD
communication protocol, allowing the transmitter
communication protocol.
Duct mount
3-45/64
[94.06]
3-1/8
[107.95]
4-17/32 [115.09]
5-7/64
[129.78]
SPECIFICATIONS
Sensor: Field replaceable electrochemical, 4 years typical lifespan. Range: CO: 0 to 500 PPM, NO2: 10 PPM.
Output Drift: <5% per year in air. Coverage Area: 5000 to 7500 sq ft typical. Accuracy: CO: 2% FS, NO2: 3% FS, at the time of calibration. Resolution: CO: 1 PPM; NO2: 0.1 PPM. Temperature Limits: -4 to 122°F (-20 to 50°C). Storage Temperature: For best sensor life, 32 to 68°F (0 to 20°C). Humidity Limits: 15 to 90% RH constant; 0 to 99% RH intermittent.
Response Time: <45 s to 90% CO, <25 s to 90% NO2.
Span and Zero Adjustment: Via pushbutton, using optional A-449 display. Zero only via BACnet or Modbus
Housing: UV resistant glass lled polycarbonate. Output Signals: BACnet MS/TP or Modbus
communication protocol.
Power Requirements: 10 to 36 VDC or isolated 21.6 to 33 VAC. Electrical Connection: Removable terminal block, knock outs for conduit tting. Calibration: Via pushbuttons using A-449 auxiliary display. Span gas concentration is eld selectable. Enclosure Rating: IP64.
Weight: 1 lb (0.45 kg).
Agency Approvals: CE.
Figure 1 shows the location of the wiring terminal, 8 position DIP Switch SW1, used for
conguring the RS-485 address, the 4 position DIP Switch SW2, used for conguring
hardware and software options, sensor, span and zero adjustments, and status LEDs.
The device provides three LEDs to indicate status and activity. The LEDs are located to the right of DIP Switch SW1. The yellow LED indicates that the unit is sending a BACnet or Modbus BACnet or Modbus
red LED will ash once periodically if the BACnet or Modbus address is set incorrectly or the red LED will ash twice periodically if the auto serial conguration is in progress.
communication protocol. The green LED indicates the unit is receiving a
Span
Sensor
DIP Switch
SW2
Wiring
Terminal
communication protocol.
communication protocol addressed to this specic device. The
2-15/64
[56.75]
Duct mountWall mount
RTU (switch selectable)
[85]
2-55/64
[73]
2-15/64
[57]
3-59/64
[100]
communication protocol
Zero
DIP Switch
SW1
Status
LEDs
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Modbus® is a registered trademark of Schneider Automation, Inc.
Phone: 219/879-8000
Fax: 219/872-9057
Figure 1
www.dwyer-inst.com
e-mail: info@dwyermail.com
Wall Mounting
TO
PWRCOM A(-)B(+)
TO
NEXT
PWRCOM A(-) B(+)
1. Remove the cover plugs from the face of the unit and the top cover.
2. Disconnect the display cable from the USB connector on the main circuit board (if present).
3. Remove the desired conduit tting knock out and install conduit tting (not
provided).
4. Position the transmitter where it is to be mounted and mark the mounting holes in each corner of the housing.
5. Drill or punch out marked locations.
6. Place the transmitter box over mounting holes on wall and align. Install wall mount screws (not provided) in mounting holes.
7. Proceed with wiring diagrams according to Figures 3 and 4.
8. Set DIP Switches SW1 and SW2 as desired. Refer to Figure 5, Figure 6, and Appendix I.
9. Reconnect the LCD cable to the USB port on the main circuit board (if present).
10. Replace cover and cover plugs on the face of the unit.
CO:
Locate GSTC carbon monoxide transmitter about 5 ft (1.5 m) off the oor. Carbon
monoxide weighs about the same as air and distributes evenly throughout the monitored space. Install GSTC CO alarm at least 15 to 20 ft (4.6 to 6.1 m) away from boiler or fuel burning heat source. Avoid extremely dusty, dirty, humid or greasy areas. Do not place in direct sunlight or areas subjected to extreme temperature. Do not place in turbulent air, near fans, heat vents, air conditioners, air returns or open windows. Blowing air may prevent CO from reaching the CO sensor.
