Series DH Digihelic®Differential Pressure Controller
Specifications - Installation and Operating Instructions
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
1.800.868.7495
QualityInstruments-Direct.ca
1
DIMENSIONS
1-3/4
[44.45]
4-1/2
[114.30]
1/2
[12.70]
4-1/2
[114.30]
3-19/32
[91.28]
1-15/16
[49.21]
3-25/32
[96.04]
Face Designed to Meet NEMA 4X (IP66)
PANEL CUT OUTS
Horizontal
3.620 in. + 0.032 - 0.0 (92.00 mm + 0.8 - 0.0)
1.772 in. + 0.024 - 0.0 (45.00 mm + 0.6 - 0.0)
1.800.868.7495
QualityInstruments-Direct.ca
2
SPECIFICATIONS Service: Air and non-combustible, compatible gases. Wetted Materials: Consult factory. Housing Material: ABS plastic, UL approved 94-V-0. Accuracy: ±0.5% at 77°F (25°C) including hysteresis and repeatability (after 1 hour
warm-up).
Stability: < ±1% per year. Pressure Limits: Ranges 2.5 in. w.c. = 2 psi
5˝: 5 psi; 10˝: 5 psi; 25˝: 5 psi; 50˝: 5 psi; 100˝: 9 psi.
Temperature Limits: 32 to 140°F (0 to 60°C). Compensated Temperature Limits: 32 to 140°F (0 to 60°C). Thermal Effects: 0.020%/°F (0.036/°C) from 77°F (25°C). Power Requirements:
High Voltage Power = 100 to 240 VAC, 50 to 400 Hz or 132 to 240 VDC. Low Voltage Power = 24 VDC ±20%.
Power Consumption:
Low Voltage Power = 24 VDC - 130 mA max. High Voltage Power = 100 to 240 VAC, 132 to 240 VDC - 7VA max.
Output Signal: 4-20 mA DC into 900 ohms max. Zero & Span Adjustments: Accessible via menus. Response Time: 250 ms (dampening set to 1). Display: 4 digit LCD 0.4˝ height LED indicators for set point and alarm status. Electrical Connections: Screw terminals. Process Connections: Compression fitting for use with 1/8˝ ID tubing x 1/4˝ OD
tubing (3.175 mm ID x 6.35 mm OD).
Enclosure Rating: Face designed to meet NEMA 4X (IP66). Mounting Orientation: Mount unit in horizontal plane. Size: 1/8 DIN. Panel Cutout: 1.772 x 3.620 in (45 x 92 mm). Weight: 14.4 oz (408 g). Serial Communications: Modbus® Protocol RTU, RS485, 9600 Baud. Agency Approvals: UL Listed, CUL Listed File No. E83725
CE EMC and Low Voltage Directives:
EN61000-4-2 EN61000-4-3* EN61000-4-4 EN61000-4-5 EN61000-4-6 EN61000-4-11 EN55011 EN601010
* Models DH-001 through DH-004, DH-011 through DH-014 pass criteria B. All others pass criteria A.
Switch SPECIFICATIONS Switch Type: 2 SPDT relays. Electrical Rating: 8 Amps at 240 VAC resistive. Set Point Adjustment: Adjustable via keypad on face.
1.800.868.7495
QualityInstruments-Direct.ca
3
WIRING
2020
1919
1818
1717
1616
1515
1414
1313
1111
1212
1010
9 8
7
6
5
4
3
2
1
21
21
2222
2323 2424
C
C
N/CN/C
N/CN/C
N/ON/O
N/O
N/O
SP1 RELAY
SP1 RELAY
SP2 OR ALARM RELAY
SP2 OR ALARM RELAY
3/8A 250VAC MEDIUM LAG
3/8A 250VAC MEDIUM LAG
100-240 VAC or 132-240 VDC POWER
100-240 VAC or 132-240 VDC POWER
NOTE1NOTE1
A
B
_
+
RS485 SERIAL COMMUNICATION
RS485 SERIAL COMMUNICATION
_
+
24 VDC POWER24 VDC POWER
REMOTE RESET SWITCH
REMOTE RESET SWITCH
NOTE 1
NOTE 1
4-20mA transmitter output
4-20mA transmitter output
Device receiving 4-20mA signal. Check specifications of this device for input load resistance. Typical 250 to 600 OHMS, 900 OHMS maximum
signal. Check specifications of this device for input load resistance. T 600 OHMS, 900 OHMS maximum
_
_
+
+
_
+
High Pressure PortHigh Pressure Port
Low Pressure Port
Low Pressure Port
NOTES:
1. The instrument may be powered from the AC line or 24 VDC. Do not wire AC line terminals 4-5 and 24 VDC terminals 14-15 at the same time or damage to the unit will result.
2. For supply connections, wire in accordance with an equivalent national standar d or code. Use copper conductors only rated for at least 75°C.
