Dwyer Instruments DM-008, DM-059, DM-052, DM-252, DM-201 User manual

...
Series DM DigiMag® Differential Pressure Transmitter
HIGH PRESSURE POR
[42.34]
Specications - Installation and Operating Instructions
T
1 [25.40]
LOW PRESSURE PORT
Bulletin P-DMT
The Series DM DigiMag® Differential Pressure Transmitter senses the pressure of air and compatible gases and sends a standard 4-20 mA output signal. The DM
housing is specically designed to mount in the same diameter cutout as a standard
Magnehelic
ranges. The polycarbonate molded housing features integral pressure connections, which reduces installation time. Digital push-button zero and span simplify calibration over typical turn-potentiometers. A single push-button allows eld selection of 4 to 6 engineering units, depending on the range.
BENEFITS/FEATURES
• Reduced installation time through zero and span controls that provides quick and
easy calibration
• Fast and easy setup and calibration with push-button zero and span controls
• Immediate corrective action can be taken by local alerts via the easy-to-read LCD display
• Reduces upgrade installation costs and simplies eld upgrade from a Magnehelic gage, as both use the same diameter cutout
APPLICATIONS
• Differential pressure across lters
• Fan control
• Static pressures in ducts or buildings
• Room pressurization monitoring
INSTALLATION Location:
Select a clean, dry mounting location free from excess vibration where the temperature will remain between -4 to 158°F (-20 to 70°C). Distance from the receiver is limited only by total loop resistance. See Electrical Connections on the next page. The tubing supplying pressure to the instrument can be practically any length required, but long lengths will increase the response time slightly.
®
gage. A wide range of models are available factory calibrated to specic
1/2 [12.70]
1-43/64
SPECIFICATIONS Service: Air and non-combustible, compatible gases. Wetted Materials: Consult factory. Housing Material: Polycarbonate. Accuracy: ±1% FSO for all ranges except 0.25 in w.c. @ ±2% FSO, and ranges at
or below ±0.1 in w.c. @ ±4% FSO.
Stability: < ±1% / year FSO. Pressure Limits: Ranges > 1 in w.c.: 6 psi max operation, 6 psi burst; Ranges ≤ 1
in w.c.: 3.6 psi max operation, 6 psi burst.
Temperature Limits: -4 to 158°F (-20 to 70°C). Thermal Effect: 0.036% FS/°C (0.02% FS/°F). Power Requirements: 10-35 VDC (2-wire). Output Signal: 4-20 mA (2-wire). Zero and Span Adjustments: Push-button. Loop Resistance: 0 to 1250 Ω max.
®
Current Consumption: 21 mA max. Electrical Connections: Screw-type terminals. Process Connections: Male ports on side for 1/8˝, 3/16˝, 1/4˝, 5 mm, 6 mm ID
exible tubing.
Enclosure Rating: NEMA 4X (IP66). Mounting Orientation: Not sensitive to position. Size: 5˝ OD (127 mm) x 1.9˝ (48 mm) deep. Weight: 7.04 oz (200 g). Agency Approvals: CE.
15/64 [5.84]
5 [127.00]
Position:
Transmitter pressure accuracy is not affected by orientation. If choosing a non-vertical installation, ZERO the unit to remove any offset due to gravity.
Pressure Connections:
NOTICE
exible tubing. Be sure the pressure rating of the tubing exceeds that of the operating
ranges.
Find Quality Products Online at: sales@GlobalTestSupply.com
Two integral tubing connections are provided on the side of the
gage. They are sized to t 1/8˝, 3/16˝, 1/4˝, 5 mm, and 6 mm ID
www.GlobalTestSupply.com
MOUNTING
W
1-1/2 [38.10]
1 [25.40]
1500
Total Receiver Resistance Ω
0 5 10 13 15 20 25 30 35 40
Panel Mount:
Provide a 4-9/16˝ diameter opening in panel. Insert gage and secure in place with
provided screws and mounting lugs.
Wire Length
The maximum wire length connecting the transmitter to the receiver depends on the on the wire gage and the resistance of the receiver. When calculating loop resistance,
wiring should not contribute more than 10% of the receiver resistance. For runs over
1000´, choose a receiver with greater resistance. When wiring length is less than 100´,
22 AWG wire can be used.
2-Wire Operation
An external power supply delivering 10-35 VDC with minimum current capability of 40 mA DC (per transmitter) must be used to power the control loop. See Figure 4 for connection of the power supply, transmitter, and receiver. The range of appropriate receiver load resistance (RL) for the DC power supply voltage available is expressed by the formula and graph in Figure 5. Shielded two wire cable is recommended for control loop wiring. If grounding is required, use the negative side of the control loop
after the receiver.