2:
NO
2 sensors should be mounted in the breathing zone, 4 to 6 ft (1.2 to 1.8 m) from the
NO
oor. This is primarily because NO
2 is a poisonous gas which should be detected in
the area where people would be exposed to it, but also because 4 to 6 ft from the oor
is an appropriate elevation to detect NO
2 gas.
Duct Mounting
Duct mounting kit includes an air ow pitot tube, air lter with barbed connections, two
short pieces of tubing, and one long piece of tubing.
1. Mount the pitot tube into the duct observing the ow direction marked on the pitot
tube.
2. Attach the two short pieces of tubing to the barbed connections on each side of the
air lter. See Figure 2.
3. Attach the remaining side of one of the short pieces of tubing to the barbed connection on the transmitter.
4. Attach the remaining side of the other short piece of tubing to the high port on the pitot tube.
5. Attach the long piece of tubing to the open barbed connection on the transmitter.
6. Attach the other end of the long tubing to the low port on the pitot tube.
Figure 3 shows how to connect the GSTC in a network containing a common power supply. Use a cable containing two twisted pairs. One pair is to be used for the power and common. The other pair is to be used for A(-) and B(+). Attach the shields together
with a wire nut. This conguration is not suitable for AC supplies. Use a DC supply
only. Care should be taken that there are not too many devices powered from the same supply as voltage drops will occur in the wiring. If you have many devices, or
have long cable runs, the local supply conguration, shown in Figure 4, may be a
better choice.
1234
PREVIOUS
DEVICE
B(+) A(-) PWR
COM
ATTA CH SHIELDS TOGETHER W/WIRE NUT
TO NEXT
DEVICE
B(+) A(-) PWR
COM
Figure 3 - Common Power Supply
Figure 4 shows how to connect the GSTC in a network containing individual local supplies. Use a cable containing a single conductor and a twisted pair. The single conductor is to be used for common, and the pair is to be used for A(-) and B(+). Attach the shields together with a wire nut. Both AC and DC supplies are suitable for
this conguration.
1234
PREVIOUS
DEVICE
B(+) A(-)
COM
TO
DEVICE
B(+) A(-) COM
-+
ATTA CH SHIELDS TOGETHER W/WIRE NUT
Figure 4 - Local Power Supply
All devices in the network should be daisy-chained. Star connections and T connections are not permitted.
The A(-) and B(+) lines must be terminated at both ends with a 120 ohm resistor. If the GSTC is an end device it has an on-board resistor that may be used. See Table 1 to enable it.
The network must be biased properly. If needed, there are bias resistors on-board the GSTC. No more than two sets of bias resistors should be enabled in the network. See Table 1 to enable them.
WIRING
NOTICE
Figure 2
Wiring should comply with Electrical Characteristics of Generators and Receivers for Use in Balanced Digital Multipoint Systems,
TIA-EIA-485-A-1998, Telecommunications Industry Association, 1998.
NOTICE
BACnet installations should comply with ANSI/ASHRAE Standard
135-2010 BACnet A Data Communication Protocol for Building Automation and Control Networks, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., 2010.
communication protocol installations should comply with
NOTICE
and Implementation Guide V1.02, Modbus
NOTICE
Modbus
communication protocol over Serial Line Specication
Modbus
Organization, Inc., 2006.
Communication wiring must be in a daisy-chain fashion. Star
connections are not permitted.
NOTICE
Cable shield must be connected to earth ground at one location
only.
Dip Switch Congurations
NETWORK BIAS
PROTOCOL NETWORK TERMINATION
Use DIP Switch SW1 (see Figure 5) to congure the RS-485 address of the device. A
valid address depends on the protocol selected. Valid BACnet addresses range from 1 to 127. Valid Modbus default, the device is shipped with Modbus
communication protocol addresses range from 1 to 247. By
communication protocol selected and the
address set to 127, as shown in Figure 5. A valid and unused address should be set
before connecting to an existing network. See Appendix I to congure the required
address using DIP Switch SW1. The device will not function properly if an invalid address is set. During the power up sequence, the LCD (if present) will display the RS-485 address as the primary value and either “BAC” to indicate BACnet or “MOD” to indicate Modbus
communication protocol as the primary text. If the RS-485 address is invalid, the invalid address is shown as the primary value with “ERR” as the primary text, and the red LED will periodically blink once.
