The SERIES DH Digihelic® Differential Pressure Controller is a 3-in-1 instrument
possessing a digital display gage, control relay switches, and a transmitter with current
output. The Digihelic
applications, achieving a 0.5% full scale accuracy on ranges from 0.25 to 100 in w.c.
The Digihelic
operation in several commonly used engineering units. Two SPDT control relays with
adjustable dead bands are provided along with a scalable 4-20 mA process output.
The Series DH provides extreme exibility in power usage by allowing 120/220 VAC
and also 24 VDC power which is often used in control panels.
Programming is easy using the menu key to access 5 simplied menus which provide
access to: security level; selection of pressure, velocity or ow operation; selection of
engineering units; K-factor for use with ow sensors; rectangular or circular duct for
inputting area in ow applications; set point control or set point and alarm operation;
alarm operation as a high, low or high/low alarm; automatic or manual alarm reset;
alarm delay; view peak and valley process readings; digital damping for smoothing
erratic process applications; scaling the 4-20 mA process output to t your application’s
range; Modbus
FEATURES/BENEFITS
• 3-in-1 instrument allows the reduction of several instruments with one product,
saving inventory, installation time and money
• Velocity of ow modes, a square root output coincides with the actual ow curve for
greater precision
• Power usage of 120/220 VAC or 24 VDC provides exibility to incorporate device in
control panel
• Secure menu program provides access to device operation only for the right skill
level
• Modbus® communications supports Process and HVAC system integration and
control
APPLICATIONS
• SCFM duct ow
• Industrial ovens air ow
• Filter status
• Clean room pressurization
• Fume hood air ow
• Surgical and medical room pressurization
• Damper and fan control
OPTIONS
To order add sufx: Description
-B
-NIST
Example: DH-004-NIST
-FC Factory calibration certicate
Example: DH-004-FC
MODEL CHART - AVAILABLE PRESSURE ENGINEERING UNITS
Model in w.c. ft w.c. mm w.c. cm w.c. psi in Hg mm Hg mbar Pa kPa hPa oz/in
DH-002
DH-004
DH-006
DH-007
DH-008
DH-009*
DH-010*
*Velocity and volumetric ow not available on bi-directional range units and models DH-009 & DH-010.
®
controller is the ideal instrument for pressure, velocity and ow
®
controller allows the selection of pressure, velocity or volumetric ow
®
communications; and eld calibration.
Barbed tting for 3/16˝ ID tubing
NIST traceable calibration certicate
.2500
-
1.000
5.000
10.00
25.00
50.00
100.0
.4167
.8333
2.083
4.167
8.333
6.350
25.40
127.0
254.0
635.0
1270
2540
0.635
2.540
12.70
25.40
63.50
127.0
254.0
-
-
.1806
.3613
.9032
1.806
3.613
-
-
.3678
.7356
1.839
3.678
7.356
0.467
1.868
9.342
18.68
46.71
93.42
186.8
0.623
2.491
12.45
24.91
62.27
124.5
249.1
62.28
249.1
1245
2491
6227
-
-
SPECIFICATIONS
Service: Air and non-combustible, compatible gases.
Wetted Materials: Consult factory.
Housing Material:
Accuracy: ±0.5% at 77°F (25°C) including hysteresis and repeatability.
Stability: < ±1% per year.
Pressure Limits: Ranges ≤ 2.5 in w.c. = 2 psi; 5˝: 5 psi; 10˝: 5 psi; 25˝: 5 psi; 50˝: 5
psi, 100˝: 9 psi.
Temperature Limits: 32 to 140°F (0 to 60°C).
Compensated Temperature Limits: 32 to 140°F (0 to 60°C).
Thermal Effects: 0.020%/°F (0.036/°C) from 77°F (25°C).
Power Requirements: High voltage power = 100 to 240 VAC, 50 to 400 Hz or 132
to 240 VDC. Low voltage power = 24 VDC ±20%.
Power Consumption: Low voltage power = 24 VDC - 130 mA max; High voltage
power = 100 to 240 VAC, 132 to 240 VDC - 7VA max.
Output Signal: 4-20 mA DC into 900 Ω max.
Zero & Span Adjustments: Accessible via menus.
Response Time: 250 ms.
Display: 4 digit LCD 0.4˝ height. LED indicators for set point and alarm status.
Electrical Connections: Screw terminals.
Process Connections:
(3.175 mm ID x 6.35 mm OD). Optional barbed tting for 3/16˝ ID tubing.
Enclosure Rating: Face designed to meet NEMA 4X (IP66).
Mounting Orientation: Mount unit in horizontal plane.
Size: 1/8 DIN.
Panel Cutout: 1.772 x 3.620 in (45 x 92 mm).
Weight: 14.4 oz (408 g).
Serial Communications: Modbus
Agency Approvals: CE, UL.
SWITCH SPECIFICATIONS
Switch Type:
Electrical Rating: 8 amps at 240 VAC resistive.
Set Point Adjustment: Adjustable via keypad on face.
ACCESSORIES
Model Description
MN-1
A-266
A-203
Digihelic Links
-
0.623
2.491
12.45
24.91
62.27
124.5
249.1
0.144
0.578
2.890
5.780
14.45
28.90
57.80
0.249
1.245
2.491
6.227
12.45
24.91
ABS plastic, UL approved 94 V-0.
Compression tting for use with 1/8˝ ID X 1/4˝ OD tubing
®
RTU, RS485, 9600 baud.
2 SPDT relays.
Mini-Node™ USB/RS-485 converter; the Mini-Node™
converters are an easy solution for utilizing the
®
controller’s RS-485 serial communication
Digihelic
and connecting to virtually any PC.
®
surface mounting bracket
Digihelic
1/8˝ ID x 1/4˝ OD PVC tubing
™
Communications Software
MODEL CHART - BI-DIRECTIONAL* RANGES
Model Range
DH-012
2
DH-014
DH-015
DH-016
DH-017
*Velocity and volumetric ow not available on
bi-directional range units and models DH-009 &
DH-010.
Modbus
Process Tubing Options: See page 489 (Gage Tubing Accessories)
0.25 to 0 - 0.25 in w.c.
1.0 to 0 - 1.0 in w.c.
2.5 to 0 - 2.5 in w.c.
5 to 0 - 5 in w.c.
10 to 0 - 10 in w.c.
®
is a registered trademark of Schneider Automation, Inc.