Figure 1: Panel mount
Surface Mount:
Provide three 3/16˝ diameter holes in panel on a 4-1/8˝ diameter bolt circle. Cut an
opening for the terminal block as shown in Figure 2.
1 [25.40]
[3] HOLES FOR #6 SCRE EQUALLY SPACED ON 4-1/8 [104.78] B.C.
+
SERIES DM PRESSURE
TRANSMITTER
SELECT UNIT OF MEASUREMENT
To select a unit of measurement, press and release the UNITS button to cycle through the available options. The LCD will display the current selected unit.
-
1400 1300 1200 1100 1000
900 800 700 600 500 400 300 200 100
+-
RECEIVER
Figure 4
Maximum Value (1250)
Vps–10.0
R Max. =
L
20mA DC
Operating
Region
50
Figure 5
+
-
POWER SUPPLY
10-35 VDC
1 [25.40]
Figure 2: Surface mount
ELECTRICAL CONNECTIONS
CAUTION
not designed for 120 or 240 V AC line operation.
Electrical connections are made to the terminal block located in the back of the transmitter. Terminals are marked + and COM (see Figure 3 below).
Do not exceed specied supply voltage ratings, as doing so will result in permanent damage not covered by warranty. This unit is
Figure 3
Find Quality Products Online at: sales@GlobalTestSupply.com
www.GlobalTestSupply.com
CALIBRATION
To calibrate the transmitter you will need three pieces of equipment:
1. A calibrated pressure source capable of generating a stable pressure value for
the maximum range of the unit under test
2. An instrument capable of validating the calibration pressure
3. An ammeter capable of measuring the current mA output from the unit under test
The transmitter is calibrated using the following procedure.
MAINTENANCE
Upon nal installation of the Series DM, no routine maintenance is required. The Series DM is not eld serviceable and should be returned if repair is needed. Field repair should not be attempted and may void warranty.
This symbol indicates waste electrical products should not be disposed of with household waste. Please recycle where facilities exist. Check with your Local Authority or retailer for recycling advice.
Preparing for Zero Calibration, Span Calibration, Response Time Calibration, or Restore Factory Calibration Coefcients
To prepare the unit for zero or span calibration, response time calibration, or to restore factory calibration coefcients, start by preparing the unit as instructed below:
1. Connect the ammeter and power supply, being careful to observe polarities.
2. Press both the ZERO and UNITS buttons simultaneously for 6 or more seconds, or until “CAL” is displayed. Release both buttons.
3. The units indicator on the LCD should blink on and off. This indicates the gage is ready for calibration or restoration of coefcients. The unit’s indicator will blink for approximately 10 minutes, then stop blinking.
Zero Calibration
• Apply zero pressure to both ports.
• Press the zero button for 3 seconds. Release.
• The zero function will be processed 3 seconds after the button is released.
• The display will read “2Er” and then sequence back to the home display.
Span Calibration
NOTICE
The span calibration function allows the pressure value to be adjusted so that the
currently applied pressure is the maximum congured pressure. This will in turn set the maximum analog output at the set pressure. It is recommended that the ZERO
function be applied before performing a span calibration.
• Apply the maximum desired pressure to the device.
• Press and hold the UNITS button for 3 seconds.
• The span function will be processed 3 seconds after the span button is released.
• The display will read “SPA” and then sequence back to the home display.
Response Time Calibration
Press both the “ZERO” and “UNITS” buttons simultaneously for 3 seconds to toggle between fast (0 seconds) and dampened (4 seconds) response. The display will read FST or SLO to indicate which mode is now selected.
For a positive span, apply pressure to the positive “+” port.
WARRANTY/RETURN
Refer to “Terms and Conditions of Sale” in our catalog and on our website. Contact customer service to receive a Return Materials Authorization (RMA) number before shipping the product back for repair. Be sure to include a brief description of the problem plus any additional application notes.
MODEL CHART Model Range Model Range DM-001 DM-002 DM-003 DM-004 DM-005 DM-007 DM-008 DM-019 DM-201 DM-202 DM-203
0.1 in w.c.
0.25 in w.c.
0.5 in w.c. 1 in w.c. 2 in w.c. 3 in w.c. 5 in w.c.
-0.05-0-0.20 in w.c. ±0.1 in w.c. ±0.25 in w.c. ±0.5 in w.c.
DM-052 DM-053 DM-056 DM-059 DM-252 DM-253 DM-256 DM-259 DM-082 DM-282
30 Pa
60 Pa
250 Pa 1250 Pa ±30 Pa
±60 Pa
±250 Pa ±1250 Pa
6 mm w.c. ±6 mm w.c.
Restore Factory Calibration
To restore the gage’s factory calibration coefcient:
• Press both the “ZERO” and “UNITS” buttons simultaneously for 6 seconds or until “rSt” is displayed.
• The device will reboot after 5 or 6 seconds.