ON
1 2 3 4 5 6 7 8
Figure 5
To activate auto serial conguration, set a valid RS-485 address using DIP Switch
SW1, connect the serial bus, common and power wires, and apply power. The device will power up and begin examining the serial bus for communication.
When the device is installed ofine or away from the main network, it is necessary to generate the appropriate trafc in order to congure the serial communication whether
BACnet or Modbus
communication protocol is selected. While the serial conguration
is in progress, the device may not respond. The device may require multiple read
requests to complete the serial conguration process.
The auto serial conguration process is completed once a message addressed to the device is received and processed successfully. If the serial conguration of the bus changes, a power cycle of the device is required to restart the auto serial conguration
process.
More detailed information for BACnet protocol can be found in Appendix II, and information for Modbus
communication protocol can be found in Appendix III.
MENU
The menu is only shown if a display is present. Figure 7 below outlines the display components. To enter the menu, press and hold both the SPAN and ZERO pushbuttons for at least 3 seconds. The menu descriptions and list of the available values for each standard menu item is shown on in Table 3. Table 4 lists the available values for each manual menu item.
Use DIP Switch SW2 (see Figure 6) to congure other hardware and software options. Table 1 shows available options. Table 2 shows supported congurations for either
BACnet or Modbus
communication protocol.
ON
1 2 3 4
Figure 6
DIP SWITCH SW2 FUNCTIONS Switch On Off
1 - Protocol 2 - B(+) Bias Resister 3 - A(-) Bias Resister 4 - Terminating Resister
Modbus
511Ω Pull-up to 5V 511Ω Pull-down to GND 120Ω between A(-) and B(+)
BACnet Pull-up not connected Pull-down not connected Open
Table 1
Auto Serial Conguration
Use the auto serial conguration to enable the device to determine the baud rate, parity, and stop bits directly from the serial trafc. After a valid RS-485 address is chosen, the GSTC can be quickly and easily deployed. The auto serial conguration procedure assumes a serial conguration appropriate to the chosen protocol, shown in Table 2. Otherwise, the serial communication must be congured manually in the
setup menu.
SUPPORTED CONFIGURATIONS Protocol Supported Baud Rates Data Size Parity Stop Bits
BACnet 9600
19200
Modbus
38400 57600 76800
8
None 1
Even Odd None 2
1
115200
Table 2
Text
Secondary
Display
Text
Primary
Display
Numeric
Figure 7
Standard Menu Descriptions
BAC or MOD: Displays the RS-485 address CAL: Start user CO or NO2 calibration process
AUT: Auto serial conguration enabled
RST: Reset settings to factory default
Manual Menu Descriptions
BAU: Baud rate selection (only available if AUT = OFF) PAR: Parity selection (only available if AUT = OFF) STP: Stop bits selection (only available if AUT = OFF)
Menu Navigation
A menu owchart, located in Appendix IV, illustrates the navigation process.
1. Press and hold the SPAN pushbutton while in the menu to move to the previous menu item.
2. Press and hold the ZERO pushbutton while in the menu to move to the next menu item.
3. Press and hold both the SPAN and ZERO pushbuttons for 5 seconds to activate the current menu item. In the lower left corner of the display “SET” is shown to indicate a setting change.
4. Press and hold either the SPAN or ZERO pushbutton to change the setting.
5. Press and hold both the SPAN and ZERO pushbuttons for 5 seconds to accept the setting.
6. After 30 seconds of inactivity, the display will return to normal operation.
STANDARD MENU OPTIONS Menu Name Value Description
BAC or MOD xxx ADR RS-485 address (view only) CAL xxx PPM Current CO or NO2 concentration AUT ON Auto-baud will start and return to the main menu
OFF Starts the manual serial conguration menu sequence
RST NO
YES Will reset settings to factory default
Table 3
MANUAL MENU OPTIONS Menu Name Value Description
9600 19200
BAU
38400 57600
Only available if AUT = OFF
76800 115200 EVE
PAR
ODD
Only available if AUT = OFF
NON
STP
1 2
Only available if AUT = OFF
Table 4
SENSOR REPLACEMENT
A replacement sensor is available from Dwyer Instruments, Inc. For CO, order part number: A-505.
2, order part number: A-506.