3. Terminals 11-15, 18 and 20 are rated CLASS 2.
4. ISOLATION:
Relays - 1500 VAC to all other inputs and outputs. AC Line Power (terminals 4-5) - 1500 VAC to all other inputs and outputs. RS485 output - 500 VAC to all other CLASS 2 wiring. The 24 VDC Power, 4-20 mA transmitter, and Remote Reset Switch share a common ground.
5. The Remote Reset Switch must be a dry contact switch.
6. Shielded cable is required for RS485 wiring.
WIRING
WARNING
If Digihelic®is powered by 24 VDC, the device receiving the 4-20 mA transmitter output MUST NOT share a common ground with the 24 VDC supply or damage to the Digihelic®will result.
1.800.868.7495
QualityInstruments-Direct.ca
4
It is not necessary to remove the control chassis from the housing for installation. If the control chassis is removed from the housing, you must follow industry standard practice for control and protection against Electro-Static Discharge (ESD). Failure to exercise good ESD practices may cause damage to the control.
Wiring to housing terminals while chassis is removed may cause dis­tortion of the internal connector and possible damage to the connec­tor when the chassis is reinstalled. It is strongly recommended that the control housing be wired with the chassis installed.
INSTALLATION
Mount the instrument in a location that will not be subject to excessive temperature, shock or vibration. All models are designed for mounting in an enclosed panel.
Select the position desired for the instrument on the panel. Prepar e the panel by cut­ting and deburring the required opening.
From the front of the panel, slide the instrument through the cut out. The housing gasket should be against the housing flange before installing.
From the rear of the panel slide the mounting collar over the housing. Hold the hous­ing with one hand and using the other hand, push the collar evenly against the panel until the springs are compressed. The ratchets will hold the mounting collar and housing in place.
C
20
20
19
19
18
18
17
17
16
16
15
15
14
14
13
13
111112
12
10
10
9 8
7
6
543
2
1
21
21
22
22
23
23
24
24
20
20
19
19
18
18
17
17
16
16
15
15
14
14
13
13
111112
12
10
10
9 8
7
6
543
2
1
21
21
22
22
23
23
24
24
20
20
19
19
18
18
17
17
16
16
15
15
14
14
13
13
111112
12
10
10
9 8
7
6
543
2
1
21
21
22
22
23
23
24
24
_
_
_
+
+
+
SHIELD
SHIELD
SHIELD
SHIELD
TIE SHIELD TO EARTH GROUND
TIE SHIELD TO EARTH GROUND
TO RS232 TO RS485 CONVERTER
TO RS232 TO RS485 CONVERTER
120 OHM RESISTOR
120 OHM RESISTOR
LAST UNIT ON RS485 BUSS
LAST UNIT ON RS485 BUSS
WIRE NUT
WIRE NUT
- RS485 WIRING TO DAISY CHAIN INSTRUMENTS ON THE
RS485 BUSS
UP TO 128 UNITS MAY BE DAISY CHAINED
THE 120 OHM RESISTOR IS USUALLY ONLY NECESSARY FOR LONG WIRE RUNS.
THE 120 OHM RESISTOR IS USUALLY ONLY NECESSARY FOR LONG WIRE RUNS.
DIGIHELIC® CONTROLER RS485 WIRING
1.800.868.7495
QualityInstruments-Direct.ca
5
SP1
SP1
SP2
SP2
ALHI
ALHI
ALLO
ALLO
SP/AL
SP/AL
RST
RST
MENU
MENU
E
X1K
X1K
MULTIPLIER DESCRIPTOR
MULTIPLIER DESCRIPTOR
VISIBLE WITH S
VISIBLE WITH SO
ME VELOCITY
ME VELOCITY
AND FLOW RANGE
AND FLOW RANGE
FRONT PANEL
FRONT PANEL
PRESSURE VALUE
PRESSURE VALUE
UNITS
UNITS
ALARM
ALARM
DESCRIPTOR
DESCRIPTOR
SP2 DESCRIPTOR
SP2 DESCRIPTOR
SP1 DESCRIPTOR
SP1 DESCRIPTOR
SP/ALSP/AL
8/25/03
SP/AL
MENUMENU
8/25/03
SP/AL
MENU
8/25/03
SP/AL
MENU
8/25/03
SP/AL
MENU
E
8/25/03
SP/AL
MENU
E
RSTRST
8/25/03
HOME POSITION FUNCTION
Sequences the display
through SET POINT and
ALARM settings
Allows access to the
menus
Displays full scale
range of unit
Clears or resets an Alarm
(alarm set for manual
reset)
MAIN MENU FUNCTION
Return to home
position
Return to home
position
Sequences through
menus
Sequences through
menus
Enter into SUB MENU
SUB MENU FUNCTION
Return to home position
Return to previous menu
Increments a value
Decrements a value
Changes a value or
setting. Press ENTER
and display will blink.
Adjust with UP or DOWN
arrows. Press ENTER to
store. Display will stop
blinking.
Peak/Valley SUB
MENU resets display to
present value.
SP/AL
MENU
UP
ARROW
DOWN
ARROW
ENTER
RESET