The Series FLMG is a anged electromagnetic owmetersfor
use in 4” to 10” pipe in municipal or industrial water and
wastewater applications where propeller meters have typically
been used in the past. Because the FLMG has no moving
parts and has electrodes designed to discourage fouling, this
magmeter performs well and requires much less frequent
maintenance in applications where debris or sand would
impede propeller meters. There is no rotor to stop turning
or bearings to wear out. Minimal straight pipe requirements
allow FLMG Series meters to be used in piping congurations
where there is little space between the meter and an elbow.
In chemical injection applications, the meter should be placed
upstream of the injection line or far enough downstream for
thorough mixing to occur before the meter.
Rate and total indication are standard on both models. Flow
measurement units are customer-selected and factory-set
and can only be changed in the eld by an authorized agent.
The Series FLMG is externally powered with 7-26 VDC at 30
mA max (see WARNING on Wiring Diagrams). Two Lithium
3.6V “AA” batteries provide backup during power failures,
allowing the meter to seamlessly continue recording ow rate
and total for the duration of the outage. Under intermittent
use, the battery life is approximately 10 years.
The 20-foot power cable also provides pulse output for use
with a variety of Dwyer Instruments Inc. and other displays
and controls for remote reading, data logging, pulse-toanalog conversion, and telemetry applications. An internal
data logger is also available for secure ow logging. Pulse
rate is customer-selected and factory-set and can only be
changed in the eld by an authorized agent. Default is high
frequency for use with 4 to20 mA signal conversion devices.
+/- 1% of reading for ow between 10% to 100% of max ow
+/- 2% of reading for ow from cutoff to 10% of max ow
Welded steel, epoxy-coated
Dual durometer rubber
Diecast aluminum, powder-coated
316 SS
Rate
5 8
Gallon/Minute, Liter/Minute, Liter/Second, Gallon, Gallon x 1000, Liter, Liter x 1000, Mega Liter,
Cubic Feet/Minute, Cubic Meter/Hour, Cubic Meter, Cubic Meter x 1000, Cubic Feet,
Million Gallon/Day, Mega Liter/Day Cubic Feet x 1000
7-32 Vdc at 30 mA max, with auxiliary battery for continuous operation during power failures
NOTE: Using an unregulated power supply >18 Vdc may damage the meter due to AC line input voltage uctuation
Current sinking pulse, opto-isolated, 30 Vdc at 10 mA max
High Frequency (default); 10 units/pulse; 100 units/pulse; 1000 units/pulse
where installation fault may expose the ow sensor to boiler pressure and temperature. Maximum
recommended temperature is 130˚ F.
Positioning the Meter. These meters can be installed
horizontally, vertically, and in any radial position.
Straight Pipe Recommendations. As with most flow
meters, the FLMG requires some straight pipe before and
after the meter for best accuracy. However, the ability of
electromagnetic meters to average the ow across the entire
pipe allows for shorter straight pipe recommendations than
most mechanical meters (see page 4).
Full Pipe Recommendations. All magmeters require a
method for determining that the pipe is empty, to prevent false
reading. This meter is designed to go to zero reading if one
or more electrodes is exposed. For highest accuracy, install
the meter so that the pipe will be full when there is ow. If air
bubbles may be present in the pipe or sludge accumulation
is an issue, rotate the meter by one ange hole to position
the control housing at a 45˚ angle (see diagrams on page 5).
EQUALIZATION AND GROUNDING
Metal Pipe Installations. To equalize the electrical potential
of the uid, the FLMG meter, and the surrounding pipe, secure
the ange plates (factory-installed on the equalization lug) to
both pipe anges at one of the bolt holes, as shown below.
Be sure the lockwasher ts between the pipe ange and the
ange plate.
Meter Flange
Pipe Flange
Lockwasher
Flange Plate
Equalization Lug
Metal
Pipe
Meter
Flange
Bolt
Pipe
Flange
Metal
Pipe
Equalization Diagram
Run wire from equalization lug to both pipe anges;
secure ange plates under bolt heads as shown.
Fittings. The FLMG anges have standard ANSI 150 lb drilling
and mate with any other ANSI 150 lb ange.
Calibration. The FLMG is factory-calibrated and will not require
any form of eld calibration.
Chemical Injection. When any magmeter, by any manufacturer, is used in a chemical injection application, the chemical
injection point must be placed downstream of the magmeter OR far enough upstream for complete mixing to occur
before the uid reaches the meter. When unmixed chemical
alternates with water passing through the meter, the rapid
changes in conductivity may cause sudden spikes and drops
in the meter’s reading, resulting in inaccurate measurement.
The magmeter will restabilize, however, with a steady ow of
uid of uniform conductivity.
Caution: In chemical injection applications, install chemical injection
point downstream of magmeter, or far
enough upstream to allow complete
mixing of uids before the meter.
WARNING: ELECTRICAL SHOCK HAZARD When
the meter is externally AC powered, the piping system must be grounded to meet national and local
electrical safety codes. Failure to do so can result
in electrocution.
Plastic Pipe Installations. When the FLMG is installed in a
plastic piping system, it is not necessary to use the equalization straps, but very important to ground the meter to avoid
electrical shock hazard and electrostatic interference with
meter function.
The FLMG operates on 8-32 VDC at 30 mA max external power
(see WARNING in wiring diagrams). The display reads “P” when
external power is in use (see illustration below).
The Lithium battery pack installed in the FLMG serves as
backup in the event of a power failure, when it will keep the
meter operating without interruption for the duration of the
outage. When battery power in is use, the FLMG display
continues to read out the rate and total, but the “P” indicating
external power is extinguished. When power resumes, the
FLMG will seamlessly return to normal power mode, and the
“P” will again display.
When used for occasional emergency backup, battery life is
approximately ten years.
Pulse Output. The FLMG cable also provides pulse output that
can be used for remote reading, 4-20 mA signal conversion,
datalogging, and telemetry applications. See page 7 for
connection diagrams to Dwyer Instruments Inc. controls and
displays.
OPERATION
Caution: There are no user-adjustable
connections or settings inside the display
housing. Use caution when opening the
housing for a battery change, to avoid
damage to internal components.
Display Reading. The FLMG display has two lines, the bottom
line for ow rate and the top line for accumulated total.
Measurement units are pre-ordered and factory-set and can
be changed in the eld only by an authorized individual.
Refer to the diagrams below to read your display.
Note: For data logger setup and operation, refer to Flow
Inspector Manual
Pulse rates are selected by the customer at time of order,
factory-set.Three pulse rates are possible: One pulse per ten
gallons (or liters), one pulse per thousand gallons (or liters), or
High Frequency (required for use with 4 to 20 mA converters;
see below):
The FLMG requires a power source of 8-32 VDC at 30 mA
max (see WARNING). The power cable also serves as a pulse
output if needed for remote reading, data logging, signal
conversion, or telemetry.
Series BAT/ Series FLMG
Cable Color Codes
Orange and Blue: Serial Output (Do Not Use)
Green (+) and White (-): Pulse Output, 30 Vdc max, 10 mA max
Red (+) and Black (-): External Power, 8-32 VDC at 30 mA max
Drain: Connect to earth ground (see WARNING)
WARNING: Using an unregulated power
supply >18 Vdc may damage the meter
due to AC line input voltage uctuation.
Series RTI/ Series FLMG
WARNING: Using an unregulated power
supply >18 Vdc may damage the meter
due to AC line input voltage uctuation.