For NO
The address of the transmitter in Figure 9 is 127. This nal value is determined by
adding the individual values of the DIP switches together. The values for each DIP switch are shown below in Table 5. When adding the individual values for Figure 9, 0+64+32+16+8+4+2+1=127, which is the correct factory setting.
DIP SWITCH VALUES
Switch Positions
Address Value112826433241658647281
Table 5
Another example would be if the desired address was 53. The only DIP switches in the “ON” position would be switches 3, 4, 6, and 8 as shown in Figure 10 below. By adding the individual values of each switch in the “ON” position, 0+0+32+16+0+4+0+1=53, the desired address is obtained.
ON
WARNING
Sensors contain acid and are harmful if handled improperly. Do not attempt to open sensors. Sensors should be disposed of
according to local laws.
Replacing The Sensor
1. Remove the cover plugs from the face of the unit and top cover. Locate the sensor, see Figure 1. The sensor is mounted on three pin sockets. The circuit board is either labeled “CO SENSOR” or “NO
2 SENSOR” underneath the sensor.
2. Remove and discard the used sensor.
3. Remove the shorting wire spring located at the bottom of the new sensor.
4. Install the new sensor into the three pin sockets.
5. The unit must be re-calibrated whenever a new sensor is installed.
6. Allow 30 minutes for the unit to come to temperature equilibrium prior to calibration. The unit has internal temperature compensation, and the sensor must be at the same temperature as the unit to calibrate properly.
CALIBRATION
Figure 8, located after Appendix III, shows how to set up a GSTC for calibration with an auxiliary display. An auxiliary display is required for calibration unless an LCD model of the GSTC was purchased. The procedure in Appendix IV shows how to set the range, and calibrate the span and zero adjustments.
MAINTENANCE/REPAIR
Upon nal installation of the Series GSTC, no routine maintenance is required with
the exception of sensor replacement and calibration. As with all electrochemical type gas sensors, routine calibration is required. It is recommended that units be re­calibrated at 6 month intervals, to maintain the published accuracy, or as required by local ordinances or other requirements. The units will maintain 5% accuracy if they are re-calibrated at 12 month intervals.
Except for the sensor replacement and calibration, the Series GSTC is not eld
serviceable and should be returned if repair is needed. Field repair should not be attempted and may void warranty.
This symbol indicates waste electrical products should not be disposed of with household waste. Please recycle where facilities exist. Check with your Local Authority or retailer for recycling advice.
1 2 3 4 5 6 7 8
Figure 10
NOTICE
The minimum possible address would be 0 when all DIP switches
are in the “OFF” position, and the maximum possible address would be 255 when all DIP switches are in the “ON” position. When BACnet protocol is selected the transmitter only has valid address from 1 to 127. When Modbus communication protocol is selected the transmitter only has valid address from 1 to
247. Any address outside the selected protocol’s range will give an error.
Appendix II: BACnet Protocol
The GSTC supports objects that are listed below. Table 6 and Table 7 outlines each item.
SUPPORTED BACNET OBJECTS
Object Type
Device Analog Input
Dynamically Creatable
No No
Dynamically Deletable
No No
Object Identier Object Name
607xxx AI1
GSTC CO Concentration
NO2 Concentration Binary Value Date Value
No No
No No
BV1 DV1 DV2
Zero Sensor
Calibration Date
Replace Sensor Date
Table 6
®
WARRANTY/RETURN
Refer to “Terms and Conditions of Sales” in our catalog and on our website. Contact customer service to receive a Return Goods Authorization number before shipping the product back for repair. Be sure to include a brief description of the problem plus any additional application notes.
Appendix I: Setting the RS-485 Address
The address assignment is determined by adding the values for each of the switches that are in the “ON” position. The transmitter comes from the factory with all of the DIP switches in the “ON” position, except position 1 as shown in Figure 9 below.
ON
1 2 3 4 5 6 7 8
Figure 9
OBJECT PROPERTIES
Property Default Value Property Data Type Access
Object Identier
Object Name
Object Type
System Status
Vendor Name
607xxx
“GSTC 607xxx”
DEVICE (8)
Operational (0)
“Dwyer
BACnetObjectIdentier
CharacterString (32)
BACnetObjectType
BACnetDeviceStatus
CharacterString
Read/Write
Read/Write
Read
Read
Read
Instruments, Inc”
Vendor Identier
Model Name
607 “GSTC-C” or
Unsigned CharacterString
Read Read
“GSTC-N” Firmware Revision Application Software
“?.?”
