Dwyer Instruments DM-2000 Operating Manual

Series DM-2000 Differential Pressure Transmitter
(38.10)
®
Specications - Installation and Operating Instructions
HIGH PRESSURE PORT
1-1/4
[31.75]
LOW PRESSURE PORT
7/16
[11.11]
17/32
[13.50]
1-11/16
[42.86]
5/32
[3.97]
Bulletin E-43-DM
ø4-3/4
[120.65]
The Dwyer Series DM-2000 Differential Pressure Transmitter senses the pressure of air and compatible gases and sends a standard 4-20 mA output signal. The DM-
2000 housing is specically designed to mount in the same diameter cutout as a
standard Magnehelic
calibrated to specic ranges.
Pressure connections are inherent to the glass lled plastic molded housing making installation quick and easy. Digital push-button zero simplies calibration over typical turn-potentiometers. Single push button allows eld selection of 5 engineering units (LCD models only). An optional 3.5 digit LCD shows process and engineering.
Accessories
Mounting Lugs
6-20 x 2˝ Screws - 3 6-19 x 1/2˝ Screws - 3
INSTALLATION
1. Location
Select a clean, dry mounting location free from excess vibration where the temperature will remain between 20 and 120˚F (-6.7 and 48.9˚C). Distance from the receiver is limited only by total loop resistance. See Electrical Connections on next page. The tubing supplying pressure to the instrument can be practically any length required, but long lengths will increase response time slightly.
2. Position
A vertical position required. That is the position in which all standard models are
spanned and zeroed at the factory.
Pressure Connections
Two integral tubing connections are provided on the side of the gage. They are sized to t 1/8˝ (3.12 mm) I.D. tubing. Be sure the pressure rating of the tubing exceeds that
of the operating ranges.
Note: The tubing connections on the back of the gage are not to be used as process
connections.
3. Mounting
Panel - Provide a 4-9/16˝ diameter opening in panel. Insert gage and secure in place
with provided screws and adapters.
Surface - Provide three 3/16˝ diameter holes in panel on a 4-1/8˝ diameter bolt circle. Cut opening for terminal block as shown in diagram to right.
®
SPECIFICATIONS Service: Air and non-combustible, compatible gases. Wetted Materials: Consult Factory. Accuracy: ±1% F.S. at 70°F. Stability: ±1% F.S./yr. Temperature Limits: 20 to 120°F (-6.67 to 48.9°C). Pressure Limits: 10 psig (0.69 bar). Thermal Effect: ±0.055% F.S./°F (0.099% F.S./°C). Power Requirements: 10-35 VDC (2 wire). Output Signal: 4 to 20 mA. Zero and Span Adjustments: Digital push-button zero and span. Loop Resistance: DC: 0-1250 ohms maximum. Current Consumption: DC: 38 mA maximum. Electrical Connections: Screw-type terminal block. Process Connections: 1/8˝ I.D. tubing. Mounting Orientation: Vertical. Weight: 4.8 oz (136 g).
Panel
Surface
11/16
(17.46)
65.000°
1
(25.40)
(3) HOLES FOR #6 SCREW EQUALLY SPACED ON
1-1/2
4-1/8 (104.78) B.C.
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Phone: 219/879-8000
Fax: 219/872-9057
www.dwyer-inst.com
e-mail: info@dwyermail.com
ELECTRICAL CONNECTIONS
1500
Total Receiver Resistance ()
0 5 10 13 15 20 25 30 35 40
CAUTION: Do not exceed specied supply voltage ratings. Permanent damage not covered by warranty will result. This unit is not designed for 120 or 240 volts AC line
operation.
Electrical connections are made to the terminal block located in back of the transmitter. Terminals are marked + and - (see Fig. B below).
Figure B
Wire Length
The maximum length of wire connecting transmitter and receiver is a function of wire
size and receiver resistance. Wiring should not contribute more than 10% of the receiver resistance to total loop resistance. For extremely long runs (over 1000 feet), choose receivers with higher resistance to minimize size and cost of connecting leads. Where wiring length is under 100 feet, hook-up wire as small as 22 AWG can be used.
2-Wire Operation
An external power supply delivering 10-35 VDC with minimum current capability of 40 mA DC (per transmitter) must be used to power the control loop. See Fig. C for connection of the power supply, transmitter and receiver. The range of appropriate receiver load resistance (RL) for the DC power supply voltage available is expressed by the formula and graph in Fig. D. Shielded two wire cable is recommended for control loop wiring. If grounding is required, use the negative side of the control loop
after the receiver.
2-Wire Connections
SERIES DM-2000
PRESSURE
TRANSMITTER
1
2
RECEIVER
Figure C
mA
POWER SUPPLY
10-35 VDC
USER CALIBRATION
The transmitter may be user calibrated with two buttons on the front. The standard models have buttons labeled “ZERO” and “SPAN”. LCD models have buttons labeled “ZERO” and “UNITS”. The “UNITS” button on the LCD models has 2 functions. If pushed for less than 2 seconds and released the pressure units that are displayed on the LCD will change when the button is released. If pushed and held for 4 - 5 seconds the “UNITS” button serves the same function as the “SPAN” button on the standard
models.
To calibrate the transmitter you will need three pieces of equipment. You will need
a calibrated pressure source capable of generating a stable pressure value for the maximum range of the unit under test, an instrument capable of validating the calibration pressure, and an ampmeter, capable of measuring mA, to measure the current output from the unit under test. The transmitter is calibrated using the following procedure.
Preparation – Connect the ampmeter and power supply, being careful to observe
polarities. The transmitter must be calibrated in a vertical position.
Performing ZERO Calibration, SPAN Calibration or Restore Factory Calibration Coefcients:
1. Press both the ZERO and UNITS/SPAN buttons simultaneously for 6 or more seconds. Release both buttons. The units indicator on the LCD should blink on and off. This indicates the gage is ready for calibration or restoration of coefcients. The units indicator blinks for approximately 10 minutes, then stops blinking.
2. a) ZERO calibrate the gage by applying no pressure to the gage and then pressing the ZERO button for 3 seconds. b) SPAN calibrate the gage by applying full-scale pressure to the gage and then pressing the UNITS/SPAN button for 3 seconds. c.) Restore the gage’s factory calibration coefcient by pressing both the ZERO and UNITS/SPAN buttons simultaneously for 3 seconds.
MAINTENANCE
Upon nal installation of the Series DM2000 Differential Pressure Transmitter and
the companion receiver no routine maintenance is required. The Series DM2000
Transmitter is not eld serviceable and should be returned, freight prepaid, to the factory if repair is required. Please enclose a description of the problems encountered plus any available application information.
This symbol indicates waste electrical products should not be disposed of with household waste. Please recycle where facilities exist. Check with your Local Authority or retailer for recycling advice.
Power Supply Voltage – VDC (2-wire)
1400 1300 1200 1100 1000
900
R Max. =
L
800 700 600 500 400 300 200 100
50
©Copyright 2019 Dwyer Instruments, Inc. Printed in U.S.A. 2/19 FR# 443402-00 Rev. 5
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Vps–10.0 20mA DC
Figure D
Maximum Value (1250 )
Operating
Region
Phone: 219/879-8000
Fax: 219/872-9057
dwyer-inst.com
e-mail: info@dwyermail.com
Loading...