“?.?”
CharacterString CharacterString
Read
Read Version Location
Description
Protocol Version Protocol Revision Protocol Services
“”
“CO Detector” or
2 Detector”
“NO 1 12 See pics
CharacterString (32)
CharacterString (32)
Unsigned Unsigned BACnetServicesSupported
Read/Write
Read/Write
Read
Read
Read Supported Protocol Object Types Supported Object List Maximum APDU
See Table 2
See Table 2 128
BACnetObjectTypesSup­ported BACnetArray Unsigned
Read
Read
Read Length Accepted Segmentation Supported APDU Timeout Number of APDU
NO_SEGMENTA­TION (3) 0 0
BACnetSegmentation
Unsigned Unsigned
Read
Read
Read Retries Max Master Max Info Frames Devices Address
127 1 Empty
Unsigned Unsigned BACnetAddressBinding
Read/Write
Read
Read Binding Database Revision Serial Number (1000)
1 “xxxxxx”
Unsigned CharacterString
Read
Read
Table 7
The default object identier is 607xxx, where xxx is replaced by the address set by the DIP Switch SW1. The object identier value will change as the address changes. When a specic object identier is written via BACnet, that value is stored and changes to the address will no longer affect the object identier. The object name reects the current object identier. When a specic object name is written via BACnet, that value is stored and changes to the object identier will no longer affect the object name.
Table 9 outlines the Binary Value (BV1) object which allows the sensor to be remotely zeroed. When set to “ACTIVE”, the zero function will attempt to recalibrate the zero point of the sensor.
BINARY VALUE
Property Default Value Property Data Type Access
Object Identier
Object Name Object Type Present Value Status Flags Event State Reliability Out of Service
BV1 “Zero Sensor” BINARY VALUE (5)
0 0 NORMAL (0) NO FAULT DETECTED (0) FALSE (0)
BACnetObjectIdentier
CharacterString BACnetObjectType Real BACnetStatusFlags BACnetEventState BACnetReliability Boolean
Read Read Read Read Read Read Read Read/Write Read
Table 9
Table 10 outlines the Date Value (DV1) object which stores the date when the sensor was last calibrated. Since the GSTC does not track time this value must be updated
manually after calibration is performed in the eld.
DATE VALUE
Property Default Value Property Data Type Access
Object Identier
Object Name Object Type Present Value Status Flags Event State Reliability Out of Service
DV1 “Calibration Date” DATE VALUE (42) ???? {F,F,F,F} NORMAL (0) NO FAULT DETECTED (0) FALSE (0)
BACnetObjectIdentier
CharacterString BACnetObjectType BACnetBinaryPV BACnetStatusFlags BACnetEventState BACnetReliability Boolean
Read Read Read Read/Write Read Read Read Read/Write
Table 10
Table 11 outlines the Replace Sensor Date (DV2) object which stores the suggested
sensor replacement date. It is recommended to replace the sensor at specic intervals
because the sensor degrades over time. The GSTC does not track time so this value
must be updated manually after the sensor is replaced in the eld.
REPLACE SENSOR DATE
Property Default Value Property Data Type Access
Object Identier
Object Name Object Type Present Value Status Flags Event State Reliability Out of Service
DV2 “Replace Sensor Date” DATE VALUE (42) ???? {F,F,F,F} NORMAL (0) NO FAULT DETECTED (0) FALSE (0)
BACnetObjectIdentier
CharacterString BACnetObjectType BACnetBinaryPV BACnetStatusFlags BACnetEventState BACnetReliability Boolean
Read Read Read Read/Write Read Read Read Read/Write
Table 11
Table 8 outlines the Analog Input (AI1) object which represents the current CO or NO concentration reading in parts per million.
ANALOG INPUT
Property Default Value Property Data Type Access
Object Identier
Object Name
AI1 “CO Concentration” or
BACnetObjectIdentier
CharacterString
Read Read
“NO2 Concentration” Object Type Present Value Status Flags Event State Reliability Out of Service Units
ANALOG_INPUT (0)
Current reading
0
NORMAL (0)
NO_FAULT_DETECED(0)
FALSE (0)
Parts-per-million (96)
BACnetObjectType Real BACnetStatusFlags BACnetEventState BACnetReliability Boolean BACnetEngineeringUnits
Read Read Read Read Read Read/Write Read
Table 8
2
BACnet Services
The GSTC supports the Device Communication Control Service BIBB. The option time
duration in minutes is also supported. This device is congured with a password that
must be provided to successfully execute the command. The password is “Dwyer”.
The GSTC also supports the Reinitialize Device Service BIBB. The supported device states are “COLDSTART” and “WARMSTART”. All other states return an error. This
device is congured with a password that must be provided to successfully execute
the command. The password is “Dwyer”.
Appendix III: Modbus
Communication Protocol
The GSTC supports functions and input registers that are listed below. Table 12, Table 13, and Table 14 outline each item.
SUPPORTED MODBUS® FUNCTIONS
Function Name Function Code
Read Holding Registers Read Input Registers Write Single Register Write Multiple Registers
03 04 06 16
Table 12
The string data type is read as a stream of ASCII characters with the rst character sent in the MSB of the rst register and the second character sent in the LSB of the rst register and so on. If the string is shorter than the allotted size, the remaining bytes
will be zero padded.
INPUT REGISTERS
Register Description Data Type Range
0001
CO or NO2 Concentration in PPM
Unsigned 16 bit integer
0 – 500 PPM CO, 0 – 100 (0 – 10.0) PPM NO2
1000-1009
Model Number String
String
“GSTC-C” or
“GSTC-N” 1010-1013 1014-1017
Serial Number String Firmware Version String
String String
“xxxxxx”
“?.?”
Table 13
Figure 8
HOLDING REGISTERS
Register Description Data Type Value Range
0001 0500
Zero Sensor Reboot device
Unsigned 16bit integer Unsigned 16bit integer
0-1 0-1
0 or 1 0 - Do Nothing 1 - Warm Reset
Table 14
Writing 1 to the Zero Sensor register will re-zero the sensor just as if the user has pressed the zero pushbutton.
®
The Reboot Device register allows a Modbus
communication protocol master to remotely request this device to perform a warm reset. When a value of 1 is written to this register the device will respond with success. The reset will take approximately 5 seconds after the command was received. Writing a value of 0 to this register has no effect.
Appendix IV: Menu Flowchart and Calibration
NOTE - WHEN IN THE MENU, THE
MODBUS/BACNET VIEW
DISPLAY WILL RETURN TO THE HOME POSITION IF NO KEY IS PRESSED WITHIN 30 SECONDS.
HOME POSITION, UNIT READS GAS CONCENTRATION PPM
CO
PPM
SPAN
ZERO
DIGIT
VALUE
PRESS AND HOLD ZERO AND SPAN KEYS FOR 5 SECODNS TO ENTER THE MAIN MENU.
ADDRESS.
ABLE ONLY.
SPAN DIGIT
CALIBRATION MODE
COMMUNICATION SETTINGS FACTORY SETTING IS AUTO BAUD ON.
SCROLL TO TOP MENU, MODBUS/BACNET ADDRESS
RESET UNIT TO FACTORY DEFAULTS
ZERO
VALUE
SPAN DIGIT
SCROLL
SCROLL
SPAN DIGIT
SCROLL
ADR
SCROLL
PPM
SCROLL
MOD
ZERO
PRESS ZERO AND SPAN TO ENTER CALIBRATION MODE
VALUE
CO
ZERO
VALUE
SPAN DIGIT
PLACE THE UNIT IN AN AREA THAT CONTAINS FRESH AIR (NO CO OR NO2 GAS). ALLOW 3 MINUTES TO STABILIZE.
ZERO VALUE
PRESS AND HOLD ZERO AND SPAN UNTIL “SET” TURNS ON
AUT
ZERO
VALUE
SPAN DIGIT
SCROLL
ZERO
SPAN DIGIT
VALUE
SET BAUDRAT E
RST
SPAN DIGIT
SPAN DIGIT
SETPARITY
SETSTOPBITS
SCROLL
PRESS AND HOLD ZERO AND SPAN UNTIL “SET” TURNS ON
ZERO
VALUE
SPAN DIGIT
SPAN DIGIT
SCROLL
SCROLL
SCROLL
PRESS THE ZERO KEY FOR 5 SECONDS. THE ZERO VALUE IS STORED AND THE DISPLAY SEQUENCES TO THE SPAN GAS CALIBRATION VALUE
CAL
ZERO
VALUE
TO ADJUST THE DISPLAY TO SET THE DESIRED SPAN CALIBRATION VALUE,
PRESS THE DIGIT KEY TO SCROLL
SPAN
THROUGH THE DIGITS. THE DIGITS WILL
DIGIT
BLINK AS THEY ARE SELECTED.
ADJUST THE VALUE OF THE DIGIT
ZERO
USING THE VALUE KEY
VALUE
HOOK UP THE UNIT TO THE SPAN CALIBRATION GAS USING THE CALIBRATION ADAPTER A-507AS SHOW IN FIG. 8 SPAN GAS FLOW IS TO BE BETWEEN 0.5 TO 10. SLPM. ALLOW GAS TO FLOW FOR AT LEAST 3 MINUTES.
PRESS ZERO OR SPAN TO SWITCH BETWEEN AUTO BAUD ON OR OFF
ZERO
AUT
VALUE
SPAN DIGIT
AUTOBAUD MUST BE SET TO “NO” TO SET BAUDRATE, PARITY AND STOP BIT SETTINGS
SCROLL
ZERO
VALUE
BAU
K
SCROLL
ZERO
VALUE
PAR
SCROLL
ZERO
VALUE
STPSTP
ZERO
VALUE
RST
PRESS AND HOLD ZERO AND SPAN UNTIL “SET” TURNS OFF
ZERO
VALUE
SPAN DIGIT
USING ZERO AND SPAN KEYS, SET BAUDRATE TO DESIRED VALUE
PRESS AND HOLD ZERO AND SPAN UNTIL “SET” TURNS ON
ZERO
VALUE
SPAN DIGIT
PRESS AND HOLD ZERO AND SPAN UNTIL “SET” TURNS ON PRESS AND HOLD ZERO AND SPAN UNTIL
ZERO VALUE
SPAN DIGIT
USING ZERO AND SPAN KEYS, SET STOP BIT TO 1 OR 2
PRESS ZERO OR SPAN TO SWITCH BETWEEN YES OR NO
ZERO VALUE
SPAN DIGIT
CAL
PPM
PRESS AND HOLD THE SPAN KEY FOR 5 SECONDS
CAL
SPAN DIGIT
DISPLAY READS “CAL” THEN “PASS” AND RETURNS TO HOME POSITION
PRESS AND HOLD ZERO AND SPAN UNTIL “SET” TURNS OFF
AUT
AUT
ZERO VALUE
SPAN DIGIT
SCROLL
PRESS AND HOLD ZERO AND SPAN UNTIL
BAU
K
PAR
RST
“SET” TURNS OFF
ZERO VALUE
SPAN DIGIT
PRESS ZERO OR SPAN TO SWITCH BETWEEN NO PARITY OR EVEN OR ODD PARITY
ZERO
VALUE
SPAN DIGIT
“SET” TURNS OFF
ZERO
VALUE
SPAN DIGIT
IF RESET IS SET TO YES, PRESSING ZERO AND SPAN WILL CAUSE A FACTORY RESET, AND DISPLAY WILL
ZERO
RETURN TO THE HOME POSITION
VALUE
IF RESET IS SET TO NO, PRESSING ZERO AND SPAN SPAN DIGIT
OK
IF THE SENSOR OUTPUT IS NO LONGER SUFFICIENT FOR CALIBRATION, THEN THE DISPLAY READS “BAD SEN”. THE SENSOR MUST BE REPLACED
SEN
AUT
AUT
PAR
PRESS AND HOLD ZERO AND SPAN UNTIL “SET” TURNS OFF
ZERO
VALUE
SPAN DIGIT
CAL
NOTES
__________________________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________________________
__________________________________________________________________________________________________________________________________________
Printed in U.S.A. 2/19 FR# 443872-00 Rev. 6©Copyright 2019 Dwyer Instruments, Inc.
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Phone: 219/879-8000
Fax: 219/872-9057
www.dwyer-inst.com
e-mail: info@dwyermail.com
Loading...